background image

Powerbox Australia Pty Ltd

Powerbox Pacific Ltd

4 Beaumont Rd Mount Kuring Gai NSW 2080 AUSTRALIA

1800 251 380  [email protected]   

www.powerbox.com.au

 

1a Henry Rose Place Albany Auckland 0632 NEW ZEALAND

09 4158 320   [email protected]    

www.powerbox.co.nz

 

Sydney

 (Head Office) 

Auckland 

(Subject to alterations.  This product is not designed to be used in applications such as life support systems wherein a failure or malfunction could result in injury or death)

Version 1.0  10/2018

2

AC-Input 

85...265Vac , 47...63Hz , 110…375Vdc 

Input Rating 

100...240Vac , 115Vac <0.8A  230Vac <0.3A 

Rated DC-Voltage 

5V 

9V 

12V 

15V 

24V 

48V 

60V 

Rated DC-Current 

5A 

3.3A 

2.5A 

2A 

1.3A 

0.6A 

0.5A 

Ripple 20MHz 230Vac 

15mV 

15mV 

10mV 

10mV

 

50mV 

100mV 

100mV 

DC adj. range 

4,9-5,25V 

8,5-9,9V 

11,4-13,6V 

14,2-22,5V 

23,5-28,5V 

45,6-53V 

57-66V

Order Code 

OSW00301.(volt) example: OSW00301.12 

Factory Adjust. Tolerance Uout  ± 1% 
Load regulation 

< ± 0.5% 10-100%, 100-10% 

Switching Frequency 

70KHz typical 

Basic Load 

0 A 

Efficiency 

Up to 86% 

Load Protection 

1,2x I

rated  

,auto recovery 

Voltage Protection 

140% of U

out 

, auto recovery 

Short Circuit Protection 

Continuous 

Temperature Control 

Not available  

Hold Up Time 

> 40ms 230Vac with full load 

Inrush Current 

< 17A (230Vac) 

Terminal Connects: 

1 = L 

SK1    

2 = N 

1 = Sense - (

5V only) 

Sk2 

2 = DC - 
3 = DC + 

Screw terminal order 
codes for SK1 & SK2: 
(each package = 10 pcs ) 

Art.No. SK1: 3520054 
(2 pins for AC-input) 
Art.No. SK2: 3520037  
(3 pins for 1x DC-out)

 

Softstart 

30ms typ. 

Cooling 

Free air convection 

Ambient Temperature 

- 20°C …+70°C 

Storage Temperature 

- 40°C …+85°C 

EMI 

EN55022 class B / EN61000-3-2 

EMS 

EN61000-6-2,3 

Safety 

EN60950-1, EN60204-1 

Safety class 1(A) 

VDE0805, VDE0100 

Air & Surface Leakage Paths 

> 8mm

Input to Output Isolation 

IP-OP: 3kVac IP-GND:2kVac  
OP-GND:0.5kVac

 

MTBF EN61209 

300000h 

MTTF EN61209.SN29500 

125433h @ 40°C 24/7 85% load 

Clima/Dirt/Hight/Humidity 

3k3, Kl.2, 3000m NN, 90% hum. 

ROHS conformity 

ROHS Directive 2011/65/EU 

REACH conformity 

REACH Directive 1907/2006 

Dimensions (HxWxD) 

28.5x62x96.5mm 

Weight 

145g 

Connectors 
SK1 & SK2 not included 

Terminal plug AWG26...AWG12 

Conception 

The OSW power supply series realizes very high power efficiency in a space-saving housing. This design enables Green Power applications 
and allows free air convection. Latest generation electrical devices relate to the high reliability of all Camtec products. The Camtec philosophy 
is, to employ low ESR ultra long life capacitors where expedient to achieve a superior lifetime of our products. The used screw terminals allow 
easy to wire and smooth service. The units perform low ripple & noise. It makes them applicable for sensitive MSR and for Audio systems. 

Sense operation

 

The OSW00751.05 provides sense connections to compensate a voltage drop over the load lines. The maximum compensation is 200mV. Be 
aware that this operation mode may recommend extended preparations concerning interference elimination or other protections. We 
recommend to use the sense wires twisted. Make sure that the polarization is correct to avoid damages to the power supply. All other 
OSW00751 models have no sense connection. 

Parallel und series operation 

Camtec power supplies of the same model and the same output voltage can be either used parallel or in series. The assembling of external 
parts is usually not recommended. Make sure that the output voltage of each connected unit is ±1% equal. We recommend connecting the 
DC-outputs to a neutral point or a power bar. Follow the safety norms of dangerous dc-voltages.

UI-Chart, overload and temperature control characteristic 

The OSW models base on a typical resonance converter. The converter is ideal for complex loads and DC-drives. Consciously we resigned 
an excessive power boost that mostly occurs in less exact working control circuits. The advantage is, that the power supply delivers its energy 
always controlled and constant to the load. Even with a faulty operation of the power supply the loads never expose to high risk. 

Отзывы: