CAUTIONS
Keep batteries out of reach of children.
Do NOT use batteries for application other than those specified in its specification.
Do NOT attempt to dis-assemble
,
re
pair
, damaged, impacted, disposed batteries, otherwise the
battery would leak, get hot, or explode.
Do NOT dispose of the batteries in water, fire, and do not heat the batteries.
Do NOT cause any short circuit
If the voltage of battery pack is above 45V, please be sure to wear insulated gloves when working;
otherwise, there is a risk of severe electrical shock.
Do NOT bring face close to the top of batteries, please keep a sensible distance when you are
measuring and repairing, you must wear safety goggles.
There is sulfuric acid in the battery, do not allow contact of sulfuric acid with skin, cloths, especially
eyes. If eyes come in contact with sulfuric acid,
flush eyes in eyewash
and consult a physician
immediately.
Longer service life will be attained when the battery is operated within an ambient temperature
range of 20~30°C
8.
Exchange of Batteries
8.1 Exchange
Considerations
:
The batteries are discharged 80% (refer the corresponding discharge rates, such as C10, C2 etc.) of
rated capacity, at the same time, the voltage is below 1.8V/cell (the discharge rate for 1 hour is 1.7V/
cell). It should be exchanged.
8.2 Exchange
T
ime
The VRLA battery has
a
certain service life; replace
old
batter
ies
with the new one before end of
service life so that the application run safely and
uninterrupted
.
9.
Maintenance Records
Good records will assist in determining if corrective action is needed to correct charging,
maintenance, or environmental issues that may reduce the maximum life of your battery. If you have any
questions or concerns, please call
Power Storage Solutions
for assistance
(888-813-5049)
.
Taking measurements is recommended
after the battery is installed, and after the battery has been in float
service for 6 months (Base Line Readings for warranty records). Quarterly, or semi-annual maintenance
records are suggested to give customer system protection predictability, however annual maintenance
readings are the minimum to maintain the warranty coverage. Maintenance records will be required for
warranty
claims
.
Below please find some suggested maintenance
forms
to assist the customer’s record keeping on the
battery.