Reference potential and ground of all electrical operating supplies
n
Installation parts and cabinets with your CNC control unit have
to be connected in star topology with the isolation/protected
ground conductor system to avoid ground loops.
n
Sufficiently dimensioned potential compensation lines have to
be laid if there are potential differences between installation
parts and cabinets
Area-wide grounding of the inactive metal parts
n
A central connection between the ground and the protected
ground conductor system have to be installed.
n
All inactive metals have to be connected extensively and impe-
dance-low.
Fixing of the cable shield
n
Data cables and analog cables must be laid separately from
each other.
n
The cable shield has to be laid extensively on a protected
ground conductor rail directly after the cabinet entry and the fix-
ation of the shield with cable clamps.
n
The isolation / protected ground rail has to be connected impe-
dance-low with the cabinet.
n
The metallic or metallized plug cases for shielded cables must
be used.
n
When transmitting signals with small amplitudes the one sided
grounding of the cable shield may be favorable.
Electromagnetic interferences may interfere with the control unit:
n
Electromagnetic fields (RF coupling)
n
Magnetic fields with power frequency
n
Power supply
n
Protected ground conductor
n
Superbus system
Depending on the spreading medium and the distance to the inter-
ference cause, interferences to the control unit occur by means of
capacitive, galvanic, inductive or radiant coupling mechanisms.
Possible Interferences
PA 8000 EL CNC control unit
Technical data
24.09.2015 | 70
Содержание PA 8000 EL
Страница 1: ...PA 8000 EL CNC control unit Installation instructions...
Страница 6: ...PA 8000 EL CNC control unit Table of contents 24 09 2015 6...
Страница 26: ...PA 8000 EL CNC control unit Safety 24 09 2015 26...
Страница 64: ...PA 8000 EL CNC control unit Design and function 24 09 2015 64...
Страница 67: ...4 4 Dimension sheet Fig 39 dimension sheet PA 8000 EL CNC control unit Technical data 24 09 2015 67...
Страница 72: ...PA 8000 EL CNC control unit Technical data 24 09 2015 72...
Страница 78: ...Fig 42 Top bottom spacing PA 8000 EL CNC control unit Installation 24 09 2015 78...
Страница 84: ...PA 8000 EL CNC control unit Installation 24 09 2015 84...
Страница 99: ...Fig 48 RMA Form RMA Form PA 8000 EL CNC control unit Service and return process 24 09 2015 99...
Страница 102: ...PA 8000 EL CNC control unit Dismounting and decommissioning 24 09 2015 102...
Страница 104: ...Fig 49 EC Declaration of Conformity PA 8000 EL CNC control unit EC Declaration of Conformity 24 09 2015 104...
Страница 106: ...PA 8000 EL CNC control unit Proof of change 24 09 2015 106...