background image

1- Moun ng Fixture and Op cal Fiber Installa on

Required for Installa on

 

A - Secure the Moun ng Fixture to Busbar and Connect Fiber

Tools for Fiber Moun ng:

 Adjustable Wrench

  1.5 mm Allen Key
  Guillo ne Cu er

Components for Hardware Installa on:

B - Route the Fiber to Low-Voltage Cabinet 

I. Insert the screw with the washer through the 

fixture and busbar.

II. Insert  the  washers  and  secure  it  with  a  nut. 

Ensure the hole for fiber inser on is pointed in 
the direc on of the fiber rou ng.

Installa on of the BriteSpot Fiber-Op c Temperature Sensor has been engineered to be simple and straigh orward. The 
following  manual  will  describe  in  detail  the  3  steps  needed  for  installa on.  No  specialized  knowledge  of  fiber  op cs  is 
necessary. A basic understanding of switchgear topology and moun ng methods is required.

35 mm DIN rail (6"-8") and moun ng 
hardware

CAT5  Ethernet cable  (if  connec ng  to  SCADA  or 
computer.

Quick Start Guide

G3

BriteSpot

Temperature Monitoring

Powell Canada Inc, 
Suite 201, 55 Gos ck Place

North Vancouver, BC, V7M 3N2

- MAX 100ºC

Sensor Tip

- MAX 120ºC

          Fiber

R

Do NOT bend fiber  ghter 
than 12 mm (1/2") radius

Do  not  fasten  or  a ach  ANY 
moun ng  hardware  ( e-wraps, 
etc.)  to  at  least  a  30  cm  (12") 
length  of  fiber  between  the 
por on  of  the  probe  at  high 
v o l t a g e   a n d   i t s   fi r s t   n o n -
energized point of contact.

Keep  away  from  sources  of 
excessive  heat  whenever 
possible. Fiber probe shall not 
be  a ached  to  surfaces  with 
te m p e rat u re s   exc e e d i n g 
100ºC or 200ºF.

!

!

 Voltage: 12-24 VDC (0.12A@24VDC)

  Power: 3 Wa s (Max)

Power Supply Requirements:

III. Insert fiber into the holding fixture and secure it  

with a 1.5 mm hex screwdriver.

Avo i d   r u n n i n g   fi b e rs   I n   t h e 
direc on of the fold of the boot to 
minimize bending and  damage of 
the fiber.  

!

Содержание BriteSpot Fiber-Opc

Страница 1: ...witchgeartopologyandmoun ngmethodsisrequired 35 mm DIN rail 6 8 and moun ng hardware CAT5 Ethernet cable if connec ng to SCADA or computer Quick Start Guide G3BriteSpot Temperature Monitoring Powell Canada Inc Suite 201 55 Gos ck Place North Vancouver BC V7M 3N2 MAX 100ºC Sensor Tip MAX 120ºC Fiber R Do NOT bend fiber ghter than 12 mm 1 2 radius Do not fasten or a ach ANY moun ng hardware e wraps e...

Страница 2: ... 100 STAT RST ID BriteSpot G3 BS3 BS2 BS1 LIN K COM SYS 4 5 6 7 8 9 1 2 3 10 100 STAT RST ID BriteSpot G3 BS3 BS2 BS1 LIN K COM SYS 4 5 6 7 8 9 1 2 3 HMI PLC G3 Slave Device 1 31 10 100 STAT RST ID BriteSpot G3 BS3 BS2 BS1 LIN K COM SYS 4 5 6 7 8 9 1 2 3 10 100 STAT RST ID BriteSpot G3 BS3 BS2 BS1 LIN K COM SYS 4 5 6 7 8 9 1 2 3 HMI Master Hub G3 Slave Devices 1 2 Notethatterminals1and6 aswellas2a...

Страница 3: ...oth the SYS and COM LEDsstaygreen about5seconds II Releasethebu onandthedevicewillrestartwithitsdefaultvalues Quick Start Guide G3 BriteSpot Temperature Monitoring Powell Canada Inc Suite 201 55 Gos ck Place North Vancouver BC V7M 3N2 Note that if connec ng via Ethernet to a computer directly the Internet Protocol Version 4 IP address must be set in the networkse ngonthecomputer The first 3 numbers...

Страница 4: ... 11 17 03 2014 DEVICE PARAMETERS DEGREE C LOG RATE 1 MIN MOD PORT 502 SLAVE ID 7 BAUD 19200 DEVICE PARAMETERS DEGREE C LOG RATE 1 MIN MOD PORT 502 SLAVE ID 7 BAUD 19200 1 2 1 FIBER POWER 0 9 0 9 9 9 0 9 0 ALARM STATUS E A W BRITEALERT STATUS WARNING ERROR NUM 1 01 05 ALERT CONFIG SOUND OFF SET THRESHOLD C WARNING 90 ALARM 105 BRITEALERT STATUS WARNING ERROR NUM 1 01 05 1 2 BRITEALERT STATUS WARNIN...

Отзывы: