53
A01-00134 Rev. A
NOTE 1:
If the UPS has been set to bypass output, it will bypass
voltage from the mains to output terminal even though the
user has turned off the UPS (inverter).
NOTE 2:
After turning off the UPS, please be aware that the UPS is
working in Bypass mode and there will be risk of power
loss for connected devices.
b.) In Bypass mode, output voltage of the UPS is still present. In
order to cut off the output, switch off the line input breaker. The
LCD display will turn off and UPS is now completely off.
8. Turn off the UPS without utility power supply in Battery mode
a.) Touch CONTROL and select Turn off UPS icon to turn off the
UPS. Refer to “UPS on/off” screen.
b.) Then UPS will cut off power to output terminals.
9. Mute the buzzer
a.) Touch SETTING and then select BASIC item. There are two
events available to mute. Refer to SETTING screen.
b.)
Some warning alarms cannot be muted unless the error is
fixed. Please refer to section 3-4 for details.
10. Operation in warning status
a.) When LCD screen shows “Fault Mode” and the buzzer beeps
once every second, it indicates that there are operational
problems. Users can read the warning message(s) from “DATA
LOG” menu. Please refer to the Section 3-3-6 for details.
b.)
Some warning alarms cannot be muted unless the error is
fixed. Please refer to Section 3-4 for details.