01.4IB.51809
Powered by Safety
®
14
Installation & Operation
Electric Remote Racking Device for
Powell LV Switchgear w/ Siemens Circuit Breakers
o. When the push button is depressed, the
“OUT” indicator light (Figure 2, c) will be
energized and illuminated.
p. When the breaker is fully racked “OUT”
the remote racking device torque
limiter will begin to slip and there will
be a clear clicking sound along with a
vibration of the racking device. At this
point, release the push button. The
breaker position indicator will read
“DISCONNECTED”.
Note:
If the remote location that was
selected is in a location where the
breaker can not be seen and the
torque limiter can not be heard it
is suggested to perform a racking
operation on dead bus and time the
operation. Document the time and
rack the breaker in and out using the
documented time.
q. Disconnect the 120V power source and
remove the remote racking device.
r. Remove the racking device from the
breaker door and breaker.