16

 

 

 

 

 

 

 

 

 

 

 

 

PN

: battery voltage to restart the inverter on DC mode     

  13.8V default, (Single: 12.6V, 12.8V, 13.0V, 13.2V, 13.4V, 

13.6V, 13.8V, 14.0V, 14.2V, 14.4V, can be set) 

F3

: Generator mode setting: 

Default  OFF  (ON  work  with  Gen.  \  OFF 
doesn’t work with Gen. ) 

F4

:  Unattended  mode  battery  lowest  voltage  to  power 

off power the inverter’s MCU. 

Default  single  section  8.0V  (8.0V,  8.2V,  8.5V,  8.7V, 

8.9V, 9.0V, 9.2V, 9.5V can be set) 

F5

: Fan failure detection settings: 

Default single block OFF (ON, OFF) 

F9

:  Auto restart from Overload condition: ON 

or OFF. The default is OFF. 

  Allows  the  inverter  to  restart  automatically 

after an Overload condition was detected. 

The  process  will  repeat  3  times  then  the 

Inverter goes OFF. 

Содержание ECO SW 10096

Страница 1: ...r more info please visit WARNING Pure Sine Wave INVERTER CHARGER WARNING INV CHR AC OFF 5s USE TO SCROLL UP DOWN DISPLAY SCREENS PROGRAMMING PAGES USE TO SCROLL UP DOWN INV MODE BAT MODE BAT PRIORITY MODE FREQUENCY LOAD WATTS BAT VOLT CHARGE INV OUTPUT POWER PROGRAMMING MODE Press for 5s to enter SET PAGES P1 to P9 PA to PN F3 to F9 See User Manual ON PAGE P0 Press for 3s to save and exit SET Push...

Страница 2: ...iring 5 4 1 Side and Front Panel 5 4 2 Battery Wiring 6 5 Leds Buttons and Display Description 7 6 Parameter Settings 10 7 Product Care and Maintenance 17 8 Fault Codes 18 8 1 Fault Codes Troubleshooting 18 8 2 Buzzer alerts 20 9 External Communication 20 10 WIFI Plug 21 11 Appendix 1 Technical Specs 23 12 General Installation Diagram 24 ...

Страница 3: ... transfer time Line to Inverter or Inv to Line makes the inverter suitable for backing up Computer or sensitive electronics devices There are four working modes to choose mains priority battery priority energy saving and unattended mode It has short circuit protection overvoltage and undervoltage protection overload protection overheat protection short circuit protection automatic restart wide inp...

Страница 4: ... loads are off to extend the battery backup time and to avoid unnecessary battery discharging 03 Battery priority mode The battery supply power to the load When the battery voltage is lower than the set battery voltage voltage set by PA the mains supply power to the load When the battery voltage is restored the battery will supply power to the load again charger is on or not depending on the PC se...

Страница 5: ...lly turn on But when the battery voltage is lower than the voltage set by F4 inverter will be turned off and will be turned ON only when the mains power returns or by hand In this mode the solar charger and the AC charger are combined to supply the charging current to the battery The main charger will be the Solar charger and the AC charger will supply the charging amps to reach the Max Charging a...

Страница 6: ...temperature environment water may condense Operate only if the device is dry otherwise there will be risk of electric shock 5 Please install the inverter near the main breaker box and where it is easy to unplug or disconnect it from the main power 6 The external battery should not be exposed to sun or water It is preferable to install it in a ventilated battery cabinet 7 The distance between the i...

Страница 7: ...ot the inverter may have output voltage turning off the inverter does not ensure that the internal parts don t have power About inductive loads when inductive load such a motor or AC compressor starts it demands up to three times its normal consumption Take this into consideration when dimensioning the inverter capacity ...

Страница 8: ...R AC OFF 5s USE TO SCROLL UP DOWN DISPLAY SCREENS PROGRAMMING PAGES USE TO SCROLL UP DOWN INV MODE BAT MODE BAT PRIORITY MODE FREQUENCY LOAD WATTS BAT VOLT CHARGE INV OUTPUT POWER PROGRAMMING MODE Press for 5s to enter SET PAGES P1 to P9 PA to PN F3 to F9 See User Manual ON PAGE P0 Press for 3s to save and exit SET Push 2 times to exit only SET CAUTION WARNING INV CHR AC ON LIN E OFF LIN E IN V ON...

Страница 9: ...Wiring 1 Battery wiring example 1 1 12V connection diagram 1 2 24V connection diagram WARNING Use the correct wires gauges according to the amount of Amps withdraw from the batteries and circulating through the wires ...

Страница 10: ...nd mains charging indicator When the inverter is working in Battery mode the light is solid ON when the charger is charging the batteries this light flashes and when the charge is completed the light turns OFF Red light When the overload is more than 105 the light flashes also when a Low Battery condition is detected If the overload is more than 110 the light is ON also when the inverter fails ...

Страница 11: ...urn the inverter OFF UP DOWN Buttons When the inverter is operating press UP or DOWN to check parameters on the display Inverter mode Output Voltage Mains mode battery capacity Reading this icon flashes when charging and stops when the charge is complete Frequency display flash Battery priority mode mains status mains icon will flash ...

Страница 12: ...10 Load display Load power display Overload display when icon flashes Battery display Battery voltage display Inverter total output power display Solar input with mains Solar input without mains flash ...

Страница 13: ...ng parameters At this time the working mode icon is not flashing and the parameter icon is flashing Press the UP button or the DOWN button to select the parameter to set press the SET button for 1S to enter the new parameter and exit from the parameter selection At this time the working mode icon flashes and the parameter icon does not flash Go back to P0 press the SET button twice to save the set...

Страница 14: ...d acid battery FLD flooded lead battery GEL gel battery LI lithium battery USE user mode default If user mode is selected adjust battery voltage in P3 and P4 menus If you do not select the USE user mode the P3 and P4 menus will not show P4 Battery voltage floating charge setting 12 9 13 8 single can be set P3 Battery voltage uniform charge setting Max voltage when charging before going to Float 13...

Страница 15: ...buzzer OFF Turn off the buzzer for DC Mode overvoltage under voltage overload over temperature conditions except faults conditions P7 Energy saving mode AC output setting 10 default can be adjusted up and down from 1 0 10 P8 Inverter output voltage setting 120V default 110V 115V 120V 130V P9 AC Output frequency setting 60Hz default 50Hz 60Hz ...

Страница 16: ...etting on Battery Priority mode on battery priority mode the battery voltage is restored and the inverter switches from city power to Inverting mod 13 2V default single battery 13 2V 13 3V 13 4V 13 5V 13 7V 13 9V 14 1V 14 4V PC mains charges or not If ON AC charge if OFF AC does not charge AUT the total current is given by the internal MPPT Charger plus the AC charger when working on solar priorit...

Страница 17: ... 135V 137 5V 140V 142 5V 145V PF AC input minimum frequency setting Default 45Hz 40Hz 41Hz 42Hz 43Hz 44Hz 45Hz PH AC input maximum frequency setting Default 63Hz 63Hz 64Hz 65Hz PL Battery low voltage shutdown setting 10 0V default Single 9 5V 9 6V 9 7V 9 8V 9 9V 10 0V 10 1V 10 2V 10 3V 10 4V 10 5V 10 6V 10 7V 10 8V 10 9V can be set ...

Страница 18: ...Unattended mode battery lowest voltage to power off power the inverter s MCU Default single section 8 0V 8 0V 8 2V 8 5V 8 7V 8 9V 9 0V 9 2V 9 5V can be set F5 Fan failure detection settings Default single block OFF ON OFF F9 Auto restart from Overload condition ON or OFF The default is OFF Allows the inverter to restart automatically after an Overload condition was detected The process will repeat...

Страница 19: ... battery it must be replaced early Batteries must be handled by professionals 7 4 It is not recommended to replace the battery individually replace them all When replacing you should follow the safety instructions 7 5 In high temperature areas the battery auto discharge in about two months and the charging time should be not be less than 10 hours Notes Before replacing the battery you must remove ...

Страница 20: ... Battery overvoltage Check the battery is broken or not E03 Buzzer rapid beep and the red light lighting Battery low voltage Check the battery is broken or not E04 Intermittent beeping and the red light off Transformer secondary line reverse connection Restart or contact the supplier E05 Intermittent beeping and the red light on Inverter startup failure Check if output is short circuited or overlo...

Страница 21: ...ed E12 E13 E14 Keep beeping red light off Fan open circuit Check the fan are not open circuit dropped E15 Input relay short circuit Tap the input relay to check it broken or not ES0 Displayed when press the controller display page Controller work well Controller work well ES3 Displayed when press the controller display page Controller over current Internal fault ES4 Displayed when press the contro...

Страница 22: ...ry is high voltage three sound every four seconds one long and two shorts 4 Overload 110 long sound 105 sound every two seconds 5 Temperature control failure 2 sound every 4 seconds 6 The temperature is too high sound every two seconds 7 Fan abnormality long sound 9 External communication OPTIONAL Support WIFI Plug RS232 USB and SNMP communication ...

Страница 23: ...21 ...

Страница 24: ...22 ...

Страница 25: ...23 ...

Страница 26: ...by a split phase transformer 120 240VAC NOT from a 3 phase transformer Contact your supplier for other alternatives Frequency 45 63Hz Mains mode 50 60Hz 1 Battery mode Voltage AC 110 120 2 Battery mode AC 80 95 135 145 V Mains mode AC 110 120 2 AC 220 230 240 2 Battery mode AC 110 120 15 V 230 240 15 V Mains mode Output waveform Pure sine wave Efficiency 85 Type of battery Any Lead Acid AGM GEL Li...

Страница 27: ...PPT solar controller Optional Current 10A 60A 12V 24 80V 48 150V 96V 280V PV Input Max 12V 22V 24 45V 48 75V 96V 145V MAX 12V 24 80V 48 150V 96V 280V MAX Input power max 12V 10A 120W 20A 240W 30A 360W 50A 600W 60A 720W 80A 960W 100A 1200W 120A 1440W MAX 24V 10A 240W 20A 480W 30A 720W 50A 1200W 60A 1440W 80A 1920W 100A 2400W 120A 2880W MAX 48V 10A 480W 20A 960W 30A 1440W 50A 2400W 60A 2880W 80A 384...

Страница 28: ...GENERAL INSTALLATION DIAGRAM ...

Страница 29: ......

Страница 30: ... 0 217 0 229 0 260 0 340 NOM VOLT DROP 0 138 0 145 0 153 0 174 0 229 WIRE LENGTH 10 FEET MODEL 1524 2024 2524 3024 3524 4024 1512 2012 2512 3012 WIRE GAUGE AWG 2 0 AWG 3 0 AWG 4 0 AWG 3 0 AWG 4 0 MAX VOLT DROP 0 206 0 273 0 288 0 330 0 430 NOM VOLT DROP 0 137 0 182 0 192 0 218 0 288 WIRE LENGTH 20 FEET MODEL 1524 2024 2524 3024 3524 4024 1512 2012 2512 3012 WIRE GAUGE AWG 2 0 AWG 3 0 AWG 4 0 AWG 3...

Страница 31: ...0V 120V 220V 230V INPUT BREAKER INVERTER 1500 12V 10 AWG 12 AWG 12 AWG 12 AWG 16 AWG 16 AWG 20 INVERTER 1800 24V 10 AWG 10 AWG 10 AWG 12 AWG 16 AWG 16 AWG 20 INVERTER 2000 24V 8 AWG 10 AWG 10 AWG 10 AWG 14 AWG 14 AWG 25 INVERTER 2500 24V 8 AWG 10 AWG 10 AWG 10 AWG 14 AWG 14 AWG 30 INVERTER 3000 24V 6 AWG 8 AWG 8 AWG 8 AWG 14 AWG 14 AWG 40 INVERTER 3600 24V 6 AWG 8 AWG 8 AWG 8 AWG 12 AWG 12 AWG 50 ...