MFG. #5406081 - REV A
7/13
PRINTED IN USA
PAGE 1 OF 2
RA-6006
LCD ANNUNCIATOR INSTALLATION
Potter Electric Signal Company, LLC • St. Louis, MO • Cust Service: 866-956-1211 • Tech Support: 866-240-1870 • Canada: 888-882-1833
• www.pottersignal.com
Install in accordance with compatible fire alarm panel.
Description
The RA-6006 is a LCD remote annunciator for the PFC-6006
Sprinkler Monitoring Panel. The RA-6006 communicates using a
RS-485 connection to the main panel providing common indication
of Alarms, Supervisory, Trouble and other system status and control
functions.
The RA-6006 features a 32 character, 16x2 LCD display with LED’s
for Power, Alarm, Supervisory, Trouble, and Silenced conditions.
It can be mounted on a single gang electrical box or a four square
electrical box. The annunciator is enclosed in a sheet metal enclosure
and has a Potter lock securing the keypad.
Figure 1: RA-6006 Class B Wiring Example
Features
Standby Current
20 mA
Alarm Current
25 mA
Operating Temperature 0°C-49°C (32°F-120°F) 10%-93%
@ 30°C (86°F) non-condensing
humidity
Maximum Wire Length 6500 FT
Maximum Annunciators 31
Dimensions (WxHxD) 8” x 6-1/4” x 1-5/8” (Cabinet)
Wire Gauge
14 AWG-22 AWG
Display
2 lines x 16 characters
Product includes 5 year warranty
Installation
The RA-6006 is connected to the PFC-6006 using a four wire RS-485
connection. The connection is power limited and supervised. Up to
four (4) RA-6006 LCD annunciators can be connected using Class B
wiring.
DIP SWITCH
A
B
+
-
Address Settings
The RA-6006 address
is set by dip switch S1
located on the back of the
RA-6006. The address
must be set in the
range of 1 to 31 to be
recognized by the control
panel.
Figure 2: RA-6006 (back panel view)
Canadian listed remote annunciator for the Potter
PFC-6006 Sprinkler Monitoring Panel.
firealarmresources.com