Table T Alarm Source Bit-Mask
Register
Source
Bit
Low
Register
BriteSpot Plus Channel 1
0
BriteSpot Plus Channel 2
1
BriteSpot Plus Channel 3
2
BriteSpot Plus Channel 4
3
BriteSpot Plus Channel 5
4
BriteSpot Plus Channel 6
5
BriteSpot Plus Channel 7
6
BriteSpot Plus Channel 8
7
BriteSpot Plus Channel 9
8
BriteSpot Plus Channel 10
9
BriteSpot Plus Channel 11
10
BriteSpot Plus Channel 12
11
BriteSpot Plus Channel 13
12
BriteSpot Plus Channel 14
13
BriteSpot Plus Channel 15
14
BriteSpot Plus Channel 16
15
Mid 1
Register
BriteSpot Plus Channel 17
16
BriteSpot Plus Channel 18
17
Reserved for Future Use
18 - 35
Mid 2
Register
MCS 1
36
MCS 2
37
MCS 3
38
MCS 4
39
MCS 5
40
MCS 6
41
MCS 7
42
MCS 8
43
EcoVisor 1
44
EcoVisor 2
45
EcoVisor 3
46
EcoVisor 4
47
Hi Register
Reserved for Future Use
48 - 63
Example:
Reading Input Registers 30114 - 30116
(Alarm Channel Low - Mid 2 for Alarm 1)
Table U Example Alarm Data
Input Register Address
(Name)
Dec
Hex
Binary
30114 (Alarm Channel Low)
64
0x 0040 0b 0000 0000 0100 0000
30115 (Alarm Channel Mid 1)
1
0x 0001 0b 0000 0000 0000 0001
30116 (Alarm Channel Mid 2)
0
0x 0000 0b 0000 0000 0000 0000
In the case above, the bits that are set
indicate that BriteSpot® channels 7 and
17 have exceeded the alarm threshold.
b. Relay Output
The BriteSpot Plus conversion module
is equipped with normally open dry-
contact type relays depending on the
unit configuration (
). The
relay are intended to be used by the
operator for wiring to an annunciator
or any similar device should action
be desired upon the occurrence of an
alarm. The specific settings for the
relays may be configured through the
UI or the web page.
There are four relay status registers
which are described in
The first indicates whether each relay
triggers on a warning or alarm. The
other three indicate what alarms trigger
the given relay.
Table V Relay Input Bit Mask
8-15
7
6
5
4
3
2
1
0
Reserved
for Future
Use
Alarm
8
Alarm
7
Alarm
6
Alarm
5
Alarm
4
Alarm
3
Alarm
2
Alarm
1
Example:
Reading Input Registers 30051 (Relay 1
Inputs)
Содержание BriteSpot Plus
Страница 4: ...Powered by Safety 01 4IB 48041 BriteSpot Plus This page is left blank intentionally ...
Страница 29: ...Powered by Safety 19 Installation 01 4IB 48041 Figure 20 Panel Mount Clip Installation X X ...
Страница 57: ...Powered by Safety 47 Appendix A 01 4IB 48041 Figure 64 10250 BSPL 18C1P1E0X0 Dimensions ...
Страница 58: ...Powered by Safety 48 Appendix A 01 4IB 48041 BriteSpot Plus Figure 65 10251 BSPL 09C1P E0X0 Dimensions ...