4.2
Equalization Charging Mode (Automatic or Manual)
WARNING:
Equalization Charging is only for Wet-type Lead Acid Battery.
The Equalization Charging Voltage is factory pre-set to the Bulk V 1 Volt.
The battery manufacturer should be consulted. Clean, distilled water will need to be added to the
battery AFTER the equalization process.
4.2.1 Automatic Equalization Charging
Automatic Equalization charge is only available when battery voltage is higher than the Low
Voltage Disconnect (LVD) voltage , see 4.3.1.
To set Automatic Equalization Charging, set the dip switch 2 to OFF position
.
The PV Charge Controller will perform Equalization charging for 2 hours once every 30 days
During equalization charge , it can be stopped any time by pressing the Reset button
once and
the controller will return to the charging mode before the Equalization charge.
4.2.2 Manual Equalization Charging
Set the Night-Light Mode , dip switch 1 to off position.
P
ress and hold the Reset button for 10seconds and the equalization charge will go on for two
hour.
During equalization charge , it can be stopped any time by pressing the Reset button
once and
the controller will return to the charging mode before the Equalization charge.
4.3 12V DC Load Terminal – Control Mode
The 12V DC load terminal is designed for low power DC load such as street light.
It prevents over-discharging the battery and has 10 Night-Light timer programs.
4.3.1 Low Voltage Disconnect (LVD)
When the battery voltage is lower than the Low Voltage Disconnect (LVD) setting for 5
minutes, the LED will blink orange once every 2 seconds and the load will be cut off. After the
load is cut off, user can press the Reset button once to switch on the load for a grace period of
10 minutes for emergency purpose.
4.3.2 Low Voltage Reconnect (LVR)
When the battery voltage is higher than Low Voltage Reconnect (LVR) setting for 5 minutes, the
controller will automatically reconnect the load.
4.3.3 NIGHT-LIGHT Mode Programs
In the night-light mode, we have 10 selections.
To Activate the NIGHT-LIGHT Mode, switch the dipswitch 1 to ON position.
After activating, when the PV panel voltage is lower than 3.5V for 10 minute, the Controller will
turn on the light for a preset period of time according to the option selected.
When the PV panel voltage is higher than 3.5V for 10minute, the Controller will turn off the
light.
In NIGHT-LIGHT Mode, press and hold the Reset button can switch on the Light to test the
light.
P.8