Enable:
Bypass enabled. Bypass mode is activated.
Disable:
Bypass disabled. There will be no output through the
bypass when manually turning off the UPS.
•
Bypass Voltage Range:
Set the bypass voltage range.
L:
Low voltage point for bypass. The setting range is 96V ~ 110V.
96V is default setting.
H:
High voltage point for bypass. The setting range is 130V ~ 146V.
146V is default setting.
•
Bypass FRE Range:
Set the bypass frequency range.
Th
e acceptable bypass frequency ranges from 46Hz to 54Hz when
UPS is 50Hz system and from 56Hz to 64Hz when UPS is 60Hz
system.
•
ECO mode:
Enable/Disable ECO mode. Default setting is “Disable”
•
ECO Voltage Range:
Set the ECO voltage range
.
L:
Low voltage point for ECO mode. The setting range is from
“Rated output voltage – 5V” to “Rated output voltage - 11V”. “Rated
output voltage – 5V” is default setting.
H:
High voltage point for ECO mode. The setting range is from
“Rated output v 5V” to “Rated output v 11V”. “Rated
output v 5V” is default setting.
•
ECO FRE Range:
Set the ECO frequency range. The setting range
is from 48Hz to 52Hz when the UPS is 50Hz system and from 58Hz
to 62Hz when the UPS is 60Hz system.