POWER ELECTRONICS
PROFIPOWER
INSTALLATION AND CONNECTION
17
3.2.3.
Connection for Equipments of Power Electronics
3.2.3.1.
Variable Speed Drives of SD250 Series
Use S+ terminal to connect RS485 high signal and use S- terminal
to connect RS485 low signal.
SD25DTC0005AE
P4
MO
MG
24
P1
P2
CM
P3
S+
S-
P5
CM
P6
P7
P8
VR
V1
I
AM
3A
3C
3B
TB3
TB1
TB4
TB2
Figure 3.4 TB1 connector of the control board
RS485 communication data:
Transmission form:
Bus method, Multi drop Link System.
Applicable drives:
SD250.
Converter: RS232
converter.
Connectable drives:
Maximum 31.
Transmission distance:
Below 1.200m maximum (700m recommended).
Recommended cable:
0.75mm² (18AWG), Shield type twisted-pare.
Installation:
S+ and S- terminals of TB1 connector located on control board.
Power supply:
Power supply insulated from the drive power supply.
After connecting the communication line, set the following
parameters as follows:
Par.
Description
Setting
drv Drive mode
3
RS485 communication.
Frq Frequency setting
mode
7 RS485
communication.
I60 Slave No. in
communic. network
Use different numbers in case of more than 1 inverter is
installed.
1 – 250
I61 Transmission speed
3
9.600bps; factory setting.
Содержание Profipower
Страница 1: ...PROFIPOWER PROFIBUS GATEWAY Communication Network profibus gateway...
Страница 2: ......
Страница 3: ...modbus profibus gateway Communication Network Edition June 2007 GBC02CI Rev C...
Страница 4: ...PROFIPOWER POWER ELECTRONICS 2...
Страница 6: ...PROFIPOWER POWER ELECTRONICS 4...
Страница 8: ...PROFIPOWER POWER ELECTRONICS 6 INDEX...
Страница 49: ...POWER ELECTRONICS PROFIPOWER DIAGNOSIS 47...
Страница 51: ...www power electronics com...