6. Specifications 

 

MODEL 

1K 

2K 

3K 

CAPACITY* 

1000 VA / 800 W 

2000 VA / 1600 W 

3000 VA / 2400 W 

INPUT 

Voltage 

Range 

Low Line Transfer 

85VAC/75VAC/65VAC/55VAC± 5% or 160VAC/140VAC/120VAC/110VAC± 5%   

(Ambient Temp.<35

0

C) 

( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)   

Low Line Comeback 

95VAC/85VAC/75VAC/65VAC or 175VAC/155VAC/135VAC/125VAC ±  5 %   

(Ambient Temp.<35

0

C) 

( based on load percentage 100% - 80 % / 80 % - 70 % / 70 - 60 % / 60 % - 0)   

High Line Transfer 

145 VAC ±  5 % or 300 VAC ±  5 %   

High Line Comeback 

140 VAC ±  5 % or 290 VAC ±  5 %   

Frequency Range 

40Hz ~ 70 Hz 

Phase 

Single phase with ground 

Power Factor 

 0.99 @ nominal voltage (input voltage) 

OUTPUT 

Output voltage 

100/110/115/120/127VAC or 200/208/220/230/240VAC 

AC Voltage Regulation   

± 1% (Batt. Mode) 

Frequency Range   

47 ~ 53 Hz or 57 ~ 63 Hz (Synchronized Range) 

Frequency Range (Batt. Mode) 

50 Hz ±  0.25 Hz or 60Hz ±  0.3 Hz 

Overload 

Ambient Temp.<35

0

105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when 

the utility is normal 

110%~130%: UPS shuts down after 1minute at battery mode or transfer to bypass when the 

utility is normal 

>130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the 

utility is normal 

Current Crest Ratio 

3:1 

Harmonic Distortion 

  3 % THD (linear load); 

  6 % THD (non-linear load) 

Transfer 

Time 

AC Mode to Batt. Mode 

Zero 

Inverter to Bypass 

4 ms (Typical) 

Waveform (Batt. Mode) 

Pure Sinewave 

EFFICIENCY 

AC Mode 

88% 

89% 

90% 

Battery Mode 

83% 

87% 

88% 

BATTERY 

Standard 
Model 

Battery Type 

12 V / 9 AH 

12 V / 9 AH 

12 V / 9 AH 

Numbers 

Recharge Time 

4 hours recover to 90% capacity (Typical) 

Charging Current   

1.0 A (max.) 

Charging Voltage   

27.4 VDC ±  1% 

54.7 VDC ± 1% 

82.1 VDC ± 1% 

Long-run 

Model* 

Battery Numbers 

Charging Current   

1.0A/2.0A/4.0A/6.0 A 

Charging Voltage 

27.4 VDC ±  

1% 

41.0VDC ±  

1% 

54.7 VDC 

± 1% 

82.1VDC 

± 1% 

109.4VDC 

± 1% 

82.1 VDC 

± 1% 

109.4VDC 

± 1% 

PHYSICAL 

Standard 

Model 

Dimension, D X W X H   

282 X 145 X 220 (mm) 

397 X 145 X 220 (mm) 

421 X 190 X 318 (mm) 

Net Weight (kgs) 

9.8 

17 

27.6 

Long-run 

Model* 

Dimension, D X W X H   

282 x 145 x 220 (mm) 

397x 145 x 220(mm) 

Net Weight (kgs) 

4.1 

4.1 

6.8 

6.8 

6.8 

7.4 

7.4 

ENVIRONMENT 

Operation Humidity 

20-90 % RH @ 0- 40°C (non-condensing) 

Noise Level 

Less than 50dBA @ 1 Meter 

MANAGEMENT 

Smart RS-232 or USB 

Supports Windows®  2000/2003/XP/Vista/2008/7/8, Linux, Unix and MAC 

Optional SNMP 

Power management from SNMP manager and web browser 

*Long-run model is only available in 200/208/220/230/240VAC systems. 
** Derate capacity to 80% of capacity in Frequency converter mode or when the output voltage is adjusted to 100/200/208VAC. 

*** Product specifications are subject to change without further notice. 

Содержание VFI-C Series 1KR

Страница 1: ...VFI C Series 1K 2K 3K Online UPS Uninterruptible Power Supply System Version 1 1...

Страница 2: ...2 2 Installation and setup 3 2 1 Rear panel view 3 2 2 Setup the UPS 7 3 Operations 9 3 1 Button operation 9 3 2 LCD Panel 9 3 3 Audible Alarm 11 3 4 LCD display wordings index 11 3 5 UPS Setting 11...

Страница 3: ...er them Do not connect domestic appliances such as hair dryers to UPS output sockets The UPS can be operated by any individuals with no previous experience Connect the UPS system only to an earthed sh...

Страница 4: ...must be kept well away from the batteries Caution risk of electric shock The battery circuit is not isolated from the input voltage Hazardous voltages may occur between the battery terminals and the...

Страница 5: ...thing inside the package is damaged Please keep the original package in a safe place for future use 2 1 Rear panel view 1K India Type IEC Type NEMA Type Schuko Type Universal Type 1KL India Type IEC T...

Страница 6: ...4 2KL India Type IEC Type Schuko Type Universal Type 3K India Type IEC Type NEMA Type Schuko Type Universal Type 3KL India Type IEC Type Schuko Type Universal Type 1KR IEC Type Universal Type...

Страница 7: ...5 China Type 2KR IEC Type Universal Type China Type 3KR IEC Type Universal Type China Type 1KRL IEC Type Universal Type...

Страница 8: ...Universal Type China Type 1 AC input 2 Input circuit breaker 3 USB communication port 4 RS 232 communication port 5 SNMP intelligent slot option 6 External battery connection only available for L mod...

Страница 9: ...status monitoring connect the communication cable one end to the USB RS 232 port and the other to the communication port of your PC With the monitoring software installed you can schedule UPS shutdown...

Страница 10: ...8 Step 6 External battery connection This UPS is not including batteries Please connect external batteries as below chart...

Страница 11: ...in standby mode under power normal or transfer to Bypass mode if the Bypass enable setting by pressing this button Confirm selection key Press this button to confirm selection in UPS setting mode Sele...

Страница 12: ...frequency Load information Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Mode operation information Indicates the UP...

Страница 13: ...re CH Charger FU Bypass frequency unstable EE EEPROM error 3 5 UPS Setting There are three parameters to set up the UPS Parameter 1 It s for program alternatives Refer to below table Parameter 2 and p...

Страница 14: ...t frequency is 60Hz If converter mode is enabled you may choose the following output frequency CF 50 presents output frequency is 50Hz CF 60 presents output frequency is 60Hz 04 ECO enable disable Int...

Страница 15: ...in parameter 3 from 230Vac to 264Vac Default 264Vac For 100 110 115 120 127 VAC models 115 132 setting the high voltage point in parameter 3 from 115Vac to 132Vac Default 132Vac LLS Bypass low voltage...

Страница 16: ...er mode When input frequency is within 40 Hz to 70 Hz the UPS can be set at a constant output frequency 50 Hz or 60 Hz The UPS will still charge battery under this mode Battery mode When the input vol...

Страница 17: ...ltage high 12 x Charger failure 45 x Inverter voltage Low 13 x 3 8 Warning indicator Warning Icon flashing Alarm Low Battery Sounding every second Overload Sounding twice every second Battery is not c...

Страница 18: ...e every second UPS is overload Remove excess loads from UPS output UPS is overloaded Devices connected to the UPS are fed directly by the electrical network via the Bypass Remove excess loads from UPS...

Страница 19: ...up time is shorter than nominal value Batteries are not fully charged Charge the batteries for at least 5 hours and then check capacity If the problem still persists consult your dealer Batteries defe...

Страница 20: ...ler Storage Before storing charge the UPS 5 hours Store the UPS covered and upright in a cool dry location During storage recharge the battery in accordance with the following table Storage Temperatur...

Страница 21: ...1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY AC Mode 88 89 90 Batt...

Страница 22: ...Current Crest Ratio 3 1 Harmonic Distortion 3 THD linear load 6 THD non linear load Transfer Time AC Mode to Batt Mode Zero Inverter to Bypass 4 ms Typical Waveform Batt Mode Pure Sinewave EFFICIENCY...

Страница 23: ...21 Note...

Страница 24: ...22 Power Inspired Ltd Units 5 7 High Point Riding Road Buckingham Road Industrial Estate Brackley Northamptonshire NN13 7BH United Kingdom www powerinspired com...

Отзывы: