Daily Controls :
Periodic Controls :
Yearly Controls :
Smoke Channels Cleaning :
These are the processes that the user must apply every day in season of everyday use. Please read and apply the
instructions and controls mentioned in ''Pre Control'' section of the manual for daily controls.
Care Instructions :
Boiler and burner controls are made in three programs.Daily (in everyday use ),periodic and yearly.
For efficient use, preventing the possible failures and optimum life of the boiler periodic controls are important.It is
recommended that periodical controls for the boiler must be made by once in every three months.These periodical controls
are made by rima technicians by applying following processes.
Boilers burning room and smoke channels check and cleaning if needed.
Leakage controls of water input - water output of the boiler and flue connections.
Valves check
Pumps check
Fuel filter control and cleaning if needed
Burning control (with eye).Burning and flame adjustments if needed.
Control of the liquid fuel sensor.Cleaning if needed.
Working and safety controls of burner and the boiler.
Sensor of the burner liquids tests.Cleaning or renewing if needed .
Working and safety controls of burner and the boiler.
Yearly controls of the boiler must be made by rima technicians before the season starts. Flue and flue lines must be cleaned
before calling technicians for yearly controls. In yearly controls rima technicians apply the following processes.
Situation and the leakproof of the sections and rope isolations controls.
Working pressure test for burning adjustment with the flue gas measurement system if needed.
Sensors and connection of the sensors test.
Boiler burning room and possible soot layers on smoke channels are checks and cleanings.
Connection and the leakproof of the boilers door test.
Leakproof of the connections of the boiler test.
Valves test for proper opening and closing.
Fuel filter test. Cleaning if needed.
Cleaning the Boiler :
The time period for cleaning service is variable according to the fuel type of the boiler and period of use.In boiler cleaning
operation ceramic ropes that isolate front door with front section and flue with back section must be controlled and must be
renewed if needed.
Before applying mentioned services to the boiler;electric must be cut off from the main switch,fuel valves must be closed,
control panel and the burner must be protected for avoiding any possible damage.
Because of the soot layer on heating surfaces, 100 °C increase on flue temperature brings out a % 5 decrease on
efficiency.By pulling out the M16 screws and stamps on the 4 hinges which connects door to the front section,open the
burner door. Clean the burning room, take turbulators out and clean horizontal smoke channels (2nd and 3rd pass). Than
clean the turbulator and put them in to the channels. Close the burner door strictly.In this cleaning operation soot layer may
occur in flue area.This soot particules can be cleaned by seperating horizontal smoke channels from boiler flue. After this
operation these two screws must be connected again and must be tested for leakage.