background image

 

 

For Technical Support: 

Visit our website at:  

www.power-tronics.com

 

Call Us at: 

(830) 895-4700 

Hookup Diagram 

 

This configuration uses an external customer-supplied 12 or 24V battery to build the 
terminal voltage to a point that the automatic voltage regulator can take over and 
perform its function.  The ABF10 will automatically disconnect itself when the sensed 
voltage reaches approximately 10-15vac. 

 
Take special care to follow the wiring directions precisely!  DO NOT use a battery 
voltage different from that marked on the ABF10 unit!  Severe damage to the 
ABF10 will result!

 

 

Note that the maximum input voltage to the ABF10 Automatic Battery Flash Unit 
is 240VAC!

  

DO NOT input 277VAC into the ABF10!

  Severe damage to the unit will 

result!  For use on 480V systems, either connect the unit to the winding center taps T7 
and T8 or use a 480-240V step-down transformer. 

 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 

 
 
 

 

 

Note 1:

  Customer-supplied battery and charging system.  

An isolated battery is strongly recommended!

 

 

Note 2:

  Flash-Enable switch.  

Should be open whenever the exciter is not operating

.  Rate at 28VDC, 10A or 

greater.  Switch may be a switched B+, oil-pressure switch, or pushbutton switch. 

 

Note 3:

  If Using the ABF10 on a 480V or higher generator, connect terminals 1 and 2 to the center taps of the stator 

leads T7 and T8, or use a step-down transformer as appropriate to supply 240vac to the ABF10.   

   

DO NOT FUSE SENSING LEADS!!! 

 

Note 4:  

Connect battery positive to “12” or 24” terminals for 12V or 24V battery applications

 

 

*Note 1*

 

*Note 2*

 

*Note 3*

 

*Note 4*

 

Содержание ABF10

Страница 1: ...perator Like the rest of our products the ABF10 Automatic Battery Flash Module is designed and manufactured with heavy duty components to withstand the harshest environmental conditions and provide extreme reliability Onboard fusing and an encapsulated design mean the ABF10 will stand up to extreme operating conditions Indicator lights help the operator know the status of the flashing module and a...

Страница 2: ...Table of Contents Introduction and Functional Description 3 Common 12 Lead Generator Wiring Diagrams 4 Hookup Diagram 5 Sequence of Operation 6 Initial Setup and Commissioning 6 Application Troubleshooting 7 Bench Check Procedures 8 Installation Warranty Form 9 Product Warranty Certificate 10 ...

Страница 3: ... ABF10 Automatic Battery Flash Module is a proven design based on industry standard flashing procedures and safety policies The ABF10 provides a very compact automatic flashing or battery flashing source to any voltage regulation system quickly easily and safely When the generator is first energized the voltage regulator typically begins its buildup mode where it brings the generator up to a given...

Страница 4: ...39V Parallel Wye 208 240V 3ø Voltage L L 208 240V Voltage L N 120 139V NOTE 208V is Standard Voltage Series Delta 240V 3ø Voltage L L 240V Voltage L1 L2 N 120V Voltage L3 N 208V NOTE L3 N is a High Leg 208V instead of 120V Double Delta 120 240V 1ø Voltage L L 240V Voltage L N 120V Preferred Single Phase Connection Don t Use Zig Zag if Possible NOTE Derate generator by 1 3 rated capacity when using...

Страница 5: ...ash Unit is 240VAC DO NOT input 277VAC into the ABF10 Severe damage to the unit will result For use on 480V systems either connect the unit to the winding center taps T7 and T8 or use a 480 240V step down transformer Note 1 Customer supplied battery and charging system An isolated battery is strongly recommended Note 2 Flash Enable switch Should be open whenever the exciter is not operating Rate a...

Страница 6: ...nd the Operating light will illuminate at this time The voltage regulator should operate and raise terminal voltage to the regulator s setpoint Initial Setup and Commissioning 1 Connect the ABF10 to the exciter field as shown in the instructions on Page 5 or to a slave relay as shown on Page 6 2 Verify wiring connections and start the generator 3 Close the Flash Enable switch and observe that the ...

Страница 7: ...ve generator 4 Flash Enable switch is open 5 Open diode in exciter or shorted rotor in generator 6 Loose component in voltage regulator 7 Loose wiring connections 8 Input voltage to regulator is too low 9 Exciter field is grounded 10 Non linear load or wrong selection for regulator hookup 11 Exciter fields are reversed 12 Wrong selection of regulator wiring configuration 13 Defective voltage regul...

Страница 8: ... F on the ABF10 and the Flashing lamp should be illuminated 4 Apply 120VAC to terminals AC1 and AC2 on the ABF10 You should hear a click and read 0VDC on F and F on the ABF10 The Operating lamp should be illuminated at this time and the Flashing lamp should be dark 5 Remove the 120VAC from terminals AC1 and AC2 on the ABF10 After approximately 1 second You should hear a click and read battery volt...

Страница 9: ... History Please be detailed Ship To Address City State Zip Country Company Name Contact Person Telephone Number Email Address Primary Load Please Explain Repair Warranty Request Information Generator Leads Check One 12 10 6 4 3ø 4 1ø 3 Generator Wiring Mode Check One High Wye Low Wye Series Delta Zig Zag Double Delta Single Phase Other Terminal Voltage Residual AC Voltage Rated KW Rated KVA Genera...

Страница 10: ... the purchase date and serial number of the defective part A repair request form must be sent in with the product before repairs will begin You can obtain this form by contacting Power Tronics Inc Send repairs to Power Tronics Inc 2802 Cobbler Ln Kerrville Texas USA 78028 Send in repairs only by UPS or FedEx USPS will NOT deliver to our facility Any one of the following conditions will void the wa...

Отзывы: