6
19. Input and field circuit are being fed by a common cable or conduit.
20. Incorrect hookup or wiring.
Fuse Replacement
•
Remove the 2 screws located on the front of the mounting can near the
terminal board.
•
Loosen the 2 screws located on the front of the mounting can near the
voltage and stability adjustment holes. (DO NOT REMOVE!)
•
Partially separate the top of the regulator printed circuit card from the
mounting housing. (Separate just enough to reach and replace the fuses)
•
Replace open fuses and re-tighten all screws.
•
Fuse size is 20mm x 5mm, 5 amps @ 250vac.
(DO NOT REPLACE WITH
ANY OTHER TYPE AND RATING OF FUSE! SEVERE DAMAGE AND
PERSONAL INJURY COULD RESULT BY DOING SO!)