background image

MFG. #5406081 - REV A

7/13

PRINTED IN USA

PAGE 1 OF 2

RA-6006

LCD ANNUNCIATOR INSTALLATION

Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-956-1211 • Tech Support: 866-240-1870 • Canada: 888-882-1833

 

• www.pottersignal.com

Install in accordance with compatible fire alarm panel.

Description

The RA-6006 is a LCD remote annunciator for the PFC-6006 

Sprinkler Monitoring Panel. The RA-6006 communicates using a 

RS-485 connection to the main panel providing common indication 

of Alarms, Supervisory, Trouble and other system status and control 

functions.
The RA-6006 features a 32 character, 16x2 LCD display with LED’s 

for Power, Alarm, Supervisory, Trouble, and Silenced conditions. 

It can be mounted on a single gang electrical box or a four square 

electrical box. The annunciator is enclosed in a sheet metal enclosure 

and has a Potter lock securing the keypad. 

Figure 1: RA-6006 Class B Wiring Example

Features

Standby Current 

20 mA

Alarm Current 

25 mA

Operating Temperature  0°C-49°C (32°F-120°F) 10%-93%  

 

@ 30°C (86°F) non-condensing    

 

humidity

Maximum Wire Length  6500 FT

Maximum Annunciators  31

Dimensions (WxHxD)  8” x 6-1/4” x 1-5/8” (Cabinet)
Wire Gauge 

14 AWG-22 AWG

Display 

2 lines x 16 characters

Product includes 5 year warranty

Installation

The RA-6006 is connected to the PFC-6006 using a four wire RS-485 

connection. The connection is power limited and supervised. Up to 

four (4) RA-6006 LCD annunciators can be connected using Class B 

wiring. 

DIP SWITCH

A

B

+

-

Address Settings

The RA-6006 address 

is set by dip switch S1 

located on the back of the 

RA-6006. The address 

must be set in the 

range of 1 to 31 to be 

recognized by the control 

panel.

Figure 2: RA-6006 (back panel view)

Canadian listed remote annunciator for the Potter 

PFC-6006 Sprinkler Monitoring Panel.