If you do not have any of the specifications of your generator’s 

exciter, or if you don’t know where to start when trying to determine 

your exciter specs, please see the section below for instructions on 

measuring and calculating your exciter specifications. 

 

•   Measure your exciter field resistance using a multimeter on your field leads.  

Record this value.  If you have a brush-type generator, also take a resistance 
reading on your slip rings:  the value you obtain on the slip rings should be no 
more than 1% difference from the value you obtained through the field leads.   

 
•   Next, start and run the generator and apply 12V from a battery through your 

field leads and record the AC voltage produced by the generator.  To 
determine your full load exciter field voltage, use the following formula: 

E

Exc.

 =

 

 

E

Gen

.

Conf

.

E

Gen

.

Output

E

Battery

"

 

#

 

$

 

$

 

%

 

&

 

'

 

'

 

* 2

   

 

Where 

E

Gen.Conf

.

 is your Generator’s configured voltage (e.g.: 120, 208, 240, 

480V, etc.), 

E

Gen.Output

 is your recorded output voltage, and 

E

Battery

 

is your battery 

voltage (12V usually).   
 

•   Next, calculate your maximum exciter field amperage using your measured 

field resistance and your calculated exciter voltage using the following formula: 

I

=

E

R

 

Where 

I

 is your maximum exciter field current, 

E

 is your calculated field 

voltage from the above formula, and 

R

 is your measured field resistance.   

 

Using the values you just measured and calculated, see the chart on 

the previous page to determine which connection you should use to 

connect the XC4 to your generator.

 

 
For Example: 

 
Measured Field Resistance:  18Ω 
Battery Voltage:  12V 
Generator Configuration: 480V Wye 
 

12V applied to the field yields 189VAC L1-L3.                 

E

Exc.

 =

  

480

$%&

$'

∗ 2 = 60.95

 

 

 
E

Exc.

 =

   60.95VDC (Full-Load Voltage) 

 

This generator would use 

240V Connection

 

Содержание XC4

Страница 1: ... heating when the engine is idled The XC4 uses the XR8 s patented electronic circuitry that automatically matches the regulator s response time to the generator exciter This greatly speeds installation and eliminates guesswork Because it only uses 4 wires for connection to the generator it also makes quick replacement in the field possible To ensure extreme durability and dependability the XC4 is ...

Страница 2: ...Generator Wiring Diagrams 6 Use with PMGs DPE AUX and Harmonic Winding Generators 7 240V Hookup Connection 8 120V Hookup Connection 9 Installation Considerations 10 Initial Setup and Commissioning 10 Optional Power Tronics Add On Modules 11 Conversion From Shunt Wound to Solid State Regulation 12 Application Troubleshooting 13 Bench Check Procedures 14 Installation Warranty Form 15 Product Warrant...

Страница 3: ...greatly simplify setup while offering extreme reliability in demanding service conditions When properly installed the XC4 Automatic Voltage Regulator is designed to provide a lifetime of service A Generator voltage regulator has several automated tasks it must perform in order to provide reliable clean and regulated electricity It must build up the generator regulate the terminal voltage within it...

Страница 4: ...your generator exciter select 120V or 240V Hookup from the list below Exciter Field Resistance 16Ω Exciter Full Load Voltage 63VDC Use 240V Hookup Connection See Page 8 Exciter Field Resistance 8Ω Exciter Full Load Voltage 32VDC Use 120V Hookup Connection See Page 10 Note about Field Resistance When measuring field resistance on a brushless generator simply measure the resistance of the exciter fi...

Страница 5: ...ator To determine your full load exciter field voltage use the following formula EExc EGen Conf EGen Output EBattery 2 Where EGen Conf is your Generator s configured voltage e g 120 208 240 480V etc EGen Output is your recorded output voltage and EBattery is your battery voltage 12V usually Next calculate your maximum exciter field amperage using your measured field resistance and your calculated ...

Страница 6: ...39V Parallel Wye 208 240V 3ø Voltage L L 208 240V Voltage L N 120 139V NOTE 208V is Standard Voltage Series Delta 240V 3ø Voltage L L 240V Voltage L1 L2 N 120V Voltage L3 N 208V NOTE L3 N is a High Leg 208V instead of 120V Double Delta 120 240V 1ø Voltage L L 240V Voltage L N 120V Preferred Single Phase Connection Don t Use Zig Zag if Possible NOTE Derate generator by 1 3 rated capacity when using...

Страница 7: ...Measure your field resistance and proceed with sizing on Page 4 DPE Winding and Auxiliary Winding These generators use an extra winding in the main stator as a power supply for the voltage regulator in an attempt to give the regulator a clean power source that isn t affected by load The XC4 has proprietary filtering circuitry in its sensing stage that is largely unaffected by generator load Becaus...

Страница 8: ...will result For use on 480V systems either connect the regulator to the winding center taps T7 and T9 See Page 6 or use a 480 240V step down transformer rated at 500VA Connecting the input of the XC4 to 2 different legs of the generator as shown in the diagram below will result in greater regulation accuracy than when connecting line neutral XC4 Commercial Series Automatic Voltage Regulator NOTE I...

Страница 9: ... NOT input 277VAC into the XC4 Severe damage to the unit will result For use on 480V systems either connect the regulator to the winding center taps T7 and T0 See Page 6 or use a 480 120V step down transformer rated at 250VA When connecting the input of the XC4 from center tap to neutral of the generator as shown in the diagram always connect AC2 to the generator neutral XC4 Commercial Series Auto...

Страница 10: ...ioning 1 Install the regulator and wire up to the correct wiring diagram 240V or 120V 2 If installing the XC4 on a brush type generator verify that the brushes and brush riggings are isolated ungrounded and connected ONLY to the XC4 3 Turn the internal voltage control fully counter clockwise left This procedure is necessary in case the original factory settings have been altered 4 Start up the pri...

Страница 11: ...allations For more information on any of the modules below visit our online catalog at www power tronics com ABF10 Automatic Battery Flash Module Adds Automatic Battery Flash to installations with low residual or requiring guaranteed buildup HVD2 High Voltage Disconnect Adds passive protection for your generator and connected equipment from runaway and high voltage conditions Disconnects power to ...

Страница 12: ...e the XC4 Automatic Voltage regulator with older Shunt Wound exciters that originally had manual mechanical or series solid state voltage regulators by converting the wiring as in the diagrams below If the generator will not build up after conversion try switching your F and F leads at the regulator and try starting up again NOTE Armature brushes MUST BE ISOLATED from the field leads for proper op...

Страница 13: ...nverter load or defective connection in exciter field 5 Open diode in exciter or shorted rotor in generator 6 Loose or failed component in voltage regulator 7 Loose wiring connections 8 Input voltage to regulator is too low 9 Exciter field is grounded 10 Non linear Inverter load or wrong selection for regulator hookup 11 Exciter fields are reversed 12 Wrong selection of regulator wiring configurat...

Страница 14: ...t or flickering do not continue this test 6 SLOWLY turn the internal voltage adjustment CW until the incandescent light bulb turns fully on it will be reduced brightness then adjust the internal voltage adjustment CCW until the light bulb is off 7 Observation You should be able to taper the incandescent light bulb on and off in a relatively smooth manner If the light flashes on or off quickly the ...

Страница 15: ...n History Please be detailed Ship To Address City State Zip Country Company Name Contact Person Telephone Number Email Address Primary Load Please Explain Repair Warranty Request Information Generator Leads Check One 12 10 6 4 3ø 4 1ø 3 Generator Wiring Mode Check One High Wye Low Wye Series Delta Zig Zag Double Delta Single Phase Other Terminal Voltage Residual AC Voltage Rated KW Rated KVA Gener...

Страница 16: ... form must be sent in with the product before repairs will begin You can obtain this form by contacting Power Tronics Inc Send repairs to Power Tronics Inc 2802 Cobbler Ln Kerrville Texas USA 78028 Send in repairs only by UPS or FedEx USPS will NOT deliver to our facility Any one of the following conditions will void the warranty v Overheating of the power supply resistor s on the printed circuit ...

Отзывы: