Page 9  — English

EXTENSION CORD CABLE SIZE

Refer to the table below to ensure the cable size of the extension cords you use are capable of carrying the required load. 
Inadequate size cables can cause a voltage drop, which can burn out the appliance and overheat the cord.

Current in

Amperes

Load in Watts

Maximum Allowable Cord Length

At 120V

At 240V

#8 Wire

#10 Wire

#12 Wire

#14 Wire

#16 Wire

2.5

 300

 600

1000 ft.

600 ft.

375 ft.

250 ft.

5

 600

1200

  500 ft.

300 ft.

200 ft.

125 ft.

7.5

 900

1800

  350 ft.

200 ft.

125 ft.

100 ft.

10

1200

2400

  250 ft.

150 ft.

100 ft.

  50 ft.

15

1800

3600

  150 ft.

100 ft.

  65 ft.

20

2400

4800

175 ft.

  125 ft.

  75 ft.

25

3000

6000

150 ft.

  100 ft.

30

3600

7200

125 ft.

  65 ft.

40

4800

9600

  90 ft.

ELECTRIC MOTOR LOADS

It is characteristic of common electric motors in normal operation to draw up to six times their running current while starting. 
This table may be used to estimate the watts required to start electric motors; however, if an electric motor fails to start or 
reach running speed, turn off the appliance or tool immediately to avoid equipment damage. Always check the requirements 
of the tool or appliance being used compared to the rated output of the generator.

Motor Size (H.P.)

Running Watts

Watts Required to Start Motor

Universal

Capacitor

Split Phase

1/8

 275

 N/A

 850

1200

1/6

 275

 600

 850

2050

1/4

 400

 800

1050

2400

1/3

 450

 950

1350

2700

1/2

 600

1000

1800

3600

3/4

 850

1200

2600

1

1100

N/A

3300

NOTICE:

Operating voltage and frequency requirement of all 
electronic equipment should be checked prior to plug-
ging them into this generator. Damage may result if the 
equipment is not designed to operate within a +/- 10% 
voltage variation, and +/- 3 hz frequency variation from 
the generator name plate ratings. To avoid damage, al-
ways have an additional load plugged into the generator 
if solid state equipment (such as a television set) is used. 
A power line conditioner is recommended for some solid 
state applications.

GROUND FAULT CIRCUIT INTERRUPTER

See Figure 1.

The 20 amp, 120 volt receptacles on the generator are 
protected by a Ground Fault Circuit Interrupter (GFCI), 

which guards against the hazards of ground fault currents. 
An example of ground fault current is the current that would 
flow through a person who is using an appliance with faulty 
insulation and, at the same time, is in contact with an electrical 
ground such as a plumbing fixture, wet floor, or earth.
GFCI receptacles do not protect against short circuits, 
overloads, or shocks.
The GFCI receptacles can be tested with the TEST and 
RESET buttons.

To test:

 

Depress the TEST button. This should cause the Reset 
button to pop out.

  To restore power, depress the RESET button.

Perform this test monthly to ensure proper operation of the 
GFCI. If the generator is stored outdoors, unprotected from 
the weather, test the GFCI receptacle before each use.

ELECTRICAL

Содержание PS906522MFI

Страница 1: ...ketools com SAVE THIS MANUAL FOR FUTURE REFERENCE WARNING To reduce the risk of injury the user must read and understand the operator s manual before using this product ADVERTENCIA Para reducir el rie...

Страница 2: ...cept culos I Fuel valve v lvula de combustible J Oil cap dipstick tapa de relleno de aceite varilla medidora de aceite K Oil drain plug tap n de drenaje del aceite L Engine switch interruptor del moto...

Страница 3: ...ig 8 Fig 7 A C Fig 5 Fig 3 10 9 1 2 3 4 6 11 5 8 7 A C B D B E D C A A Handle mango B Handle lock pin pasador de seguro del mango C Handle release knob perilla de liberaci n del mango A C B A Oil cap...

Страница 4: ...del filtro de aire A D B C A Oil drain plug tap n de drenaje del aceite B Oil cap dipstick tapa de relleno de aceite varilla medidora de aceite B A A Engine switch in ON position interruptor del motor...

Страница 5: ...filter filtro de combustible A A Fuel valve v lvula de combustible B Hose barb conector de manguera dentada C Fuel line conducto de combustible B C A Fuse holder sujetador de la fusible B Fuse fusible...

Страница 6: ...rely to a suitable ground source that is in contact with the soil for a minimum distance of 8 ft The National Electric Code contains several practical ways in which to establish a good ground source I...

Страница 7: ...ical codes Do not allow children or untrained individuals to use this unit Do not start or operate the engine in a confined space building near open windows or in other unventilated space where danger...

Страница 8: ...nder during or immediately after use they are HOT and will cause burn injury Do not allow the generator s gas tank to overflow when filling Fill to 1 in below the top neck of the gasoline tank to allo...

Страница 9: ...It will only activate due to the presence of carbon monoxide gas at the sensor Carbon monoxide gas may be present in other areas The carbon monoxide shutoff feature on this generator is not a substitu...

Страница 10: ...th Hot Surface and Exhaust Gases To reduce the risk of injury or damage avoid contact with any hot surface and do not place any body parts in the path of hot exhaust gases Lifting Hazard To reduce the...

Страница 11: ...well ventilated outdoor areas away from open windows or doors Do not expose to rain or use in damp locations Using a generator indoors CAN KILL YOU IN MINUTES Generator exhaust contains carbon monoxi...

Страница 12: ...does not include a ground rod or copper wire Call a qualified electrician for local grounding requirements SPARK ARRESTOR Operation of this equipment may create sparks that can start fires around dry...

Страница 13: ...1 4 400 800 1050 2400 1 3 450 950 1350 2700 1 2 600 1000 1800 3600 3 4 850 1200 2600 1 1100 N A 3300 NOTICE Operating voltage and frequency requirement of all electronic equipment should be checked p...

Страница 14: ...e generator outlets before starting its engine The correct and safe way to manage generator power is to sequentially add loads as follows 1 With nothing connected to the generator start the engine as...

Страница 15: ...Dindicatorlightinthecontrolpanelwillilluminatetoindicate afaultintheengine sfuelinjectionsystem Pleasecontactcustomer service or a qualified service center for assistance DIGITAL DISPLAY The digital d...

Страница 16: ...not attempt to modify this product or create acces sories not recommended for use with this product Any such alteration or modification is misuse and could result in a hazardous condition leading to...

Страница 17: ...wires to the positive terminal first then connect the black wire to the negative terminal Make sure all connections are tight NOTE Be careful not to short across the terminals when installing Shortin...

Страница 18: ...or assistance APPLICATIONS This generator is designed to supply electrical power for operating compatible electrical lighting appliances tools and motor loads BEFORE OPERATING THE UNIT Only use OUTSID...

Страница 19: ...ant after the initial 25 hours of run time When a cumulative time of 50 hours is reached P50 will display on the meter to remind you to clean the air filter When a cumulative time of 100 hours is reac...

Страница 20: ...the START position Release the switch when the engine starts NOTE The battery may require charging before the gen erator can be started using the engine switch Once the generator is started the batter...

Страница 21: ...etc Do not use a garden hose to clean the generator Water enter ing the fuel system or other internal parts of the unit can cause problems that will decrease the life of the generator To clean the uni...

Страница 22: ...sh not provided to remove carbon deposits from the spark arrestor screen as needed DRAINING FUEL TANK See Figures 19 20 To help prevent gum deposits in the fuel system drain the fuel from the tank bef...

Страница 23: ...able when not in use BATTERY REMOVAL AND PREPARATION FOR RECYCLING To preserve natural resources please recycle or dispose of batteries properly Thisproductusesleadacidbatteries Local state or federal...

Страница 24: ...Spark Plug Replace Spark Plug2 Check Clean Spark Screen Check Adjust Idle Speed Check Adjust Valve Clearance1 2 Check Adjust Head Bolt Torque1 2 Fuel Filter Inspect Replace 1 These items should only...

Страница 25: ...gasoline or refueled with bad gasoline Check air filter element Clean or replace as needed Contact a qualified service center Drainfuel Refuelwithfreshgasoline Ifproblem continues contact a qualified...

Страница 26: ...Page 22 English NOTES NOTAS...

Страница 27: ...ocoso se la puede enterrar en una trinchera de al menos 75 cm 30 pulg de profundidad En cualquier caso el extremo superior de la jabalina debe estar al ras del suelo o por debajo del rasante o protegi...

Страница 28: ...s bater as No conecte la unidad al sistema el ctrico de un edificio a menos que el generador y el interruptor de transferencia se hayan instalado correctamente y que un electricista calificado haya ve...

Страница 29: ...e usarla para ver si tiene tornillos flojos fugas de combustible etc Reemplace toda pieza da ada PELIGRO Riesgo de incendios y lesiones por quemaduras Nunca retire la tapa de combustible mientras est...

Страница 30: ...esultar necesario un condicionador de la l nea el ctrica para algunas aplicaciones de equipo de estado s lido Para usarse s lo en el exterior NUNCA ignore un evento de apagado autom tico SI SE PRODUCE...

Страница 31: ...io debe leer y comprender el manual del operador antes de usar este producto Alerta de condiciones h medas No exponga la unidad a la lluvia ni la use en lugares h medos Descarga el ctrica Si no se usa...

Страница 32: ...UERTE Opere en reas exteriores bien ventiladas lejos de puertas o ventanas abiertas No exponga la unidad a la lluvia ni la use en lugares h medos Usar un generador en el interior PUEDE MARTARLO EN POC...

Страница 33: ...o incluye un cable de cobre ni una jabalina de puesta a tierra Consulte con un electricista calificado para conocer los requisitos locales de puesta a tierra PARACHISPAS El uso de este equipo puede pr...

Страница 34: ...75 N A 850 1200 1 6 275 600 850 2050 1 4 400 800 1050 2400 1 3 450 950 1350 2700 1 2 600 1000 1800 3600 3 4 850 1200 2600 1 1100 N A 3300 AVISO El requerimiento de voltaje y frecuencia operativa de to...

Страница 35: ...ado al agregar cargas el ctricasalgenerador NOdebehaberequipoalgunoconectado a los tomacorrientes del generador antes de poner en marcha el motor respectivo La manera correcta y segura de administrar...

Страница 36: ...n un centro de servicio calificado para recibir asistencia PANTALLA DIGITAL La pantalla digital muestra el voltaje de CA de salida la frecuencia cu nto tiempo hace que el motor est en marcha desde la...

Страница 37: ...r ADVERTENCIA No intente modificar esta producto ni introducir accesorios no recomendados para la misma Cualquier alteraci n o modificaci n constituye maltrato y puede causar una condici n peligrosa y...

Страница 38: ...onecte el cables rojo con la terminal positiva y el cable negro con la terminal negativa Aseg rese de que todas las conexiones est n firmes NOTA Teniendo cuidado de no causar cortocircuito en las term...

Страница 39: ...adas faltantes o sueltas como tornillos tuercas pernos tapas etc Apriete firmemente todos los sujetadores y las tapas y no accione este producto hasta que todas las partes faltantes o da adas sean re...

Страница 40: ...s ruedas VERIFICACI N Y ABASTECIMIENTO DE LUBRICANTE Vea la figura 9 AVISO Si se intenta arrancar el motor antes de haberse abastecido debidamente de lubricante podr a descomponerse el equipo NOTA Sir...

Страница 41: ...de arranque tanto de impacto trasero como el ctrico Evite el uso prolongado de arranque con manivela pues esto puede da ar el motor La bater a que se suministra es de plomo cido de 12 voltios nominale...

Страница 42: ...el cable de la buj a y al jelo de sta Permita un per odo de enfriamiento de 30 minutos antes de efectuar cualquier tarea de mantenimiento El incumplimiento de cualquiera de estas instrucciones puede...

Страница 43: ...ado debe desecharse en un sitio de desecho aprobado Si necesita m s informaci n consulte a un concesionario de aceite de la localidad MANTENIMIENTO DE LA BUJ A Vea la figura 17 Labuj adebetenereldebid...

Страница 44: ...on el servicio al cliente o con un centro de servicio calificado NOTA El tanque de combustible debe estar vac o antes de reemplazarelfiltro Siesnecesario pongaenfuncionamiento la unidad hasta vaciar e...

Страница 45: ...o de bater a de plomo y cido RT12150 de 12V 15AH 20 HR horas provista con este generador Conecte el mantenedor de carga de la bater a a la l nea de alimentaci n Aseg rese de que el suministro de corri...

Страница 46: ...r limpiar pantalla parachispas Verificar ajustar r gimen de ralent Verificar ajustar holguera de la v lvula1 2 Verificar ajustar par de torsi n del perno con cabeza1 2 Filtro de combustible Inspec cio...

Страница 47: ...o de gasolina o reabastecido de gasolina de mala calidad Compruebe el elemento de filtro de aire Limpie o reemplace seg n sea necesario Comun quese con un centro de servicio calificado Vac e el combus...

Страница 48: ..._ MANUFACTURING NO ___________________________________________ SERIAL NO ______________________________________________________ SERVICIO Para obtener piezas o servicio comun quese con el centro de ser...

Отзывы: