Determining Which Hookup Configuration to Use 

 

STOP!

  

If you are using an optional SEM250A/B or SE350/450 Static Exciter 

Module, 

DO NOT

 use these instructions for hookup!  See the instructions that 

came with your module instead!

 

 

The XR8 Universal Voltage Regulator is configurable for 3 different output ranges suitable for use on the vast 
majority of generators available on the market from past and present.  It is necessary to choose the proper 
mode of operation for your generator in order to get the best regulation and fastest response time possible. 

 

To determine the proper connection for your generator you need to know any two of the following 3 
specifications from the rating plate of your generator: 

 

1:  Exciter Field Voltage (in DC Volts)

 

[Generally given in full load Voltage on nameplates]

  

2:  Exciter Field Resistance (in Ohms)

 

[See Note Below]

 

3:  Exciter Field Amperage (in DC Amps)

 

[Generally given in full load Amps on nameplates]  

 

 

 

Using the specifications obtained from your generator exciter, select a 

Connection (A, B, or C) from the chart below: 

 

 

Exciter Field Resistance

 

≥26Ω

 

& Exciter Full-Load Voltage

 

≤125VDC

    

Use connection 

A

 

(See Page 8)

 

 

 

Exciter Field Resistance

 

≥13Ω

 

& Exciter Full-Load Voltage

 

≤63VDC

     

Use connection 

B

  

(See Page 10)

 

 

 

Exciter Field Resistance

 

≥6.5Ω

 & 

Exciter Full-Load Voltage

 

≤32VDC

     

Use connection 

C

  

(See Page 12)

 

 
 
 

Note about Field Resistance: 

•  When measuring field resistance on a brushless generator, simply measure the resistance of the 

exciter field through your field leads with a multimeter. 

 

•  When measuring field resistance on a brush-type generator, measure the resistance through both the 

field leads as well as directly on the slip rings themselves.  

The readings you obtain should ideally 

be the same, but 

no more than 1% difference.

 

 If you show more than 1% difference in reading your 

generator has brush and ring contact problems and will need cleaning or maintenance before installing 
the XR8.  

Failure to correct brush and ring contact problems will result in severe damage to the 

voltage regulator as well as possible PERMANENT damage to the slip rings themselves!

  

NEVER

 

use emery cloth, carborundum stones, “comm sticks”, or Tuner cleaner to dress or 

clean slip rings

.  They will make a bad problem much, much worse!  Only use Garnet or Flint 

sandpaper and clean with a clean rag soaked with Acetone for best results! 

 

 

Содержание XR8

Страница 1: ...nal inexpensive digital interface module This capability makes the XR8 suitable for automated or unattended installations or large scale parallel operations Like our previous models the XR8 is fully repairable All major electronic components are not encapsulated to facilitate repair while all sensitive components are encapsulated to protect them from contamination and moisture The XR8 is compatibl...

Страница 2: ...enerators 7 Hookup Connection A 8 Parallel Configuration for Connection A 9 Hookup Connection B 10 Parallel Configuration for Connection B 11 Hookup Connection C 12 Parallel Configuration for Connection C 13 Initial Setup and Commissioning 14 Optional Power Tronics Add On Modules 15 Conversion From Shunt Wound to Solid State Regulation 16 Internal Fuse Replacement 17 Application Troubleshooting 18...

Страница 3: ...rly installed the XR8 Universal Voltage Regulator is designed to provide a lifetime of service A Generator voltage regulator has several automated tasks it must perform in order to provide reliable clean and regulated electricity It must build up the generator regulate the terminal voltage within its design specifications and protect both itself and the generator should a fault situation arise The...

Страница 4: ... A B or C from the chart below Exciter Field Resistance 26Ω Exciter Full Load Voltage 125VDC Use connection A See Page 8 Exciter Field Resistance 13Ω Exciter Full Load Voltage 63VDC Use connection B See Page 10 Exciter Field Resistance 6 5Ω Exciter Full Load Voltage 32VDC Use connection C See Page 12 Note about Field Resistance When measuring field resistance on a brushless generator simply measur...

Страница 5: ...rator To determine your full load exciter field voltage use the following formula EExc Where EGen Conf is your Generator s configured voltage e g 120 208 240 480V etc EGen Output is your recorded output voltage and EBattery is your battery voltage 12V usually Next calculate your maximum exciter field amperage using your measured field resistance and your calculated exciter voltage using the follow...

Страница 6: ...39V Parallel Wye 208 240V 3ø Voltage L L 208 240V Voltage L N 120 139V NOTE 208V is Standard Voltage Series Delta 240V 3ø Voltage L L 240V Voltage L1 L2 N 120V Voltage L3 N 208V NOTE L3 N is a High Leg 208V instead of 120V Double Delta 120 240V 1ø Voltage L L 240V Voltage L N 120V Preferred Single Phase Connection Don t Use Zig Zag if Possible NOTE Derate generator by 1 3 rated capacity when using...

Страница 7: ...Measure your field resistance and proceed with sizing on Page 4 DPE Winding and Auxiliary Winding These generators use an extra winding in the main stator as a power supply for the voltage regulator in an attempt to give the regulator a clean power source that isn t affected by load The XR8 has proprietary filtering circuitry in its sensing stage that is largely unaffected by generator load Becaus...

Страница 8: ...or use on 480V systems either connect the regulator to the winding center taps T7 and T9 See Page 6 or use a 480 240V step down transformer rated at 1 5KVA Connecting the input of the XR8 to 2 different legs of the generator as shown in the diagram below will result in greater regulation accuracy than when connecting line neutral NOTE It is not necessary to jumper terminals 7 and 8 if not using th...

Страница 9: ...ance a bit at a time until satisfactory droop is achieved CT should be sized at 25 35VA burden XR8 Professional Series Universal Voltage Regulator 240VAC MAX Secondary Voltage 100K 2W Unit Parallel Switch Reactive Droop Adjustment 10Ω 100W CT Rating XXX 5A 25 35VA Transformer Rating XXX 240V 1 5KVA Regulator On Off Switch Rate for Primary Voltage 10A Setup Tips Isolation Transformer is recommended...

Страница 10: ... to the unit will result For use on 480V systems either connect the regulator to the winding center taps T7 and T9 See Page 6 or use a 480 240V step down transformer rated at 1KVA Connecting the input of the XR8 to 2 different legs of the generator as shown in the diagram below will result in greater regulation accuracy than when connecting line neutral NOTE It is not necessary to jumper terminals...

Страница 11: ...tance a bit at a time until satisfactory droop is achieved CT should be sized at 25 35VA burden XR8 Professional Series Universal Voltage Regulator 240VAC MAX Secondary Voltage 100K 2W Unit Parallel Switch Reactive Droop Adjustment 10Ω 100W CT Rating XXX 5A 25 35VA Transformer Rating XXX 240V 1KVA Regulator On Off Switch Rate for Primary Voltage 10A Setup Tips Isolation Transformer is recommended ...

Страница 12: ...ither connect the regulator to the winding center taps T7 to T0 See Page 6 or use a 480 120V step down transformer rated at 500VA Preferred for superior regulation accuracy Connecting the input of the XR8 to 2 different legs of the generator through a transformer will result in greater regulation accuracy than when connecting line neutral as shown in the diagram below NOTE It is not necessary to j...

Страница 13: ...resistance a bit at a time until satisfactory droop is achieved CT should be sized at 25 35VA burden XR8 Professional Series Universal Voltage Regulator 120VAC MAX Secondary Voltage 100K 2W Unit Parallel Switch Reactive Droop Adjustment 10Ω 100W CT Rating XXX 5A 25 35VA Transformer Rating XXX 120V 500VA Regulator On Off Switch Rate for Primary Voltage 10A Setup Tips Isolation Transformer is recomm...

Страница 14: ... turning the adjustment screw clockwise right The voltage adjustment is a 25 turn pot NOTE The maximum internal voltage setpoint is 260VAC This helps prevent accidental over voltage conditions due to incorrect installation 8 Place the generator on line and observe the frequency and voltage 9 If the generator is being paralleled measure the droop during loading and adjust the droop resistor as nece...

Страница 15: ...Converts the XR8 into a 125VDC 25ADC Static Exciter AFM5X Automatic Flash Module Adds Automatic Flash or Battery Flash to installations with low residual or requiring guaranteed buildup EIM1020VM External Interface Card Allows the XR8 to be controlled externally by virtually any digital load sharing controller VAR controller genset controller or digital governor controller MOP1224HD Motorized Pote...

Страница 16: ...e the XR8 Universal Voltage regulator with older Shunt Wound exciters that originally had manual mechanical or series solid state voltage regulators by converting the wiring as in the diagrams below If the generator will not build up after conversion try switching your F and F leads at the regulator and try starting up again NOTE Armature brushes MUST BE ISOLATED from the field leads for proper op...

Страница 17: ... Littelfuse Part Number 0314010 MXP or 0314010 HXP Fuse Replacement Procedure Refer to the image above for easy reference Remove the 4 screws located on the front of the aluminum mounting can to allow removal of the can Remove the aluminum mounting can from the circuit card Use a continuity tester or multimeter to test the fuses A good fuse will read continuity or 0Ω resistance Replace open fuses ...

Страница 18: ...generator 4 Non linear Inverter load or defective connection in exciter field 5 Open diode in exciter or shorted rotor in generator 6 Loose component in voltage regulator 7 Loose wiring connections 8 Input voltage to regulator is too low 9 Exciter field is grounded 10 Non linear Inverter load or wrong selection for regulator hookup 11 Exciter fields are reversed 12 Wrong selection of regulator wir...

Страница 19: ...atus light is not on do not continue this test 6 SLOWLY turn the internal voltage adjustment CW until the incandescent light bulb turns fully on then adjust the internal voltage adjustment CCW until the light bulb is off 7 Observation You should be able to taper the incandescent light bulb on and off in a relatively smooth manner If the light flashes on or off quickly the regulator has an internal...

Страница 20: ...ww power tronics com warranty Problem Description History Please be detailed Ship To Address City State Zip Country Company Name Contact Person Telephone Number Email Address Primary Load Please Explain Repair Warranty Request Information Generator Leads Check One 12 10 6 4 3ø 4 1ø 3 Generator Wiring Mode Check One High Wye Low Wye Series Delta Zig Zag Double Delta Single Phase Other Terminal Volt...

Страница 21: ...se date and serial number of the defective part A repair request form must be sent in with the product before repairs will begin You can obtain this form by contacting Power Tronics Inc Send repairs to Power Tronics Inc 2802 Cobbler Ln Kerrville Texas USA 78028 Send in repairs only by UPS or FedEx USPS will NOT deliver to our facility Any one of the following conditions will void the warranty v Ov...

Отзывы: