background image

 

© 2018 Power-Tronics, Inc. 

 

Connection A 

(

See page 9

 if the generator will be paralleled using this connection) 

 

Connection A

 is a Full-Wave rectified configuration, which allows a maximum output of

 

210VDC @ 5A

 with an input voltage of 240VAC. 

 
This connection is typically used on higher voltage excitation fields (generally referred to 
as 125V fields) or on shunt control fields where the full-load excitation voltage is greater 
than 63VDC. 
 

Note that the maximum input voltage to the XR5B-400 Universal Voltage regulator 
is 240VAC!

  

DO NOT input 277VAC into the XR5B-400!

  Severe damage to the unit 

will result!  For use on 480V systems, either connect the regulator to the winding center 
taps T7 and T9 (

See Page 6

) or use a 

480-240V step-down transformer rated at 

1.5KVA.

 

 

Connecting the input of the XR5B-400 to 2 different legs of the generator as shown in 
the diagram below will result in greater regulation accuracy than when connecting line-
neutral. 
 
 

 
 
 
 
 
 
 
 
 
 
 

 

 

 

NOTE: 

It is not necessary 
to jumper terminals 
7 and 8 if not using 
the Remote Voltage 
Adjustment! 

XR5B-400 Specialty Series 

Universal Voltage Regulator 

NOTE: 

If the generator is to be operated below 400 Hz, a disconnect or switch should be installed in 
series with the incoming power to terminals #1 and #2 on the XR5B-400. 
 

NEVER install a switch or breaker on the DC or Exciter side of the voltage regulator!   

Only install a switch or disconnect on the AC Side of the regulator! 

240VAC 

MAX! 

100K, 2W 

 

Regulator On/Off 
Switch 
Rate for:  

240V @ 10A 

Содержание XR5B-400

Страница 1: ...ble for automated or unattended installations or large scale parallel operations Like our previous models the XR5B 400 is fully repairable All major electronic components are not encapsulated to facilitate repair while all sensitive components are encapsulated to protect them from contamination and moisture The XR5B 400 is compatible with all previous and current optional modules available for use...

Страница 2: ...8 Parallel Configuration for Connection A 9 Hookup Connection B 10 Parallel Configuration for Connection B 11 Hookup Connection C 12 Parallel Configuration for Connection C 13 Initial Setup and Commissioning 14 Optional Power Tronics Add On Modules 15 Conversion From Shunt Wound to Solid State Regulation 16 Internal Fuse Replacement 17 Application Troubleshooting 18 Bench Check Procedures 19 Insta...

Страница 3: ... greatly simplify setup while offering extreme reliability When properly installed the XR5B 400 Universal Voltage Regulator is designed to provide a lifetime of service A Generator voltage regulator has several automated tasks it must perform in order to provide reliable clean and regulated electricity It must build up the generator regulate the terminal voltage within its design specifications an...

Страница 4: ...xciter Field Resistance 42Ω Exciter Full Load Voltage 125VDC Use connection A See Page 8 Exciter Field Resistance 21Ω Exciter Full Load Voltage 63VDC Use connection B See Page 10 Exciter Field Resistance 10Ω Exciter Full Load Voltage 32VDC Use connection C See Page 12 Note about Field Resistance When measuring field resistance on a brushless generator simply measure the resistance of the exciter f...

Страница 5: ...xciter field voltage use the following formula EExc EGen Conf EGen Output EBattery 2 Where EGen Conf is your Generator s configured voltage e g 120 208 240 480V etc EGen Output is your recorded output voltage and EBattery is your battery voltage 12V usually Next calculate your maximum exciter field amperage using your measured field resistance and your calculated exciter voltage using the followin...

Страница 6: ...tage L L 208 240V Voltage L N 120 139V NOTE 208V is Standard Voltage Series Delta 240V 3ø Voltage L L 240V Voltage L1 L2 N 120V Voltage L3 N 208V NOTE L3 N is a High Leg 208V instead of 120V Double Delta 120 240V 1ø Voltage L L 240V Voltage L N 120V Preferred Single Phase Connection Don t Use Zig Zag if Possible NOTE Derate generator by 1 3 rated capacity when using this connection ...

Страница 7: ...and proceed with sizing on Page 4 DPE Winding and Auxiliary Winding These generators use an extra winding in the main stator as a power supply for the voltage regulator in an attempt to give the regulator a clean power source that isn t affected by load The XR5B 400 has proprietary filtering circuitry in its sensing stage that is largely unaffected by generator load Because the regulator isn t aff...

Страница 8: ...ect the regulator to the winding center taps T7 and T9 See Page 6 or use a 480 240V step down transformer rated at 1 5KVA Connecting the input of the XR5B 400 to 2 different legs of the generator as shown in the diagram below will result in greater regulation accuracy than when connecting line neutral NOTE It is not necessary to jumper terminals 7 and 8 if not using the Remote Voltage Adjustment X...

Страница 9: ...tisfactory droop is achieved CT should be sized at 25 35VA burden XR5B 400 Specialty Series Universal Voltage Regulator 240VAC MAX Secondary Voltage 100K 2W Unit Parallel Switch Reactive Droop Adjustment 10Ω 100W CT Rating XXX 5A 25 35VA Transformer Rating XXX 240V 1 5KVA Regulator On Off Switch Rate for Primary Voltage 10A Setup Tips Isolation Transformer is recommended for best results but is op...

Страница 10: ...on 480V systems either connect the regulator to the winding center taps T7 and T9 See Page 6 or use a 480 240V step down transformer rated at 1KVA Connecting the input of the XR5B 400 to 2 different legs of the generator as shown in the diagram below will result in greater regulation accuracy than when connecting line neutral NOTE It is not necessary to jumper terminals 7 and 8 if not using the Re...

Страница 11: ...satisfactory droop is achieved CT should be sized at 25 35VA burden XR5B 400 Specialty Series Universal Voltage Regulator 240VAC MAX Secondary Voltage 100K 2W Unit Parallel Switch Reactive Droop Adjustment 10Ω 100W CT Rating XXX 5A 25 35VA Transformer Rating XXX 240V 1KVA Regulator On Off Switch Rate for Primary Voltage 10A Setup Tips Isolation Transformer is recommended for best results but is op...

Страница 12: ... winding center taps T7 to T0 See Page 6 or use a 480 120V step down transformer rated at 500VA Preferred for superior regulation accuracy Connecting the input of the XR5B 400 to 2 different legs of the generator through a transformer will result in greater regulation accuracy than when connecting line neutral as shown in the diagram below NOTE It is not necessary to jumper terminals 7 and 8 if no...

Страница 13: ...ntil satisfactory droop is achieved CT should be sized at 25 35VA burden XR5B 400 Specialty Series Universal Voltage Regulator 120VAC MAX Secondary Voltage 100K 2W Unit Parallel Switch Reactive Droop Adjustment 10Ω 100W CT Rating XXX 5A 25 35VA Transformer Rating XXX 120V 500VA Regulator On Off Switch Rate for Primary Voltage 10A Setup Tips Isolation Transformer is recommended for best results eve...

Страница 14: ... notice unsteady or pulsating voltage If so turn the Stability adjustment clockwise until the pulsation stops As you turn the stability adjustment the terminal voltage will rise Always keep your voltage within 10 of the desired setpoint with your voltage adjustment 8 Place the generator on line and observe the frequency and voltage 9 If the generator is being paralleled measure the droop during lo...

Страница 15: ...400 into a 125VDC 25ADC Static Exciter EIC1020 External Interface Card Allows the XR5B 400 to be controlled externally by virtually any digital load sharing controller VAR controller genset controller or digital governor controller MOP1224HD Motorized Potentiometer Allows the XR5B 400 to be externally controlled by older automated controllers using pulsed signals or dry contacts for control ABF10 ...

Страница 16: ...Voltage regulator with older Shunt Wound exciters that originally had manual or mechanical voltage regulators by converting the wiring as in the diagrams below If the generator will not build up after conversion try switching your F and F leads at the regulator and try starting up again NOTE Armature brushes MUST BE ISOLATED from the field leads for proper operation ...

Страница 17: ...Cooper Bussmann Part Number BK GDB 5A Fuse Replacement Procedure Refer to the image above for easy reference Remove the 4 screws holding the mounting can to the circuit board Separate the regulator printed circuit card from the mounting housing Replace open fuses then replace and replace and tighten all screws Fuse size is 20mm x 5mm 5A 250VAC DO NOT REPLACE WITH ANY OTHER TYPE OR RATING OF FUSE Y...

Страница 18: ...ld 5 Open diode in exciter or shorted rotor in generator 6 Stability adjustment is not properly adjusted or loose component in voltage regulator 7 Loose wiring connections 8 Input voltage to regulator is too low 9 Exciter field is grounded 10 Non linear load stability control too far clockwise or wrong selection for regulator hookup 11 Exciter fields are reversed 12 Wrong selection of regulator wi...

Страница 19: ...nue this test 6 SLOWLY turn the internal voltage adjustment CW until the incandescent light bulb turns fully on then adjust the internal voltage adjustment CCW until the light bulb is off 7 Observation You should be able to taper the incandescent light bulb on and off in a relatively smooth manner If the light flashes on or off quickly the regulator has an internal fault do not continue this test ...

Страница 20: ...blem Description History Please be detailed Ship To Address City State Zip Country Company Name Contact Person Telephone Number Email Address Primary Load Please Explain Repair Warranty Request Information Generator Leads Check One 12 10 6 4 3ø 4 1ø 3 Generator Wiring Mode Check One High Wye Low Wye Series Delta Zig Zag Double Delta Single Phase Other Terminal Voltage Residual AC Voltage Rated KW ...

Страница 21: ...e part A repair request form must be sent in with the product before repairs will begin You can obtain this form by contacting Power Tronics Inc Send repairs to Power Tronics Inc 2802 Cobbler Ln Kerrville Texas USA 78028 Send in repairs only by UPS or FedEx USPS will NOT deliver to our facility Any one of the following conditions will void the warranty v Overheating of the power supply resistor s ...

Отзывы: