Installation
01.4IB.65131
Prior to removing the circuit breaker from the
circuit breaker compartment, make sure that
the control circuits are deenergized.
!
CAUTION
a. To remove the circuit breaker from
the Connected position to the Test/
Disconnect Position perform the
following:
1. Verify that the circuit breaker
open/closed indicator displays
“
BREAKER OPEN
”
. If “
CLOSED
”,
operate the circuit breaker control
switch to open the circuit breaker.
2. Open the compartment door. If the
padlock seal is present, remove the
seal. Open the emergency racking
drive shaft shutter. Place the racking
handle socket onto the racking drive
shaft shutter. The racking handle
socket may be used to push down
the shutter to gain access to the
racking drive.
3. Turn the racking handle
clockwise
until the breaker position indicator
displays
“
BREAKER TEST/DISCONNECTED
”
.
4. Remove the racking handle and
verify that the emergency racking
drive shaft shutter has returned to its
normal position.
Note: This is the Test Position.
b. To remove the circuit breaker from the
Test position out of the circuit breaker
compartment perform the following:
1. Push the secondary disconnect latch
to the left. This will
unlock the secondary disconnect
plug, allowing it to be removed.
Remove the secondary disconnect
plug.
Removal of the secondary disconnect plug will
trip a closed breaker and discharge the main
closing spring.
!
CAUTION
2. Press the anti-rollout latch to
release the circuit breaker and
pull the circuit breaker out of the
compartment using the handles.
3. Once the circuit breaker has been
removed and service has been
performed, replace the padlock seal.