-14-
VFI 1000 TGS
2*Schuko
3*C13
VFI 2000 TG
4*Schuko
4*C13
VFI 2000 TGS
2*1*C13
6*C13
VFI 3000 TG
4*Schuko
4*C13+1*C19
VFI 3000 TGS
2*1*C19
3*C13+Terminal
block
(3) Battery Input Connection for long backup time model
When connecting the external batteries it
’
s recommended to pay
attention to these following items:
★
Use the battery pack with voltage:
24VDC for 1000 TG(S) (2 pcs of 12V batteries),
48VDC for 2000 TG(S) (4 pcs of 12V batteries),
72VDC for 3000 TG(S) (6 pcs of 12V batteries)
Note: Connection of batteries more than or less than required will
cause abnormality or permanent damage.
★
One Standard type battery connector on the rear panel is used for
connecting the battery pack.
★
The battery connection procedure is very important. Any incompliance
may result in the risk of electric shock. Therefore, the following steps
must be strictly complied with.
★
Prepare the battery cable with Standard type connector which should
be able to carry the current.
★
If there is a battery breaker then turn it off first. Then connect the
battery cable to the Standard type battery connector on the real panel.
★
Connect the input power cord of the UPS to mains power supply, the
battery would start to be charged.
Содержание VFI 1000 TG
Страница 1: ...USER MANUAL PowerWalker VFI 1000 2000 3000 TG VFI 1000 2000 3000 TGS ...
Страница 11: ... 8 UPS Block Diagram ...
Страница 39: ... 36 Appendix Rear panel 1000 TG S Back View of Schuko 2000 TG S Back View of Schuko ...
Страница 40: ... 37 3000 TG S Back View of Schuko 1000 TG S Back View of IEC ...
Страница 41: ... 38 2000 TG S Back View of IEC 3000 TG S Back View of IEC 11 04 2016 614 02071 00 ...