background image

 

Page 

21

 of 

24

 

 

PTI-25-30-T4F Operators Manual 

GENERATOR ASSEMBLY INFORMATION 

 

EXCITER TYPE GENERATOR 

The exciter pole pieces contain residual magnetism, which sets up lines of force 

across the air gap to the exciter armature.  When the exciter begins to rotate a voltage 
is induced and current flow is initiated in the exciter armature AC windings.  This voltage 
is fed to the rotating rectifier assembly, rectified and fed to the alternator field, which 
sets up lines of force across the air gap to the alternator stator windings and to the 
output circuit. A static voltage regulator is connected to the generator output.  The 
regulator will rectify part of the output voltage to provide a DC voltage to the exciter field 
coils.  This will increase the density of the lines of force in the exciter, increasing the 
voltage induced into the exciter armature windings, and therefore, to the rotating 
rectifiers. The rotating rectifier output will be increased which increase the alternator 
field strength and generator output will build up its rated voltage.  Adjustment of the 
generator output to the rated voltage level is accomplished by controlling the current fed 
to the exciter field coils. Regulation is automatic with the static type voltage regulator.  
An additional voltage adjustment range is provided if desired by turning the Voltage 
Adjust Rheostat. 

 

ELECTRONIC VOLTAGE REGULATION 

Electronic Voltage Regulator (EVR) also referred to, as an Automatic Voltage 

Regulator (AVR) is a very reliable device, which uses solid-state electronics to maintain 
voltage accuracy at ±2% of the regulated voltage.  The Voltage Regulator is designed to 
automatically regulate and maintain the generated AC voltage throughout the load 
range that is from no load to full load.  

 

VOLTAGE CONNECTION 

The generator may be connected at the terminal board to deliver 120/240 volts to 

a 3 wire grounded neutral system.  
  If all equipment requires 120-volts then the 120-volt connection is preferred, even if 
two lines leave the same switch box. The two lines at the inputs to the switch box are 
both connected to the un-grounded 120-volt lines from the generator.   
The 120-volt connection enables the Electronic Voltage Regulator (EVR) to hold the 
voltage very close to the 115 or 120 volts, as initially adjusted, regardless of the power 
distribution amount the different distribution lines.  The 120-volt connection is 
recommended if the entire electrical load requires only 115 or 120 volts. Although the 
120/240-volt connection may also be used when all loads requires only 110 volts, it 
should be pointed out that this connection, the 240-volts, is regulated and the lightly 
loaded phase, or line, will deliver a high line to neutral voltage and the heavily loaded 
phase will deliver a low line to neutral voltage.  The heavily loaded line may have such a 
low voltage that air

 

conditioning will have more difficulty in starting, and long starting 

lines may overload generator and trip circuit breakers. 
For three phase connections, please contact Power Technology’s Tech support Dept. 

 

Содержание PTI-25-30-T4F

Страница 1: ...Generating Power to The World Power Technology Southeast 634 State Road 44 Leesburg FL 34748 8103 Phone 352 365 2777 Fax 352 787 5545 ...

Страница 2: ...gine Specifications 14 Wet Stacking 15 Engine Maintenance Schedule 16 Engine Oil Maintenance 17 Lubricating Oil Specifications 17 LUBRICATING OIL VISCOSITY 17 RECOMMENDATIONS 17 COOLANT RECOMMENDATIONS 18 CHECKING RADIATOR COOLANT LEVEL 18 COOLANT SERVICE LIFE 19 CHECKING RESERVOIR TANK 19 COOLANT LEVEL 19 CLEANING RADIATOR CHARGED AIR COOLER CORE 19 OPERATING HOURS and SERVICE LOG 20 GENERATOR AS...

Страница 3: ...Page 3 of 24 PTI 25 30 T4F Operators Manual BALANCE 22 BEARING 22 STATOR ASSEMBLY 22 Enclosure Information Error Bookmark not defined TROUBLESHOOTING 24 TROUBLE 24 POSSIBLE CAUSE 24 SUGGESTED ACTION 24 ...

Страница 4: ...manual was up to date at time of printing downloading there may be changes not reflected in your manual If there is any questions please contact Power Technology s customer service dept TO OUR CUSTOMERS Thank you for your purchase of a Power Technology Generator In the event you experience a problem with your generator please contact the sales dealer one of our authorized service centers or Power ...

Страница 5: ...t authorized in writing by Power Tech I Damage caused by operation with improper fuel or at speeds loads conditions modifications or installation contrary to published specifications or recommendations J Original installation charges and startup costs K Removal and re installation charges of more than 1 hour labor for outside units 2 hours for compartment mounted units and 3 hours for below deck m...

Страница 6: ... before you attempt to assemble or use this unit WARNING Indicates a potentially hazardous situation which may possibly result in serious injury or possible death CAUTION Indicates a potentially hazardous situation which may possibly result in minor injury IMPORTANT Indicates that equipment or property damage may result if instructions are not followed NOTE Indicates helpful information Cautious o...

Страница 7: ...clothing around machinery Entanglement in rotating parts controls or projections may cause persona injury Use additional safety items e g hardhat eye protection gloves etc as appropriate or required DO NOT operate machinery or equipment while under the influence of alcohol medication or other drugs or while fatigued DO NOT wear radio or music headphones while operating engine CHECK BEFORE OPERATIN...

Страница 8: ... DO NOT mix gasoline or alcohol with diesel fuel The mixture can cause a fire EXHAUST GASES AND FIRE PREVENTION Engine exhaust fumes can be very harmful if allowed to accumulate Be sure to run the engine in a well ventilated area where there are no people or livestock nearby The exhaust gas from the muffler is very hot To prevent a fire do not expose dry grass oil or any other combustible material...

Страница 9: ...l etc DO NOT remove the radiator cap while the engine is running or immediately after stopping Wait approximately ten minutes for the radiator to cool before removing the cap Be sure the radiator drain valve petcock and hose clamps are tightened Check radiator pressure cap and oil fill cap before operating the engine The battery presents an explosive hazard When the battery is being activated hydr...

Страница 10: ...mation of harmful substances Only use anti freeze that is recommended and approved by Engine Manufacturer Be mindful of the environment Before draining any fluids be prepared to dispose of them in a manner consistent with environmental protection regulations in your location When draining fluids from the engine use appropriate containers to hold the different fluids do not mix fuel oil or coolant ...

Страница 11: ...er the engine radiator muffler or muffler cover has cooled off completely Always use the appropriate tools and jig fixture when performing any service work Be sure to understand and follow the instructions included with these tools Use ONLY correct engine barring techniques for manually rotating the engine DO NOT attempt to rotate the engine by pulling or prying on the cooling fan and V belt Serio...

Страница 12: ... Fill add if necessary Check for absence of water in fuel drain if necessary Check for absence of DTC or failures Check for absence of excessive fan belt looseness Using the PTG Series Controller The LCD display is the primary source of information of the controller The LCD allows you to view change settings and monitor the status of sensors and other engine parameters NOTE The genset mounted cont...

Страница 13: ... the menu changing a settings value or changing the currently displayed parameter page Generator LED Green Engine running with no issues Amber Engine running with warnings Red Engine shutdown on failure Using the Menu System Task Description Entering Menu When in the OFF mode press the enter button to bring up the menu Navigating Menu Once in the menu use the up and down arrows to navigate Pressin...

Страница 14: ... waits to receive a stop command Failure When a failure occurs the controller shuts down the engine and displays reason for failure The unit must be reset using the front panel OFF button with the exception of Modbus Menu When in the menu you can change settings and view the events history Engine Specifications Engine Make Isuzu Engine Model 4LE2X EPA Tier Tier4 Final KWM 1800rpm 49 Oil type SAE 1...

Страница 15: ...equently because of the diverse load applications an automatic load bank is sometimes used A load bank will place a false load on the generator system to keep the diesel engine properly loaded to prevent a wet stack condition and automatically adjust the false load to the real load In smaller applications a false load can be provided by an electric heater or other high load appliances to ensure th...

Страница 16: ...ers need to be changed Maintenance Service Item See notes Daily 150 Hour Interval 500 Hour Interval 1000 Hour Interval Remarks Engine Oil Level deterioration Leakage x Engine Oil Change x x Or Once a Year Oil Filter Change x Or Once a Year Coolant Level x Coolant Leakage x Coolant Change x Or Once a Year Fuel Level x Fuel Leakage x Water in Fuel x x Primary Fuel filter Replacement x x Or Once a Ye...

Страница 17: ...cifications API Class CJ 4 Engine Oil LUBRICATING OIL VISCOSITY RECOMMENDATIONS The minimum ambient temperature during cold engine start up and the maximum ambient temperature during engine operation determine the proper SAE viscosity grade of oil Refer to the Engine Oil Viscosity Table below Lowest Ambient Temperature in order to determine the required oil viscosity for starting an engine in cold...

Страница 18: ...0 Percent 51 C 60 F 111 C 232 F PROPYLENE GLYCOL Freeze Boil Concentration Protection Protection 50 Percent 29 C 20 F 106 C 223 F NOTE Do not use Propylene Glycol in concentrations that exceed 50 percent glycol because of Propylene Glycol s reduced heat transfer capability Use Ethylene Glycol in conditions that require additional protection against boiling or freezing CHECKING RADIATOR COOLANT LEV...

Страница 19: ...ween the upper limit FULL and the lower limit LOW on the side of the reservoir tank CLEANING RADIATOR CHARGED AIR COOLER CORE Visually inspect the core for any obstructions such as dirt or debris Use running water to clean particles from between fins IMPORTANT Never use hard objects to clean radiator core damage to core could result IMPORTANT If your generator is equipped with remote radiator asse...

Страница 20: ...ICE LOG THIS SERVICE LOG IS PROVIDED TO HELP YOU KEEP AN ACCUMULATIVE RECORD OF OPERATION HOURS ON YOUR GENERATOR SET AND THE DATES REQUIRED SERVICES WERE PERFORMED ENTER TIME TO THE NEAREST HOUR Operating Hours Service Record Date Timer Cumulative Date Service performed ...

Страница 21: ...referred to as an Automatic Voltage Regulator AVR is a very reliable device which uses solid state electronics to maintain voltage accuracy at 2 of the regulated voltage The Voltage Regulator is designed to automatically regulate and maintain the generated AC voltage throughout the load range that is from no load to full load VOLTAGE CONNECTION The generator may be connected at the terminal board ...

Страница 22: ...ed and fastened together to form a single laminated assembly The field windings are wound around this assembly FIELD COIL Field coils of heavily insulated wire are wet wound directly onto the poles Field coil leads are brought out to the rectifier assembly for connection to the source of DC excitation voltage BALANCE The rotor assembly is precision balanced to a high degree of static and dynamic b...

Страница 23: ...Page 23 of 24 PTI 25 30 T4F Operators Manual ...

Страница 24: ... check crank connections Cranking fuse blown Replace fuse with new of identical size Engine cranks but doesn t start Out of fuel Check fuel level add fuel if necessary Fuse Blown Replace fuse in control box Fuel relay damaged Check fuel relay and replace if damaged Fuel System lost prime Use Primer on top of fuel filter Engine Starts but shuts down after a few seconds See failure on controller LCD...

Отзывы: