11
Maintenance
The
controller
is
maintenance-free.
We
strongly
suggest
that
all
components
of
the
PV
system are
checked
at
least
annually,
Ensure
adequate
ventilation
of
the
cooling
element or body of the controller.
Check any
cable
strain
reliefs
Check
that
all
cable
connections
are
secure
Tighten
screws
if
necessary
Check and remove any terminal
corrosion
Error Messages
Caution! Please do not open the controller or attempt to replace components when troubleshooting. Improper
maintenance can be hazardous to the user and the system.
If the controller detects errors or unauthorized operating states, it shows error codes on the display. Error codes
can generally be differentiated, whether there is a temporary malfunction, e.g. regulator overload or a more
serious system error that can be remedied by appropriate external measures.
Since not all errors can be simultaneously displayed, the error with the highest error number (priority) is
displayed. If several errors are present, the second error code is displayed after remedying the more significant
error.
The
following
meaning
is
assigned
to
the
different
error
codes:
1.
Meaning:
Battery
polarities reverse
warning
Remedy: Reconnect
cable
of
battery
in
proper
way.
2.
Meaning:
Battery
is
wrong.
Remedy:
Check
battery
voltage
it
might
be
too
low
or
too
high. Recharge
battery
manually if necessary.
If
battery
can’t
be
recharged,
it
might
be
deeply discharged.
Replace battery if necessary.
3.
Meaning:
Module
current
too
high.
Remedy:
Reduce
the
load
current
or
module
power.
4.
Meaning:
Over
current
at
the
load
output.
Remedy:
Reduce
load current.
If reducing load current does not work, one of the two situations occurred:
1) No load connected, press “Enter” button, LCD showing E4.
2) If the load is over 50W, press “Enter” button, load current showing 0.00A.
Reset: Remove all connections in Reverse sequence from 6 to 1(as advised on page 6), then follow the reset
procedure:
i. While holding down the “Menu” button, connect the Battery terminals
ii. Release the “Menu” button; this will prompt the LCD to show “FFFF”
iii. First connect the PV then the Load terminals
NOTE:
Always connect the Negative first, then the Positive for all connections