![Powell 38PV40ARMM-4 Скачать руководство пользователя страница 57](http://html1.mh-extra.com/html/powell/38pv40armm-4/38pv40armm-4_instruction-bulletin_1585524057.webp)
Powered by Safety
®
47
Maintenance
01.4IB.65131
c. Tripping System Adjustment
Prior to adjustments, servicing, maintenance,
or any act requiring the operator to make
physical contact with the equipment, the
power source must be disconnected and the
equipment grounded. Failure to do so may
result in death or serious injury.
!
WARNING
To adjust the PowlVac 38™ ARM 3000A
Series 4 Vacuum Circuit Breaker Tripping
System perform the following steps:
1. Prior to performing this adjustment
procedure, all high voltage
components shall be deenergized,
disconnected by means of visible
break and securely grounded, and
ensure that the control circuits are
deenergized.
2. Remove the circuit breaker front
cover.
3. Loosen the secondary trip prop
adjusting screw locking nut several
full turns.
!
CAUTION
Do NOT allow the secondary trip prop
adjusting screw to turn while loosening the
locking nut. Failure to observe this caution
will severely damage the mechanism.
4. Manually charge the circuit breaker
main spring.
5. Manually CLOSE the circuit breaker.
6. Slowly turn the secondary trip prop
adjusting screw
clockwise in 1/8 turn (45˚)
increments until the breaker trips
OPENS. Carefully note the rotational
position of the too used to turn the
adjusting screw at the moment the
breaker operates. Do NOT turn the
screw any further clockwise after the
breaker operates.
7. Turn the secondary trip prop
adjusting screw counterclockwise
1½ full turns from the position
noted in
step 6
.
8. While holding the secondary trip
prop adjusting screw from turning,
securely tighten the secondary trip
prop adjusting screw locking nut.
9. Manually charge the main closing
spring using the manual charge
handle per
D. Placing the Circuit Breaker Into
Service, 4) Mechanical Operation
10. Manually CLOSE the circuit breaker.
11. Using leaf type feeler gauges with
a total of 0.090” thickness selected,
position the feeler gauge as shown
.
Figure 18 Feeler Gauge
12. Slowly depress the trip coil armature
as shown in
. Depress the
handle until the armature contacts
the feeler gauges. The circuit
breaker should not trip.