background image

PRINTED IN USA

 PAGE 2 OF 6

AUTO TEST VSR (VSR-AT)

VANE TYPE WATERFLOW ALARM SWITCH WITH 

ELECTRONIC RETARD AND AUTO TEST FEATURE

MFG. #5401239 - REV B

3/14

Do not trim the paddle. Failure to follow these instructions may prevent 

the device from operating and will void the warranty. Do not obstruct or 

otherwise prevent the tripstem of the flowswitch from moving when water 

flows as this could damage the flowswitch and prevent an alarm. If an alarm 

is not desired, a qualified technician should disable the alarm system. 

DWG 1239-2

Retard Adjustment

The delay can be adjusted by turning switch S1 (see Fig. 6) to the 

desired time delay (0 = no delay and 9 = 90 second delay).  Factory 

setting is set at 3 = 30 second delay. The time delay should be set at 

the minimum required to prevent false alarms.

Installation  (

see Fig. 1)

These devices may be mounted on horizontal or vertical pipe.  On horizontal pipe they shall be installed on the top side of the pipe where they 

will be accessible.  The device should not be installed within 6" (15 cm) of a fitting which changes the direction of the waterflow or within 24" 

(60 cm) of a valve or drain.

Drain the system and drill a hole in the pipe using a hole saw in a slow speed drill (see Fig. 1). Clean the inside pipe of all growth or other 

material for a distance equal to the pipe diameter on either side of the hole. Roll the vane so that it may be inserted into the hole; do not bend 

or crease it. Insert the vane so that the arrow on the saddle points in the direction of the waterflow. Take care not to damage the non-corrosive 

bushing in the saddle. The bushing should fit inside the hole in the pipe. Install the saddle strap and tighten nuts alternately to required torque 

(see the chart in Fig. 1). The vane must not rub the inside of the pipe or bind in any way.

ADAPTER

USE (2) 5180162 ADAPTERS AS SHOWN ABOVE

        DN50 ONLY

ADAPTER

50mm

20mm ±2mm MAX.

DWG# 1146-1F

Fig. 1

Compatible Pipe/ Installation Requirements

Model

Nominal Pipe 

Size

Nominal Pipe 

O.D.

Pipe Wall Thickness

Hole Size

U-Bolt Nuts 

Torque

Schedule 10 (UL) Schedule 40 (UL)

BS-1387 (LPC)

DN (VDS)

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

inch

mm

ft-lb

n-m

VSR AT-2

2

DN50

2.375

60.3

0.109

2.77

0.154

3.91

0.142

3.6

0.091

2.3

1.25 + .125/-.062

33.0 ± 2.0

20

27

VSR AT-2 1/2

2.5

-

2.875

73.0

0.120

3.05

0.203

5.16

 -

-

-

-

VSR AT-2 1/2

 -

DN65

3.000

76.1

-

-

-

-

0.142

3.6

0.102

2.6

VSR AT-3

3

DN80

3.500

88.9

0.120

3.05

0.216

5.49

0.157

4.0

0.114

2.9

2.00 ± .125

50.8 ± 2.0

VSR AT-3 1/2

3.5

 -

4.000

101.6

0.120

3.05

0.226

5.74

-

-

-

-

VSR AT-4

4

DN100

4.500

114.3

0.120

3.05

0.237

6.02

0.177

4.5

0.126

3.2

VSR AT-5

5

-

5.563

141.3

0.134

3.40

0.258

6.55

-

-

-

-

VSR AT-5

-

DN125

5.500

139.7

-

-

-

-

0.197

5.0

0.142

3.6

VSR AT-6

6

DN150

6.625

168.3

0.134

3.40

0.280

7.11

0.197

5.0

0.157

4.0

VSR AT-8

8

DN200

8.625

219.1

0.148

3.76

0.322

8.18

0.248

6.3

0.177

4.5

(Flowing water activates 

device in one direction only.)

DO NOT LEAVE COVER OFF FOR 

AN EXTENDED PERIOD OF TIME

DIRECTION OF 

WATERFLOW

TIGHTEN NUTS 

ALTERNATELY

MOUNT ON PIPE SO 

ARROW ON SADDLE 

POINTS IN DIRECTION 

OF WATERFLOW

ROLL PADDLE IN 

OPPOSITE DIRECTION 

OF WATERFLOW

Hole must be drilled perpendicular to the pipe and vertically centered. 

Refer to the Compatible Pipe/Installation Requirements chart for size. 

Correct

Incorrect

Do not leave cover off for an extended period of time as leaving the cover 

off could result in damage to the VSR and result in improper operation. 

On horizontal installations, it may be necessary to install a vent such as the 

Potter PAV or similar to exhaust air out of the system and allow the piping to 

fill with water to ensure proper operation of the Auto Test VSR. 

Содержание VSR-AT Series

Страница 1: ...The alarm contacts are actuated when a flow of 10 GPM 38 LPM or more occurs downstream of the device The flow condition must exist for a period of time necessary to overcome the selected retard time The VSR AT may be remotely tested without flowing water by using the optional auto test Control model ATC 1or ATC 4 or the use of addressable relays and monitor modules as part of a listed addressable ...

Страница 2: ...d torque see the chart in Fig 1 The vane must not rub the inside of the pipe or bind in any way ADAPTER USE 2 5180162 ADAPTERS AS SHOWN ABOVE DN50 ONLY ADAPTER 50mm 20mm 2mm MAX DWG 1146 1F Fig 1 Compatible Pipe Installation Requirements Model Nominal Pipe Size Nominal Pipe O D Pipe Wall Thickness Hole Size U Bolt Nuts Torque Schedule 10 UL Schedule 40 UL BS 1387 LPC DN VDS inch mm inch mm inch mm...

Страница 3: ...e inoperable risking severe property damage and loss of life Do not strip wire beyond 3 8 of length or expose an uninsulated conductor beyond the edge of the terminal block When using stranded wire capture all strands under the clamping plate Maintenance Inspect detectors monthly If leaks are found replace the detector The VSR AT waterflow switch should provide years of trouble free service Fig 4 ...

Страница 4: ...te From power source suitable for bell 120 VAC connection shown See Note 1 Bell Orange ATC 1 Mounts to standard single gang handy or switch box 4 L X 2 1 8 W X 1 7 8 D such as RACO 660 or equivilent Box not included Black Blue The ATC consists of a momentary push button switch a key switch to enable disable the push button and an LED Turning the keyswitch to Test will enable the push button switch...

Страница 5: ... contacts The connection to the waterflow zone of the fire panel involves 3 terminals on theVSR AT C and NO Connect the two wires fromthewaterflowzoneofthefirepaneltotheCandNOterminals with the End of Line Resistor of the fire panel being connected across the C and other terminal as shown on the drawing The NO and resistor terminal are internally connected by a normally energized relay Aloss of po...

Страница 6: ... The NO and End of Line Resistor terminals are connected in ternally by a normally energized relay A loss of power or failed AutoTest causes the relay to drop out and initiates a trouble at the fire panel The only way to clear the trouble on the fire panel is to conduct a successful AutoTest using the ATC test switch or other test method Conducting an actual waterflow test will put the panel in al...

Отзывы: