UDACT-9100 Dialer Installation and Operation Instructions
3
Introduction and Features
UDACT-9100 is a single board Digital Communicator that can connect to a Potter Fire Alarm Control Panel (FACP)
such as PFC-9000 and PFC-5000, via an RS-485 data link and common relay connection on a single ribbon cable.
It can transmit Zoned Alarm, Supervisory and Trouble information on two telephone lines to a Digital Alarm
Communicator Receiver (DACR).
Features:
• Receives events from the FACP via an RS-485 data link and common relay connection.
• Communicates to a DACR using
Ademco Contact ID
or
SIA DCS
reporting protocols (300 baud or 110 baud
rate).
• The UDACT-9100 has the ability of disconnecting the incoming and outgoing calls and capturing the line for
transmission to the DACR.
• Provides telephone line monitoring and reports status via LED indication on-board, yellow for trouble and red
for dialing out.
• User configurable locally by on-board keypad and a
CFG-LCD Configuration Tool
or using a
UIMA
and
computer with serial port or USB. Remotely configurable via a Personal Computer modem.
• Provides event logs of 500 entries each to save events from local dialer or remote fire alarm panel. These logs
can be reviewed locally with CFG-LCD Configuration Tool or remotely via modem.