AUTO TEST VSR (VSR-AT)

VANE TYPE WATERFLOW ALARM SWITCH WITH 

ELECTRONIC RETARD AND AUTO TEST FEATURE

MFG. #5401239 - REV B

3/14

Do not connect power directly to these terminals.

DWG1239-3

C        NO      C                 NO    GND  LED   

SWITCH 

   +          -

ALARM

ALARM

24 VDC PWR

From power source

suitable for bell,

120 VAC connection shown

Bell

Load

(Black)

Neutral

(White)

Line 

(Black)

EOLR

Contact 

Monitor 

Module

COM

NO

Addressable 

Relay

SLC 

from 

FACP

Fig. 7 

Typical Electrical Connections For Operation by Addressable Fire Alarm Panel

Aux. power of 

fire panel or

other Listed 24 

VDC supply.

24 VDC @ 120 mA.

Notes: 

 

1.  The model VSR-AT has two sets of alarm contacts:

• 

The connection to the waterflow zone of the fire panel involves 3 

terminals on the VSR-AT. C 

 and NO. Connect the two wires 

from the waterflow zone of the fire panel to the C and NO terminals 

with the End of Line Resistor of the fire panel being connected 

across the C and other terminal as shown on the drawing. The 

NO and resistor terminal are internally connected by a normally 

energized relay. A loss of power or failed AutoTest causes the relay 

to drop out and initiate a trouble on the fire panel.

•  The second connection may be used for a local audible or visual 

annunciator.

2.  For supervised circuits, see “Switch Terminal Connections” drawing 

and warning note (Fig. 3).     

The Auto Test feature can be initiated by momentarily connecting 

the GND and Switch terminals together using the Auto Test Control 

(ATC) or any UL Listed switch or relay. 

Содержание VSR-AT Series

Страница 1: ...The alarm contacts are actuated when a flow of 10 GPM 38 LPM or more occurs downstream of the device The flow condition must exist for a period of time necessary to overcome the selected retard time The VSR AT may be remotely tested without flowing water by using the optional auto test Control model ATC 1or ATC 4 or the use of addressable relays and monitor modules as part of a listed addressable ...

Страница 2: ...d torque see the chart in Fig 1 The vane must not rub the inside of the pipe or bind in any way ADAPTER USE 2 5180162 ADAPTERS AS SHOWN ABOVE DN50 ONLY ADAPTER 50mm 20mm 2mm MAX DWG 1146 1F Fig 1 Compatible Pipe Installation Requirements Model Nominal Pipe Size Nominal Pipe O D Pipe Wall Thickness Hole Size U Bolt Nuts Torque Schedule 10 UL Schedule 40 UL BS 1387 LPC DN VDS inch mm inch mm inch mm...

Страница 3: ...e inoperable risking severe property damage and loss of life Do not strip wire beyond 3 8 of length or expose an uninsulated conductor beyond the edge of the terminal block When using stranded wire capture all strands under the clamping plate Maintenance Inspect detectors monthly If leaks are found replace the detector The VSR AT waterflow switch should provide years of trouble free service Fig 4 ...

Страница 4: ...te From power source suitable for bell 120 VAC connection shown See Note 1 Bell Orange ATC 1 Mounts to standard single gang handy or switch box 4 L X 2 1 8 W X 1 7 8 D such as RACO 660 or equivilent Box not included Black Blue The ATC consists of a momentary push button switch a key switch to enable disable the push button and an LED Turning the keyswitch to Test will enable the push button switch...

Страница 5: ... contacts The connection to the waterflow zone of the fire panel involves 3 terminals on theVSR AT C and NO Connect the two wires fromthewaterflowzoneofthefirepaneltotheCandNOterminals with the End of Line Resistor of the fire panel being connected across the C and other terminal as shown on the drawing The NO and resistor terminal are internally connected by a normally energized relay Aloss of po...

Страница 6: ... The NO and End of Line Resistor terminals are connected in ternally by a normally energized relay A loss of power or failed AutoTest causes the relay to drop out and initiates a trouble at the fire panel The only way to clear the trouble on the fire panel is to conduct a successful AutoTest using the ATC test switch or other test method Conducting an actual waterflow test will put the panel in al...