Installation / Initial Set-Up (cont’d)
18
5. Grounding the generator
Always ensure the generator is properly grounded to prevent electrical shock.
You must always ground the generator by the following method when using the generator as a portable
electrical source:
1.
Drive a ¾” or 1” copper pipe or rod into the ground close to the generator. The pipe/rod must
penetrate moist earth – the depth required will be dictated by local soil conditions. Consult with an
electrician.
2.
Connect an approved ground clamp to the pipe.
3.
Run an 8 gauge wire from the clamp to the generator grounding post which is located on the base of
the generator frame to the right of the battery location.
4.
DO NOT connect the generator grounding post to a water pipe or a ground used by a radio system.
If a licensed electrician installs the generator with a connection to your building’s electrical circuit for use as a
back-up power system, grounding may alternatively be completed through the building’s grounding system.
Ask your electrician. If the generator is not grounded through your building’s electrical system, follow the
procedure above.
WARNING:
Operating the generator when it is not properly grounded can result in electrical shock.
Grounding Post
8 Ga. wire
Copper
Pipe/Rod
Ground