CT =

MAX AMPERES

5 AMPERES

IMPORTANT  INSTALLATION  NOTES 

MODEL  SE-4E

110

THE CLOCKWISE TURNING
OF U/S TRIMMER 
ACTIVATES THIS FEATURE AT
HIGHER Hz.  (~74Hz THE HIGHEST)  

25 TURNS TRIMMER   (IT DOES NOT STOP)

THE ANTI-CLOCKWISE TURNING
OF U/S TRIMMER 
ACTIVATES THIS FEATURE AT
LOWER Hz.(~22Hz THE LOWEST)

THE ORANGE NEON INDICATOR IS LIT WHEN:

 

   

                         

THE PHASE SEQUENCE ARE 

WRONG.

THE GREEN LED IS LIT WHEN:

 

THE IDENTITY OF THE PHASES ARE OK.
THE SEQUENCE OF THE PHASES ARE OK. 
THE POLARITY OF CURRENT TRANSFORMER  ARE OK.

                            

THE CIRCUIT OF THIS LED WILL ACTIVATED ONLY IF:       

                     

A:  THE CT IS INSTALLED.     

  

                                   

B:  THE GENERATOR IS UNDER LOAD.

STABILITY 

E-D close:

30% 

stability (default).

E-F  close:  

6

0% stability.

no jumper:            

100% 

stability.

F
E
D

F
E
D

F
E
D

SPECIFICATION

OUTPUT

INPUT

VOLT AC
PHASE
FREQUENCY

VOLT DC
CURRENT
EXC. FIELD OHMS

0V - 150V 

120A CONTINUOUS

 1 Ohm MINIMUM

350-500

NO NEUTRAL

40 - 70 Hz

OPERATIONAL TEMPERATURE  80 C MAX

AUTOMATIC FLASH

REGULATION   +/- 0.5%

WRONG 

PHASE SEQUENCE INDICATOR.

CABLE CHECKER IN PARALLEL OPERATION

.

P/F COMPENSATED IN PARALLEL OPERATION.

UNDER FREQUENCY PROTECTION.

50 - 60 Hz COMPATIBILITY.

USE MAX 32 AMPERES FUSES.

CONNECT FINE VOLTAGE POT ON PANEL (500 Ohm) 

                     

OR ELSE YOU MUST LINK TERMINAL s’ - t’.

IN CASE OF USING 

"

CURRENT TRANSFORMER                           

CT

      

     

IT MUST BE TO PHASE V.

FUSES BOX

32A

32A

32A

    BRUSH
GENERATOR

SWITCH

ACB

MAIN

l

k

L

K

380 - 440 V BUS  BAR

J

K

J

K

X Y Z

U V W

s' t'

CT

U

W

V

  FLASH BUTTON

    

 FOR

OR LINK

AUTOMATIC FLASH

FINE VOLTAGE

POT 500 Ohm

OR LINK s’ - t’ 

A B

R

S

T

l

k

2

2.5mm

2

10mm

2

25mm

POWER & ISOLATION

TRANSFORMER

X Y Z

W

V

U

2

1.5mm

  WRONG PHASE SEQUENCE  

  INDICATOR

Cable checker.

Lit when all cable 
connections are good.

Under Frequency 
protection checker

.

Lit when U/Hz
protection is activated.

UNDER SPEED

F

E

D

STABILITY

-

+

POWER FACTOR

-

+

VOLTAGE

FOR EXCLUSIVE SINGLE OPERATION
THE USE OF 

"

"

 IS 

 

NECESSARY.

CT

NOT

POSITIVE

NEGATIVE

EXCITER

FIELD

2

50mm

UNDER FREQUENCY PROTECTION

Содержание SE-4E110

Страница 1: ...USER MANUAL AUTOMATIC VOLTAGE REGULATOR SE 4E110 POWER ELECTRONICS...

Страница 2: ...AUTOMATIC VOLTAGE REGULATOR SE 4E110 POWER ELECTRONICS...

Страница 3: ...LED IS LIT WHEN THE IDENTITY OF THE PHASES ARE OK THE SEQUENCE OF THE PHASES ARE OK THE POLARITY OF CURRENT TRANSFORMER ARE OK THE CIRCUIT OF THIS LED WILL ACTIVATED ONLY IF A THE CT IS INSTALLED B TH...

Страница 4: ...500 3 NO NEUTRAL 40 70 Hz OPERATIONAL TEMPERATURE 80 C MAX AUTOMATIC FLASH REGULATION 0 5 WRONG PHASE SEQUENCE INDICATOR CABLE CHECKER IN PARALLEL OPERATION P F COMPENSATED IN PARALLEL OPERATION UNDER...

Страница 5: ...ent transformer has from one side the letters K or P1 and on the other side L or P2 From the side K or P1 enters the bar from the generator and as it exits from the L or P2 it is going to ACB i e to m...

Страница 6: ...VOLT trimmer proceed as follows Since the engine has the right periods cycles then the remote knob is adjusted to the middle position Then the VOLT trimmer which is located in the main unit is adjuste...

Страница 7: ...mail com MODELS SE 4A15 SE 4E15 SE 4A65 SE 4E65 SE 3A110 SE 3E110 SE 4E110 SE 4A110 SE 4E150 SE 4A150 SE 4E200 SE 4A200 1 AVR R S T U V W V V AVR 2 AVR U W 3 1 V AVR 2 O 1 L P2 1 L 2 ACB K L s1 s2 K L...

Страница 8: ...tection H U S 1 25 U S 25 2 3 Governor 50Hz 60Hz 44Hz 54Hz 4 U S led led VOLT 5 STAB Stability H STAB pin stability 30 60 100 VOLT Voltage H VOLT VOLT AVR ACB OFF P F Power Factor H P F anti clockwise...