C MANUAL

 

 POWER FLAME INCORPORATED

Содержание C1-GO-10

Страница 1: ...C MANUAL POWER FLAME INCORPORATED...

Страница 2: ...6 Removable Total Access Door 27 Optional Board for Sequence Indicator Lights The computer generated Burner Specification Sheets shipped with the burner represent the as built version of your specific...

Страница 3: ...fore starting up the system all appropriate air and oil leak tests should be performed Make certain that the tank atmospheric vent line is unobstructed Refer to page 12 Figure 11 for fuel pump oil pip...

Страница 4: ...valves etc Suction line vacuum values for such compo nents vary by manufacturer A Rule of Thumb to determine total vacuum for suction line sizing is to add 10 to vacuum determined from Figure 10 calcu...

Страница 5: ...r calls for low fire the normally closed Oil Solenoid Return Valve 7 closed at high fire is energized reducing nozzle pressure to the low fire rate Simultaneously the Three Way Solenoid Valve 10 is de...

Страница 6: ...trol Mode Using a Two Step Oil Pump Model C O Field Piped Check Valve At Tank Fuel Shutoff Valve Fusible Link Valve If Required by Code Check Valve Field Piped 12 pressure setting of the pump low fire...

Страница 7: ...urn Pressure Tap 8 5 Metering Valve 7 1 8 Allen Screw For Oil Nozzle Pressure Adjustment Under Cap Vacuum Gauge Inlet Port Optional Return Port For Simplex Nozzle Use Alternate Connec tion to Tee on O...

Страница 8: ...us tion chambers or high heat release pressurized fireboxes Moving the adjustment knob back increases the premix air Gas Oil Linkage Adjustment For Full Modulation Standard System Typical general link...

Страница 9: ...als is for factory use only and should not be used for incoming power connections 2 Close main and checking gas cocks Open suction line manual oil valves and others as appropriate 3 Tighten all screws...

Страница 10: ...uit the particular operating conditions 3 Do not secure flame safeguard control into its wiring base until it has been determined that there are no shorts or grounds in the system 4 Install oil pressu...

Страница 11: ...chamber 18 For small On Off burners with a simplex nozzle adjustments consist primarily of attaining correct fuel air ratios Adjustments should be set to obtain11 121 2 CO2 and no more than a 2 smoke...

Страница 12: ...rm in the boiler or follow specific initial firing recommendations provided by the heat exchanger manufacturer 34 Tighten all linkages and permanently mark settings 35 Limit control check should be ma...

Страница 13: ...sure gauges overhead oil lines or fittings A leaking check valve on the bypass return line from the nozzle can create the same effect 6 The Teflon seal should stay on the nozzle when servicing On some...

Страница 14: ...2 Fuel Oil By Pass Return Closed Approx High Fire Rate GPH 300 PSIG By Pass Return Closed Approx High Fire By Pass Return Pressure PSIG By Pass Return Closed Approx By Pass Return Pressure PSIG Appro...

Страница 15: ...eturn and Firing Rates Will be Reduced Somewhat Consult Factory for Further Information When Supply Pressure to Nozzle is Lower Than 300 PSIG the By Pass Return and Firing Rates Will be Reduced Somewh...

Страница 16: ...lon seal in the Monarch F80BPS and Delavan 33769 nozzles is an integral part of the nozzles and that if the seal is removed accidentally the nozzle must be replaced On the Delavan 30630 and 30637 nozz...

Страница 17: ...ulators should be kept clean and must be replaced if cracked 2 The spark gap must be set in accordance with the dimensions noted Refer to Figures 30 31 32 Ensure that the distance between the electrod...

Страница 18: ...Setting 1 16 Blade Tips After Adj Must be Within 1 16 of A Flat Plane Mark Pipe With Saw For Full Forward Pilot Extends Thru Diffuser 0 125 1 8 5 32 Diameter Orifice Gas Inlet Oil Nozzle Choke Assembl...

Страница 19: ...e or check valve not holding Correct as required GAS OPERATION 1 Burner Motor Runs but Pilot Does Not Light A Gas supply to burner shut off make sure all manual gas supply valves are open Automatic hi...

Страница 20: ...echanical binding of linkage Readjust linkage O Loose wiring connections Check and tighten all connections 2 Oil Flame Ignites but then Flame Safeguard Control Locks Out on Safety A Flame scanner lens...

Страница 21: ...f necessary F On two step pump N O pump mounted oil solenoid valve defective not closing Replace valve or pump G Oil pump coupling loose slipping or defective Replace H Linkage mechanically binding Re...

Страница 22: ...turer s instructions Refractory hold in As required annually Service Technician See Pilot turndown tests High limit safety control Annually Service Technician Refer to heat exchanger manufacturer s in...