Step 4:
Please follow below steps to prepare battery cable with supplied
external battery connectors. The cable length should be prepared based on
the real distance between battery module and inverter module.
The recommended cable size is listed as below:
Wire Size
Cable mm2
1*4AWG
25
(a)
Loosen and disassemble the plug of the supplied battery connector.
(b)
Insert the battery cable through the tunnel and housing, and strip
battery cable 11.5±0.2mm.
11.5
±0.2
(c)
Crimp the cable and the plug with a proper crimping tool (ex.
hydraulic clamp) together into a hexagon shape as shown in below
chart. Then, move the housing toward plug and tighten them.
7.8
±0.1