17
EN
1/2/4/6/8: setting the charger maximum current
1/2/4/6/8 in Ampere. (Default: 2A)
Note: Please set the appropriate charger current based on
battery capacity used. The recommended charging current
is 0.1C~0.3C of battery capacity as following table for
reference.
Battery capacity(AH)
Total charging current (A)
7~20
2
20~40
4
40~60
6
60~80
8
80~100
10
100~150
12
14: Charger boost voltage setting
Interface
Setting
Parameter 2: Set up the charger boost voltage.
2.25-2.40: setting the charger boost voltage from 2.25
V/cell to 2.40V/cell. (Default: 2.36V/cell)
15: Charger float voltage setting
Interface
Setting
Parameter 2: Set up the charger float voltage.
2.20-2.33: setting the charger float voltage from 2.20
V/cell to 2.33V/cell. (Default: 2.28V/cell)
16: EPO logic setting
Interface
Setting
Parameter 2: Set up the EPO function control logic.
AO: Active Open (Default). When AO is selected as EPO
logic, it will activate EPO function with Pin 1 and Pin 2 in
open status.
AC: Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
17: External output isolation transformer connection
Interface
Setting
Parameter 2: Allow or disallow external output isolation
transformer connection.
ENA: If selected, it’s allowed to connect to an external
output isolation transformer.
DIS: If selected, it’s not allowed to connect to external
output isolation transformer. (Default)
Содержание VFI 1000 RMG PF1
Страница 3: ......
Страница 29: ......
Страница 41: ...12 DE ...
Страница 43: ...14 DE ...
Страница 61: ......
Страница 89: ...RU Содержание TOC ...
Страница 90: ......
Страница 102: ...12 RU ...
Страница 104: ...14 RU ...