* REPAIRS SHOULD BE PERFORMED BY A MECHANIC / ELECTRICIAN

        TROUBLESHOOTING - UNHEATED UNITS

SYMPTOMS

POSSIBLE CAUSES

CHECK/REMEDIES

NON-OPERATIONAL

Main circuit breaker or discon

-

nect is in OFF position.

Move switch to ON position 

or reset.

Loose electrical connection.

Check / tighten connection.

Fuse blown.

Replace fuse.

MINIMAL / NO AIR

Air Intake and filter clogged.

Remove, clean and / or replace.

Air intake restricted.

Remove obstruction or move air 

curtain.

Fan not rotating.

Affix set screw(s) to shaft.

Air discharge inadequate.

Obstruction in discharge path 

(i.e. door headers, automatic 

door openers, etc.) Move air 

curtain.

Air discharge deflecting into 

wall.

For every 1 inch air curtain is 

mounted above the door head

-

er, air curtain should be moved 

away from the wall 

1/2 inch.

Negative air pressure.

Equalize building pressure.

Multiple motor units: (only) one 

motor not operating.

Repair or replace motor.

EXCESSIVE BLOWER NOISE/ 

VIBRATION

Blower wheel loose on motor 

shaft.

Tighten set screw(s).

Air intake vibration.

Tighten air intake screws.

Blower wheel dirty.

Remove and clean.

Damaged blower or unbalanced 

wheel.

Repair or replace.

Motor being worn.

Replace motor.

Fan hitting / rubbing fan hous

-

ing.

Motor shaft bent. Repair or 

replace. Free housing from fan’s 

path.

ELECTRIC CONTROLS NOT 

FUNCTIONING

Switch in OFF position.

Move switch to ON position.

Door switch won’t turn unit 

on/off when used in conjunc

-

tion with Hand/Off/Automatic 

switch.

Move switch to AUTOMATIC 

position. Check wiring.

Improperly wired.

Check and repair.

Faulty switch.

Repair or replace.

EXCESSIVE AIR SPILL TO OUTSIDE 

OR INSIDE. 

Nozzle angle too great.

Optimum angle setting is 15 

degrees towards outside.

RETURN POLICY

• 

For all warranty issues contact factory at 724-588-3305 or toll-free 888-321-2473.

 All returns must be approved in advance and accompanied by an RGA number or 

   will not be accepted.

 Once units have been installed no returns will be allowed.

 Units that are returned damaged will not be accepted and full payment will be required.

• 

No returns will be allowed after 10 working days from shipment.

• 

Contact factory for Restocking Fee Schedule.

SYMPTOMS

POSSIBLE CAUSES

CHECK/REMEDIES

EXCESSIVE HEAT

Not enough air over electric 

heating coil.

See MINIMAL / NO AIR

Improper voltage.

Supply voltage that unit re

-

quires.

Thermostat setting is too high.

Switch to a lower temperature 

setting.

NO HEAT / NOT ENOUGH HEAT

Time delay is improperly wired.

Blown out, replace.

Heat switch is in OFF position. 

Rotate to ON position.

Heat switch is in ON position.

Check wiring. Replace switch or 

contactor.

Coil(s) burned out. 

Replace.

Heaters glowing red and thermal 

cut outs activating

Not enough air over coil. See 

MINIMAL / NO AIR

Thermostat improperly set.

Set to desired temperature.

Heater contactor not function

-

ing.

Repair or replace.

Improperly wired.

Check and adjust.

Ambient temperature.

Units are recommended to have 

a minimum of 66 degrees intake 

air.

* REPAIRS SHOULD BE PERFORMED BY A MECHANIC / ELECTRICIAN

TROUBLESHOOTING - ELECTRICALLY HEATED UNITS

CLEARANCES

5

Содержание EVE

Страница 1: ...Aire will not be responsible for misplaced switches Please review the following instructions for unpacking your air curtain and preparing it for installation Replace the air intake and filter if provided when installation is complete 4 2 Using a Phillips head screwdriver unscrew the truss head screws that hold air intake screen in place Set aside air intake and screws for later use Remove filter i...

Страница 2: ...re no belts to maintain n Motors are permanently lubricated so there are not any fittings that need greased VANE PIVOT POINT VANE A IR FL O W A IR F L O W INSTALLATION OPTIONS Wall Mount Back side of air curtain has 4 mounting holes capable of accepting four 3 8 mounting bolts or lags with washers use these holes only for mounting Mark and pre drill mounting surface accurately A long extension and...

Страница 3: ...nd Off Automatic switch Move switch to AUTOMATIC position Check wiring Improperly wired Check and repair Faulty switch Repair or replace EXCESSIVE AIR SPILL TO OUTSIDE OR INSIDE Nozzle angle too great Optimum angle setting is 15 degrees towards outside RETURN POLICY For all warranty issues contact factory at 724 588 3305 or toll free 888 321 2473 All returns must be approved in advance and accompa...

Страница 4: ... to take or ship the Powered Aire product to the factory should contact the home office A repair by anyone other than Powered Aire authorized personnel must be approved in advance by Powered Aire Repairs Outside the Scope of Warranty Problems with Powered Aire products can be due to improper maintenance faulty installation non Powered Aire additions or modifications or other problems not due to de...

Отзывы: