At the temperature of 25 degrees Celsius, A regular 6-12 months’ checkup is
advised.
6.4.2
Replacement
Caution: Read safety instruction before proceeding.
In all the following steps and factory stander:
The
black
battery cable is the
negative
(-) pole
The
red
battery cable is
positive
(+) pole
Caution
: Avoid battery positive port directly contacts with metal. (including UPS cover)
Caution:
Do not remove the battery during battery-mode
.
1.
Ensure the UPS is turned off and disconnected from the main power.
2.
Unscrew the front panel.
3.
Push the front panel upward then pull out the front panel.
4.
Remove the battery cover, disconnect battery cable, then remove the battery.
(negative pole first)
5.
Replace with the same type and quantity of battery.
6.
Reinstall the battery cover and front panel.
APP-A. Troubleshooting
Troubleshooting procedures give simple instructions in determining UPS
malfunctions. Start the troubleshooting procedure if you witness any alarm indication.
Alarm
The UPS has an audible alarm. When different situations occurred, UPS will alert
users with display and buzzer.
Battery-mode (Slow alarm)
During battery mode, the alarm will beep every 2 seconds. The alarm will stop
when UPS return to Line-mode.
Battery-Low (Rapid alarm)
During Battery-low (less than 30%), the UPS will beep every 0.5 seconds. The alarm
will stop when UPS shutdown or returns to Line-mode.
Overload (Constant alarm)
When UPS operating with load exceeded its maximum capacity, UPS will emit a
continuous alarm to warn an overload condition. UPS will automatically turn off to
protect your essential load. Please consider remove or shutdown less-essential loads.
Silencing Alarm
Here is the instruction to mute the active alarm or future alarm notification:
Note
: During battery-mode, if the battery is low on power, the alarm will sound
regardless of silent-mode enable/disable.