COM128 Installation and Operation Manual
Schneider Electric
4
3
CONFIGURATION
3.1
CONFIGURATION SWITCHES
These six switches are used to configure the COM128 for the
desired operation (see Figure 3.1.1). A switch is ON when it is
in the UP position. The following is a description of each mode
of operation. A list of switch settings for the different modes
follows each mode description. The configuration switches are
only read when control power is initally applied to the
COM128. To re-configure the COM128, the control power
must be removed and re-applied.
3.2
MODE DESCRIPTIONS
3.2.1
RS-485 FLOW CONTROL
FUNCTION
This mode is used to convert the RS-232 signals from either a
DTE or DCE device to RS-485 signals. The COM128 makes the
signal conversion and provides the timing control signals for
the RS-485 ports. No data buffering takes place. Timing can be
set for a fixed baud rate or the COM128 is able to do auto-
matic baud rate detection on the incoming RS-232 data. Either
the DTE or DCE port can be programmed. When the DTE port
of the COM128 is selected in automatic baud rate detection
mode, the input CD (Carrier Detect) signal from the DCE
device can be used to control the transmission of RS-232 data
from the COM128 to the DCE device.
For applications where a DTE device uses the RS-232 RTS
signal for flow control the COM128 can be programmed to use
the RTS signal to control the RS-485 ports.
SW2
SW1
SW3
SW4
SW5
SW6
OFF
ON
SWITCHES
1 2 3 4 5 6
NOTE
Setting the Configuration Switches to an
undefined value will cause the COM128 to
continually reset.
Mode
Port
Baud
SW1
SW2
SW3
SW4
SW5
SW6
RS-485 Flow Control @ fixed Baud Rate
DTE
1200
OFF
OFF
OFF
OFF
O N
OFF
RS-485 Flow Control @ fixed Baud Rate
DTE
2400
O N
OFF
OFF
OFF
O N
OFF
RS-485 Flow Control @ fixed Baud Rate
DTE
4800
OFF
O N
OFF
OFF
O N
OFF
RS-485 Flow Control @ fixed Baud Rate
DTE
9600
O N
O N
OFF
OFF
O N
OFF
RS-485 Flow Control @ fixed Baud Rate
DTE
19,200
OFF
OFF
O N
OFF
O N
OFF
RS-485 Flow Control @ fixed Baud Rate
DCE
1200
O N
OFF
O N
OFF
O N
OFF
RS-485 Flow Control @ fixed Baud Rate
DCE
2400
OFF
O N
O N
OFF
O N
OFF
RS-485 Flow Control @ fixed Baud Rate
DCE
4800
O N
O N
O N
OFF
O N
OFF
RS-485 Flow Control @ fixed Baud Rate
DCE
9600
OFF
OFF
OFF
O N
O N
OFF
RS-485 Flow Control @ fixed Baud Rate
DCE
19,200
O N
OFF
OFF
O N
O N
OFF
RS-485 Flow Control with Auto Baud Rate Detect
DCE
NA
OFF
O N
OFF
O N
O N
OFF
RS-485 Flow Control with Auto Baud Rate Detect
DTE
NA
O N
O N
OFF
O N
O N
OFF
RS-485 Flow Control with Auto Baud Rate Detect and Carrier Detect Required
DTE
NA
OFF
OFF
O N
O N
O N
OFF
RS-485 Flow Control with Hardware RTS
DCE
NA
O N
OFF
O N
O N
O N
OFF
Figure 3.1.1
COM128 Configuration Switches