Following are monitored devices
acceptable for use with
Universal Board
:
IMPORTANT NOTICE FOR GATE OPERATORS
MANUFACTURED AFTER JANUARY 11, 2016:
All gate operators manufactured after January 11,2016 must have a monitored
input for EACH direction. In order to satisfy this requirement, all PowerMaster
gate operators with the universal board will have one monitored input for each
direction. The reverse (REV) terminal will function for the close direction, and
the open edge (OPN EDG) will function for the open direction. These terminals
will look for, or "monitor", the presence of a 10k in-line resistor. If either terminal
does not detect the presence of the monitored device the unit will function in
constant contact for this direction.
Other terminals that will also monitor for
devices include Open Photo (OPN PHO) and Close Photo (CLO PHO) for each
respective direction.
Note: the first time a monitored device is added to the unit, the board must
"learn" what the monitored device is. To have the board learn the
monitored device, perform the following steps:
1. With the power off, hold both the open and close limits simultaneously.
2. Power up the unit and release your fingers from the limits. The unit has
now learned the monitored device.
EG: the operator detects there is a monitored device on the REV terminal,
but not the OPN EDG terminal. The operator will function in momentary
contact to close, and constant pressure to open.
Device Name Manufacturer
Description
-----------------------------------------------------------------------------------------------
•Prime-Guard
Miller Edge Monitored PhotoEye
•Reflecti-Guard
Miller Edge Retroreflective Monitored PhotoEye
•IRB-MON
EMX
Monitored PhotoEye
•IRB-RET
EMX
Retroreflective Monitored PhotoEye
•The Solution
Miller Edge Multiple Safety devices
Any actions taken to circumvent this monitoring are in violation of
the UL325, building code, and local laws.