XR8 

Professional Series 

Universal Voltage Regulator 

REVISION A (or later) 

 

The Power-Tronics XR8 Universal Voltage 
Regulator is the latest upgrade for all UVR and 
XR series voltage regulators and features an 
upgraded regulation system and a higher 
amperage rectifier section capable of 8 amps!  
The XR8 is also capable of replacing other 
manufacturers' voltage regulators and has 
optional Static Exciter Modules to boost its 
capacity to 30 amps DC! 
 
The XR8 is designed specifically for Professional 
Electrical Generator Service Technicians and 
the Electrical Generator Repair Industry.  It 
incorporates an easily selectable frequency 
range for voltage roll-off during under-frequency 
operation and offers precise voltage regulation 
regardless of the connected load and ambient 
temperature.  The XR8 is a ruggedized design 
and is engineered to provide a lifetime of 
trouble-free, reliable operation. 
 
Manual stability matching is a thing of the past, 
the XR8 contains patented electronic circuitry 
that automatically matches the regulator's 
response time to the generator exciter.  This 
greatly speeds installation and eliminates 
guesswork. 
 
PLC and automated Genset control is possible 
with the XR8 by simply adding an optional, 
inexpensive digital interface module.  This 
capability makes the XR8 suitable for automated 
or unattended installations, or large-scale 
parallel operations. 
 
Like our previous models, the XR8 is fully 
repairable!  All major electronic components are 
not encapsulated to facilitate repair while all 
sensitive components are encapsulated to 
protect them from contamination and moisture. 
The XR8 is compatible with all previous and 
current optional modules available for use with 
Power-Tronics voltage regulators making it 
extremely simple to upgrade an existing voltage 
regulator installation. 

 

Specifications 

 

Input Voltage:

   

 

 

120 / 208 or 240vac 

Frequency:

 

 

 

 

50 or 60hz 

Voltage Regulation:

 

 

 

± .25% From NL to FL 

Parallel Operation

 

 

 

Yes 

Maximum Output Voltage:

 

 

52vdc @ 120vac input 

 

 

 

 

 

105vdc @ 240vac input 

 

 

 

 

 

210vdc @ 240vac input 

Continuous Output Voltage:

 

 

32vdc @ 120vac input 

 

 

 

 

 

63vdc @ 240vac input 

 

 

 

 

 

125vdc @ 240vac input 

Maximum Continuous Output:

 

 

8adc 

Minimum Field Resistance:

 

 

6.5Ω @ 32vdc output 

 

 

 

 

 

13Ω @ 63vdc output 

 

 

 

 

 

26Ω @ 125vdc output 

Min Residual Build up Voltage:

   

3.5vac 

Under Frequency Protection:

 

 

Yes, VPH reduction 

Physical Size:

   

 

 

4.75 x 6 x 1 in. 

Weight:

  

 

 

 

7 oz 

Repairable:

 

 

 

 

Yes 

Internal Protection:

 

 

 

Fuses, cartridge type 

External Voltage Adjustment:

 

 

Yes 

System Operating Indicator:

 

 

Yes 

Optional Static Exciter Modules

:   

Yes 

Optional External Controls

 

Yes 

Cartridge Fuse Type:

 

 

 

3AG 10A @ 250V Fast-Blow 

Optional External Potentiometer:

   

100KΩ @ 2W 

External Adjustment Range:

 

 

±10% of Terminal Voltage 

Содержание XR8

Страница 1: ...nal inexpensive digital interface module This capability makes the XR8 suitable for automated or unattended installations or large scale parallel operations Like our previous models the XR8 is fully repairable All major electronic components are not encapsulated to facilitate repair while all sensitive components are encapsulated to protect them from contamination and moisture The XR8 is compatibl...

Страница 2: ...enerators 7 Hookup Connection A 8 Parallel Configuration for Connection A 9 Hookup Connection B 10 Parallel Configuration for Connection B 11 Hookup Connection C 12 Parallel Configuration for Connection C 13 Initial Setup and Commissioning 14 Optional Power Tronics Add On Modules 15 Conversion From Shunt Wound to Solid State Regulation 16 Internal Fuse Replacement 17 Application Troubleshooting 18...

Страница 3: ...rly installed the XR8 Universal Voltage Regulator is designed to provide a lifetime of service A Generator voltage regulator has several automated tasks it must perform in order to provide reliable clean and regulated electricity It must build up the generator regulate the terminal voltage within its design specifications and protect both itself and the generator should a fault situation arise The...

Страница 4: ... A B or C from the chart below Exciter Field Resistance 26Ω Exciter Full Load Voltage 125VDC Use connection A See Page 8 Exciter Field Resistance 13Ω Exciter Full Load Voltage 63VDC Use connection B See Page 10 Exciter Field Resistance 6 5Ω Exciter Full Load Voltage 32VDC Use connection C See Page 12 Note about Field Resistance When measuring field resistance on a brushless generator simply measur...

Страница 5: ...rator To determine your full load exciter field voltage use the following formula EExc Where EGen Conf is your Generator s configured voltage e g 120 208 240 480V etc EGen Output is your recorded output voltage and EBattery is your battery voltage 12V usually Next calculate your maximum exciter field amperage using your measured field resistance and your calculated exciter voltage using the follow...

Страница 6: ...39V Parallel Wye 208 240V 3ø Voltage L L 208 240V Voltage L N 120 139V NOTE 208V is Standard Voltage Series Delta 240V 3ø Voltage L L 240V Voltage L1 L2 N 120V Voltage L3 N 208V NOTE L3 N is a High Leg 208V instead of 120V Double Delta 120 240V 1ø Voltage L L 240V Voltage L N 120V Preferred Single Phase Connection Don t Use Zig Zag if Possible NOTE Derate generator by 1 3 rated capacity when using...

Страница 7: ...Measure your field resistance and proceed with sizing on Page 4 DPE Winding and Auxiliary Winding These generators use an extra winding in the main stator as a power supply for the voltage regulator in an attempt to give the regulator a clean power source that isn t affected by load The XR8 has proprietary filtering circuitry in its sensing stage that is largely unaffected by generator load Becaus...

Страница 8: ...or use on 480V systems either connect the regulator to the winding center taps T7 and T9 See Page 6 or use a 480 240V step down transformer rated at 1 5KVA Connecting the input of the XR8 to 2 different legs of the generator as shown in the diagram below will result in greater regulation accuracy than when connecting line neutral NOTE It is not necessary to jumper terminals 7 and 8 if not using th...

Страница 9: ...ance a bit at a time until satisfactory droop is achieved CT should be sized at 25 35VA burden XR8 Professional Series Universal Voltage Regulator 240VAC MAX Secondary Voltage 100K 2W Unit Parallel Switch Reactive Droop Adjustment 10Ω 100W CT Rating XXX 5A 25 35VA Transformer Rating XXX 240V 1 5KVA Regulator On Off Switch Rate for Primary Voltage 10A Setup Tips Isolation Transformer is recommended...

Страница 10: ... to the unit will result For use on 480V systems either connect the regulator to the winding center taps T7 and T9 See Page 6 or use a 480 240V step down transformer rated at 1KVA Connecting the input of the XR8 to 2 different legs of the generator as shown in the diagram below will result in greater regulation accuracy than when connecting line neutral NOTE It is not necessary to jumper terminals...

Страница 11: ...tance a bit at a time until satisfactory droop is achieved CT should be sized at 25 35VA burden XR8 Professional Series Universal Voltage Regulator 240VAC MAX Secondary Voltage 100K 2W Unit Parallel Switch Reactive Droop Adjustment 10Ω 100W CT Rating XXX 5A 25 35VA Transformer Rating XXX 240V 1KVA Regulator On Off Switch Rate for Primary Voltage 10A Setup Tips Isolation Transformer is recommended ...

Страница 12: ...ither connect the regulator to the winding center taps T7 to T0 See Page 6 or use a 480 120V step down transformer rated at 500VA Preferred for superior regulation accuracy Connecting the input of the XR8 to 2 different legs of the generator through a transformer will result in greater regulation accuracy than when connecting line neutral as shown in the diagram below NOTE It is not necessary to j...

Страница 13: ...resistance a bit at a time until satisfactory droop is achieved CT should be sized at 25 35VA burden XR8 Professional Series Universal Voltage Regulator 120VAC MAX Secondary Voltage 100K 2W Unit Parallel Switch Reactive Droop Adjustment 10Ω 100W CT Rating XXX 5A 25 35VA Transformer Rating XXX 120V 500VA Regulator On Off Switch Rate for Primary Voltage 10A Setup Tips Isolation Transformer is recomm...

Страница 14: ... turning the adjustment screw clockwise right The voltage adjustment is a 25 turn pot NOTE The maximum internal voltage setpoint is 260VAC This helps prevent accidental over voltage conditions due to incorrect installation 8 Place the generator on line and observe the frequency and voltage 9 If the generator is being paralleled measure the droop during loading and adjust the droop resistor as nece...

Страница 15: ...Converts the XR8 into a 125VDC 25ADC Static Exciter AFM5X Automatic Flash Module Adds Automatic Flash or Battery Flash to installations with low residual or requiring guaranteed buildup EIM1020VM External Interface Card Allows the XR8 to be controlled externally by virtually any digital load sharing controller VAR controller genset controller or digital governor controller MOP1224HD Motorized Pote...

Страница 16: ...e the XR8 Universal Voltage regulator with older Shunt Wound exciters that originally had manual mechanical or series solid state voltage regulators by converting the wiring as in the diagrams below If the generator will not build up after conversion try switching your F and F leads at the regulator and try starting up again NOTE Armature brushes MUST BE ISOLATED from the field leads for proper op...

Страница 17: ... Littelfuse Part Number 0314010 MXP or 0314010 HXP Fuse Replacement Procedure Refer to the image above for easy reference Remove the 4 screws located on the front of the aluminum mounting can to allow removal of the can Remove the aluminum mounting can from the circuit card Use a continuity tester or multimeter to test the fuses A good fuse will read continuity or 0Ω resistance Replace open fuses ...

Страница 18: ...generator 4 Non linear Inverter load or defective connection in exciter field 5 Open diode in exciter or shorted rotor in generator 6 Loose component in voltage regulator 7 Loose wiring connections 8 Input voltage to regulator is too low 9 Exciter field is grounded 10 Non linear Inverter load or wrong selection for regulator hookup 11 Exciter fields are reversed 12 Wrong selection of regulator wir...

Страница 19: ...atus light is not on do not continue this test 6 SLOWLY turn the internal voltage adjustment CW until the incandescent light bulb turns fully on then adjust the internal voltage adjustment CCW until the light bulb is off 7 Observation You should be able to taper the incandescent light bulb on and off in a relatively smooth manner If the light flashes on or off quickly the regulator has an internal...

Страница 20: ...ww power tronics com warranty Problem Description History Please be detailed Ship To Address City State Zip Country Company Name Contact Person Telephone Number Email Address Primary Load Please Explain Repair Warranty Request Information Generator Leads Check One 12 10 6 4 3ø 4 1ø 3 Generator Wiring Mode Check One High Wye Low Wye Series Delta Zig Zag Double Delta Single Phase Other Terminal Volt...

Страница 21: ...se date and serial number of the defective part A repair request form must be sent in with the product before repairs will begin You can obtain this form by contacting Power Tronics Inc Send repairs to Power Tronics Inc 2802 Cobbler Ln Kerrville Texas USA 78028 Send in repairs only by UPS or FedEx USPS will NOT deliver to our facility Any one of the following conditions will void the warranty v Ov...