COM128  Installation and Operation Manual

Schneider Electric

9

RS-485 PORT

SHLD

SHLD

To next
device

To next
device

RS-485

Device

RS-485 Cable

22 gauge shielded

twisted pair

Terminal

Strip

DISTANCE X

NOTE

Terminal strip connection

method adds 2 times

distance X to overall RS-485

cable length.

4.3

RS-485 BUS CONNECTIONS

4.3.1

CONVERTOR CONNECTIONS

The RS-485 port of the COM128 provides screw down,
captured wire type terminal blocks that unplug from the main
chassis to simplify wiring.

Refer to the following sections for detailed information on
wiring requirements and recommended topologies.

4.3.2

GENERAL BUS WIRING
CONSIDERATIONS

Up to 32 devices can be connected on a single RS-485 bus.  The
overall length of the RS-485 cable connecting all devices cannot
exceed 4000 ft. (1219 m).

Devices connected on the bus, including convertor(s) and other
instrumentation, must be wired as follows:

a.

Use a good quality shielded twisted pair cable for each
RS-485 bus.  It is recommended that AWG 22 (0.6 mm) or
larger conductor size be used.

b.

Ensure that the polarity is correct when connecting to the
RS-485 port (+) and (-) terminals of each device.

c.

The shield of each segment of the RS-485 cable must be
connected to ground at 

one end only

.

CAUTION

Do not connect ground to the shield at both
ends of a segment.  Doing so will allow
ground loop currents to flow in the shield,
inducing noise in the communications cable.

d.

It is recommended that an intermediate terminal strip be
used to connect each device to the bus.  This will allow for
easy removal of a device for servicing if necessary.  The
terminal strip should be connected as shown in Figure
4.3.2.

4.3.3

RECOMMENDED TOPOLOGIES

Devices on an RS-485 bus are connected in a point-to-point
configuration, with the (+) and (-) terminals of each device
connected to the associated terminals on the next device.  This
is illustrated in Figure 4.3.3a.

While there are many topologies that can be used to connect
devices on an RS-485 communication bus, the two recom-
mended methods are the 

straight-line 

and 

loop

 

topologies.

STRAIGHT-LINE TOPOLOGY

The straight-line wiring method is illustrated in Figure 4.3.3a.
Note that connections are shown for one RS-485 port only.  The
COM128 supports four RS-485 buses simultaneously.  The
COM128 can exist at any position on the RS-485 bus, including
an end point.

Each end point of the straight-line bus must be terminated with
a 1/4 watt resistor.  These 

termination resistors 

reduce signal

reflections which may corrupt data on the bus.

Termination resistors are connected between the (+) and (-)
terminals of the device at each end of the bus.  This device can
include either a convertor or any other instrument.  The value
of the resistor should match the line impedance of the cable
being used. For AWG 22 shielded twisted pair cable, values
between 150 and 300 ohms are typical.  Consult the cable
manufacturer’s documentation for the exact impedance of
your cable.

LOOP TOPOLOGY

The loop wiring method is illustrated in Figure 4.3.3a. The
COM128 can exist at any position on the RS-485 bus.

One advantage of the loop topology is that a single open
circuit fault condition anywhere on the loop will not result in
the loss of communication between the computer station and
any of the remote devices.

The loop topology does not require termination resistors at any
point on the bus.

Figure 4.3.2

RS-485 Intermediate Terminal Strip Connection

Содержание COM128

Страница 1: ...PowerLogic COM128 RS 232 to RS 485 Converter Installation and Operation Guide August 2006...

Страница 2: ......

Страница 3: ...cribes important considerations related to a device setup feature or application CAUTION Alerts you to a condition which could potentially cause damage to the device or other external equipment WARNIN...

Страница 4: ...4 RS 485DataBuffering 6 3 2 5 Repeater 6 4 INSTALLATION 7 4 1 DCSupplyConnections 7 4 2 RS 232Connection Configuration 7 4 2 1 RS 232Cable 7 4 2 2 Direct Connection to a Computer 7 4 2 3 Connection t...

Страница 5: ...RS 485 transmit enable may be controlled automatically or by the RS 232 RTS line RTS CTS handshaking capability for use with radio modems Compatible with short haul modems and line drivers that are p...

Страница 6: ...COM128 automatically enables the RS 485 transmit mode and begins to transmit onto the RS 485 buses DTEORDCEOPERATION The COM128 is switch selectable to act in DTE or DCE mode An RS 232 port is provide...

Страница 7: ...The RS 485 panel of the COM128 is illustrated in Figure 2 2 1 RS 485 PORTS These four ports connect the COM128 to the four RS 485 buses Four pluggable 3 pin terminal blocks are provided STATUS INDICA...

Страница 8: ...COM128 to the DCE device For applications where a DTE device uses the RS 232 RTS signal for flow control the COM128 can be programmed to use the RTS signal to control the RS 485 ports SW2 SW1 SW3 SW4...

Страница 9: ...the RS 232 DTE port the COM128 de asserts the RTS signal and returns to the Idle State If CTS is not asserted after 256 bytes have been received from the RS 485 port a buffer overflow will occur The C...

Страница 10: ...FF ON RS 485 Data Buffering with 20 mSec transmission delay after RTS assertion DTE 9600 ON OFF OFF ON OFF ON RS 485 Data Buffering with 50 mSec transmission delay after RTS assertion DTE 9600 OFF ON...

Страница 11: ...to the corresponding terminals of the removable 2 pin terminal block connector supplied with the COM128 See Chapter 2 Figure 2 1 1 4 2 RS 232CONNECTIONS CONFIGURATION Sections 4 2 2 and 4 2 3 discuss...

Страница 12: ...force the COM128 to buffer all RS 485 data received until the modem is ready to receive the data Most radio modems require this mode as do some telephone modems Refer to your modem s operation manual...

Страница 13: ...connected as shown in Figure 4 3 2 4 3 3 RECOMMENDEDTOPOLOGIES Devices on an RS 485 bus are connected in a point to point configuration with the and terminals of each device connected to the associate...

Страница 14: ...T A DCE PORT DTE PORT COM128 RS 232 to RS 485 Converter RS 232 RS 485 R T RS 485 Cable AWG 22 shielded twisted pair Overall length 4000 ft maximum Last RS 485 Device End Point Last RS 485 Device End P...

Страница 15: ...int on the RS 485 bus no more than two 2 cables should be con nected Thisincludesconnectionpointson instruments converters andterminalstrips Followingthisguidelineensuresthatstar andteeconnectionsarea...

Страница 16: ...ORT A DCE PORT DTE PORT COM128 RS 232 to RS 485 Converter RS 232 RS 485 Computer or Modem RS 485 STAR CONNECTION RS 485 PORT RS 485 PORT SHLD SHLD RS 485 PORT SHLD RS 485 PORT DO NOT CONNECT SHLD SHLD...

Страница 17: ...1220 F ambient air Storage Temperature 300 C to 700 C 220 F to 1580 F Humidity 5 to 95 percent non condensing Shipping Weight 0 9 kg 2 lbs 0 oz Carton 30 x 25 x 18cm 11 8 x 9 8 x 5 9 5 25 133mm 5 25...

Страница 18: ...be valid the IND power supply must be installed in accor dance with all local electrical codes and standards and must not be user accessible duringnormaloperation MechanicalandMountingDimensions Dimen...

Страница 19: ...COM128 InstallationandOperationManual SchneiderElectric 15 COM128 IND Power Supply AC L AC N FG see specs for for input range 1A Slo Blo Figure 7 2 Connecting the IND Power Supply...

Страница 20: ...COM128 InstallationandOperationManual SchneiderElectric 16 Figure 7 2 1 IND Option Industrial P S...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...8 EQI 31 rue Pierre Mend s France F 38050 Grenoble C dex 9 Tel 33 0 4 76 57 60 60 Getting technical support Contact your local Schneider Electric sales representative for assistance or go to the www p...

Отзывы: