(If applicable) To avoid electrical hazards, please turn off the internal/external input breaker. Then,
turn off any external battery breaker and wait till all fans completely shut down.
Test
Press once to start self-test function during Line-Mode
Silence
Press once to enable/disable alarm buzzer during Battery-Mode
Green mode
The Green mode feature will enable UPS no-Load or light-load shutdown to maintain power
consumption and battery life. During battery mode, the UPS will shut down approximately 4 min with no
load/light load operating.
Green mode can also be enabled or disabled via monitoring software.
Green Mode Enable: Turn on UPS normally. Green mode activates in default.
Green Mode Disable: When turning on UPS, please keep holding the “ON” button until a double “beep”
occurred.
4.4 UPS Configuration
UPS Manual test
Manual tests for UPS or battery can be conducted from the UPS configuration as well and are
functional even when the UPS is not charging the battery.
Simple test
: It’s recommended to conduct a simple simulation test when.
1. The first use of UPS.
2. Adding new loads.
3. 6 months’ regular check-up
Switch on the UPS and wait for the power indicator to light up, then unplug UPS to simulate the main
power failure.
Manual Battery Test: Press the “test” button once. UPS will automatically conduct a self-test. Please
note that the UPS will briefly switch to battery mode.
5.
UPS Monitoring Connection
UPSMON Pro software (Or other power monitoring software) can further utilize the UPS with warning
reminders, monitoring, control shut down, and setting adjustments.
Using monitoring features requires connecting the UPS to a computer or the internet.
Connect UPS to Computer with USB (Optional)
Locate the USB port on UPS.
Connect with factory-provided.
Ensure your computer can install and support power management software.
6.
Maintenance
Please read the following instruction to ensure your safety and maintain a longer product lifetime. This
section contains detailed information about moving, maintaining, and placing the UPS. With a minimal
amount of maintenance, you can expect the UPS to function smoothly.
6.1 Transportation
Please handle UPS with extreme caution since a high amount of energy is within the batteries. Keep
the unit in position as marked on the packaging and never drop the unit.
6.2 Storage
Please read the following instructions if the UPS is not installed immediately:
Store the equipment as is in its original packing and shipping carton.
Do not store in temperatures outside the range of +15°C to +25°C.
Protect the equipment from wet or damp areas and moist air.
To maintain the vitality of the batteries, please recharges the UPS at least 8 hours every six months.
6.3 Operation
CAUTION:
Ensure that all environmental concerns and requirements are met according to safety instruction;
otherwise, the safety of installation personnel cannot be guaranteed since the unit may malfunction.
Please ensure no flammable substances such as gases or fumes.
Avoid extreme temperature and humidity. Protect the equipment from moisture.
Ensure there is enough space (300mm or above recommended) at the rear and side of UPS for proper
ventilation.
Ensure that the front of the UPS remains clear for user operation.
Only
authorized agents or technicians may service the unit.
Do not
open the UPS cabinet. Components may contain hazardous or fatal voltage.
Output receptacles may carry live voltage without connecting to the main power.
Pay special attention to UPS air inlet;
do not
let it coved by dust.
6.4 Battery
6.4.1
Maintenance
The reliability of the battery is heavily related to the environmental issue.
At the temperature of 25 degrees Celsius, A regular 6-12 months’ checkup is advised.