AUTO TEST VSR (VSR-AT)

VANE TYPE WATERFLOW ALARM SWITCH WITH 

ELECTRONIC RETARD AND AUTO TEST FEATURE

MFG. #5401239 - REV B

3/14

UL,  CUL,  FM   Approved   

Service Pressure:         

450 PSI (31 BAR) - UL 

 

          

Flow Sensitivity Range for Signal:                                  

 

  

     4-10 GPM (15-38 LPM) - UL 

               

Maximum Surge:        

18 FPS (5.5 m/s)

Contact  Ratings:

   2.5 AMP @ 125/250 VAC & 30 VDC

Power Requirements:

 24 VDC From Listed or Approved Source    

 

 

      With Battery Backup

Typical Current Draw:

  

 

Standby 20 mA

 

Alarm 65 mA

 

Autotest 120 mA

Conduit Entrances:

   Two knockouts provided for 1/2" conduit.

Environmental Specifications:

    

 

•  NEMA 4/IP54 Rated Enclosure suitable for indoor or  

outdoor use with factory installed gasket and die-cast housing 

when used with appropriate conduit fitting.

 

•  Temperature Range:  40°F - 120°F, (4.5°C - 49°C) - UL

 

•  Non-corrosive sleeve factory installed  in saddle.

Service Use:

     

 

 

 

 

 

      

Automatic 

Sprinkler   NFPA-13 

 

One or two family dwelling   

 

NFPA-13D 

 

Residential occupancy up to four stories 

NFPA-13R 

National Fire Alarm Code 

 

 

NFPA-72 

Ordering Information

Nominal Pipe Size

Model

Part #

Replacement PCB #

2"

DN50

VSR-AT-2

1116102

1029074

2 1/2"

DN65

VSR-AT-2 1/2

1116125

1029075

3"

DN80

VSR-AT-3

1116103

1029076

3 1/2"

-

VSR-AT-3 1/2

1116135

1029077

4"

DN100

VSR-AT-4

1116104

1029078

5"

-

VSR-AT-5

1116105

1029079

6"

DN150

VSR-AT-6

1116106

1029080

8"

DN200

VSR-AT-8

1116108

1029081

Optional Power Supply: Ordering Information

Model

Description

Part Number

-

Power Supply

3006479

BT-80

12V Battery-8AH (2 REQUIRED)

5130084

Optional Test Switch: Ordering Information

Model

Description

Part Number

ATC-1

Single Zone Test Control

1000221

ATC-4

Four Zone Test Control

1000224

SGB-R

Single Gang Box-Red

1000483

DGB-R

Double Gang Box-Red

1000484

General Information

The model VSR-AT is an electronic vane type waterflow switch for 

use on wet sprinkler systems. It is UL Listed and FM Approved for 

use on steel pipe schedules 10 thru 40 sizes 2” thru 8”. See ordering 

Information chart.

The VSR-AT may also be used as a sectional waterflow detector on large 

systems. The VSR-AT has two sets of alarm contacts and an adjustable 

instantly recycling electronic retard. The alarm contacts are actuated 

when a flow of 10 GPM (38 LPM) or more occurs downstream of the 

device. The flow condition must exist for a period of time necessary to 

overcome the selected retard time.

The VSR-AT may be remotely tested without flowing water by using 

the optional auto test Control model ATC-1or ATC-4 or the use of 

addressable relays and monitor modules as part of a listed addressable 

  

Installation must be performed by qualified personnel and in    

    

   accordance with all national and local codes and ordinances. 

•  Shock hazard. Disconnect power source before servicing. Serious        

   injury or death could result.

•  Risk of explosion. Not for use in hazardous locations. Serious  

 

   injury or death could result.

Specifications subject to change without notice.

fire alarm panel. 

When the auto test feature is initiated, the VSR-AT performs a self test to 

ensure compliance with UL requirements regarding waterflow detection 

and retard time. In addition, the auto test feature ensures the integrity of 

the paddle/trip stem assembly. A successful completion of the auto test 

will activate both sets of normally open contacts on the flow switch. If 

the auto test detects a problem with the trip stem/paddle assembly or if 

there is no water in the pipe, neither normally open contact will operate 

and the flow switch will indicate a trouble condition at the test switch 

and transmit a trouble signal to the fire alarm panel.

Enclosure

 

The VSR-AT switches and retard device are enclosed in a general 

purpose, die-cast  housing.  The cover is held in place with two tamper 

resistant screws which require a special key for removal.  

Waterflow switches that are monitoring wet pipe sprinkler systems shall 

not be used as the sole initiating device to discharge AFFF, deluge, 

or chemical suppression systems.  Waterflow switches used for this 

application may result in unintended discharges caused by surges, 

trapped air, or short retard times.

Potter Electric Signal Company, LLC • St. Louis, MO • Phone: 866-956-1211/Canada 888-882-1833

 

• www.pottersignal.com

Important: 

This document contains important information on the 

installation and operation of VSR-AT waterflow switches. Please read 

all instructions carefully before beginning installation.  A copy of this 

document is required by NFPA 72 to be maintained on site.

Содержание VSR-AT Series

Страница 1: ...The alarm contacts are actuated when a flow of 10 GPM 38 LPM or more occurs downstream of the device The flow condition must exist for a period of time necessary to overcome the selected retard time The VSR AT may be remotely tested without flowing water by using the optional auto test Control model ATC 1or ATC 4 or the use of addressable relays and monitor modules as part of a listed addressable ...

Страница 2: ...d torque see the chart in Fig 1 The vane must not rub the inside of the pipe or bind in any way ADAPTER USE 2 5180162 ADAPTERS AS SHOWN ABOVE DN50 ONLY ADAPTER 50mm 20mm 2mm MAX DWG 1146 1F Fig 1 Compatible Pipe Installation Requirements Model Nominal Pipe Size Nominal Pipe O D Pipe Wall Thickness Hole Size U Bolt Nuts Torque Schedule 10 UL Schedule 40 UL BS 1387 LPC DN VDS inch mm inch mm inch mm...

Страница 3: ...e inoperable risking severe property damage and loss of life Do not strip wire beyond 3 8 of length or expose an uninsulated conductor beyond the edge of the terminal block When using stranded wire capture all strands under the clamping plate Maintenance Inspect detectors monthly If leaks are found replace the detector The VSR AT waterflow switch should provide years of trouble free service Fig 4 ...

Страница 4: ...te From power source suitable for bell 120 VAC connection shown See Note 1 Bell Orange ATC 1 Mounts to standard single gang handy or switch box 4 L X 2 1 8 W X 1 7 8 D such as RACO 660 or equivilent Box not included Black Blue The ATC consists of a momentary push button switch a key switch to enable disable the push button and an LED Turning the keyswitch to Test will enable the push button switch...

Страница 5: ... contacts The connection to the waterflow zone of the fire panel involves 3 terminals on theVSR AT C and NO Connect the two wires fromthewaterflowzoneofthefirepaneltotheCandNOterminals with the End of Line Resistor of the fire panel being connected across the C and other terminal as shown on the drawing The NO and resistor terminal are internally connected by a normally energized relay Aloss of po...

Страница 6: ... The NO and End of Line Resistor terminals are connected in ternally by a normally energized relay A loss of power or failed AutoTest causes the relay to drop out and initiates a trouble at the fire panel The only way to clear the trouble on the fire panel is to conduct a successful AutoTest using the ATC test switch or other test method Conducting an actual waterflow test will put the panel in al...

Отзывы: