PRESSURE SWITCH

Installation

The Potter PS10 Series Pressure Actuated Switches are designed for the 

detection of a waterflow condition in automatic fire sprinkler systems of 

particular designs such as wet pipe systems with alarm check valves, dry 

pipe, preaction, or deluge valves.  The PS10 is also suitable to provide a 

low pressure supervisory signal; adjustable between 0,27 and 1,03 BAR (4 

and 15PSI). 

1. Apply Teflon tape to the threaded male connection on the device.                                        

    (Do not use pipe dope)
2. Device should be mounted in the upright position (threaded connection down).
3. Tighten the device using a wrench on the flats on the device.  

 

 

 

 

 

 

 

 

 

Wiring Instructions  

 

 

 

 

1. Remove the tamper resistant screw with the special key provided. 

2. Carefully place a screwdriver on the edge of the knockout and sharply 

apply a force sufficient to dislodge the knockout plug. See Fig 9 

 

3. Run wires through an approved conduit connector and affix the connector 

to the device. 

 

 

 

 

 

 

4. Connect the wires to the appropriate terminal connections for the service 

intended.  See Figures 2,4,5, and 6. See Fig 7 for two switch, one conduit 

wiring.                                                                                          

 

 

 

Testing:  

The operation of the pressure alarm switch should be tested upon 

completion of installation and periodically thereafter in accordance with the 

applicable NFPA codes and standards and/or the authority having jurisdiction 

(manufacturer recommends quarterly or more frequently). 

 

 

 

 

 

 

 

 

 

Wet System

  

 

 

 

 

 

METHOD 1:  When using PS10 and control unit with retard - connect PS10 

into alarm port piping on the input side of retard chamber and electrically 

connect PS10 to control unit that provides a retard to compensate for surges. 

UL,  cUL,  and  CSFM  Listed,  FM  and  LPC  Approved,  NYMEA 

Accepted, CE Marked 
Dimensions: 

(9,6cm) 3.78" W x (8,1cm) 3.20" D x (10,7cm) 4.22" H

Conduit Entrance: 

Two knockouts provided for 1/2" conduit.  Individual  

  

 

switch compartments and ground screws suitable for  

 

 

dissimilar voltages.

Enclosure:    

Cover - Die-cast with textured red powdercoat finish, single

                       cover screw and rain lip.
                       Base - Die-cast                                                     

Pressure Connection: 

Nylon 1/2" NPT Male

Factory Adjustment: 

 0,27 - 0,55 BAR (4 - 8 PSI)

Differential:  

0,13 BAR (2 PSI) typical

Maximum System Pressure:  

17,2 BAR (250 PSI)

Switch Contacts: 

 SPDT (Form C)  

                               10.1 Amps at 125/250VAC, 2.0 Amps at 30VDC

                               One SPDT in PS10-1, Two SPDT in PS10-2

Environmental Specifications:  

 

 

 

 

 

 

NEMA 4/IP66 Rated Enclosure - indoor or outdoor when used   

 

with NEMA 4 conduit fittings.

 

Temperature range: -40°C to 60°C (-40° - 140°F)   

Potter Electric Signal Company • St. Louis, MO • Customer Service: 866-572-3005 • Tech Support: 866-956-0988 • Canada 888-882-1833 • www.pottersignal.com

Insure that no unsupervised shut-off valves are present between the alarm 

check valve and PS10.
METHOD 2:  When using the PS10 for local bell application or with a control 

that does not provide a retard feature - the PS10 must be installed on the alarm 

outlet side of the retard chamber of the sprinkler system.
TESTING:  Accomplished by opening the inspector's end-of-line test valve. 

Allow time to compensate for system or control retard.  

         

NOTE:  Method 2 is not applicable for remote station service use, if there 

is an unsupervised shut-off valve between the alarm check valve and the 

PS10. 

 

Wet System With Excess Pressure 

 

 

Connect PS10A into alarm port piping extending from alarm check valve. 

Retard  provisions  are  not  required.    Insure  that  no  unsupervised  shut-off 

valves are present between the alarm check valve and the PS10.  

 

TESTING:  Accomplished by opening the water by-pass test valve or the 

inspector's end-of-line test valve. When using end-of-line test, allow time 

for excess pressure to bleed off.

 

 

 

 

 

 

 

 

Dry System

 

 

 

 

 

 

Connect  PS10  into  alarm  port  piping  that  extends  from  the  intermediate 

chamber of the alarm check valve.  Install on the outlet side of the in-line 

check valve of the alarm port piping.  Insure that no unsupervised shut-off 

valves are present between the alarm check valve and the PS10.  

 

TESTING: Accomplished by opening the water by-pass test valve.

Note:

  The above tests may also activate any other circuit closer or water 

motor gongs that are present on the system.

Service Use:

 

Automatic Sprinkler 

NFPA-13

 

One or two family dwelling 

NFPA-13D

 

Residential Occupancy up to four stories 

NFPA-13R

 

National Fire Alarm Code 

NFPA-72

Tamper:

 Cover incorporates tamper resistant fastener that requires a special key 

for removal.  One key is supplied with each device. For optional cover tamper 

switch kit, order Stock No. 0090200. See bulletin #5401200 PSCTSK.

Models: 

PS10-1 VDS 

 

 

 

 

 

PS10-2 VDS

Содержание PS10 Series

Страница 1: ...al 0 13 BAR 2 PSI typical Maximum System Pressure 17 2 BAR 250 PSI Switch Contacts SPDT Form C 10 1 Amps at 125 250VAC 2 0 Amps at 30VDC One SPDT in PS10 1 Two SPDT in PS10 2 Environmental Specifications NEMA 4 IP66 Rated Enclosure indoor or outdoor when used with NEMA 4 conduit fittings Temperature range 40 C to 60 C 40 140 F PotterElectricSignalCompany St Louis MO CustomerService 866 572 3005 Te...

Страница 2: ...TER BY PASS VALVE WET SYSTEM WITHOUT EXCESS PRESSURE WATER MOTOR GONG WET SYSTEM ALARM CHECK VALVE OS Y VALVE RBVS WATER BY PASS VALVE RETARD PS10 DRY SYSTEM ALARM CHECK VALVE OS Y VALVE WATER BY PASS VALVE CHECK VALVE RBVS DRY SYSTEM PS10 WATER MOTOR GONG DWG 923 2AA Fig 2 Fig 4 Fig 5 Fig 3 NOTE To prevent leakage apply Teflon tape sealant to male threads only ADJUSTMENT KNOB 2 87 72 97 4 22 107 ...

Страница 3: ...nderstand instructions could result in improper operation of device resulting in serious injury or death Risk of explosion Not for use is hazardous locations Serious injury or death could result Do not tighten by grasping the switch enclosure Use wrenching flats on the bushing only Failure to install properly could damage the switch and cause improper operation resulting in damage to equipment and...

Страница 4: ...l be factory adjusted Ordering Information Model Description Stock No PS10 1 Pressure switch with one set SPDT contacts 1320011 PS10 2 Pressure switch with two sets SPDT contacts 1320021 Hex Key 5250062 Cover Tamper Switch Kit 0090200 to operate on a pressure increase of 0 27 0 55 BAR 4 8 PSI Pressure switch shall have one or two form C contacts switch contact rating 10 1 Amps at 125 250 VAC 2 0 A...

Страница 5: ...wei SPDT beim PS10 2 Umgebungsspezifikationen NEMA 4 IP66 klassifiziertes Gehäuse Innen oder Außeneinsatz mit gemäß NEMA 4 klassifiziertem Rohrleitungszubehör Temperaturbereich 40 C bis 60 C 40 bis 140 F Potter Electric Signal Company St Louis MO Customer Service 866 572 3005 Tech Support 866 956 0988 Canada 888 882 1833 www pottersignal com integriertundelektrischmitderSteuereinheitverbunden dief...

Страница 6: ... VENTIL NASSAN LAGE ALARM VENTIL NASSAN LAGE ALARM VENTIL TROCKEN ANLAGE OS Y VENTIL BEIPASS VENTIL WASSER DURCHFLUSS BEIPASS VENTIL WASSER DURCHFLUSS OS Y VENTIL BEIPASS VENTIL WASSER DURCHFLUSS OS Y VENTIL NASSANLAGE OHNE ÜBERDRUCK RBVS VERZÖGERUNG PS10 RÜCK SCHLAG VENTIL RBVS TROCKENANLAGE PS10 DWG 923 2AA WASSERTURBINE MIT GONG HINWEIS Bringen Sie an den Außengewinden Teflonband an um Leckagen...

Страница 7: ...d Bestimmungen durchgeführt werden Es besteht Stromschlaggefahr Schalten Sie vor Wartungsarbeiten die Stromversorgung ab Anderenfalls könnten Sie schwer verletzt oder getötet werden Lesen Sie vor Beginn der Installation alle Anweisungen sorgfältig durch Bewahren Sie die Anweisungen zur künftigen Verwendung auf Das Nichtlesen und beachten der Anweisungen könnte zum fehlerhaften Betrieb des Geräts f...

Страница 8: ...ckschalter hat einen oder zwei Form C Kontakte Die Bestellinformationen Modell Beschreibung Produktnr PS10 1 Druckschalter mit einem Satz SPDT Kontakte 1320011 PS10 2 Druckschalter mit zwei Sätzen SPDT Kontakte 1320021 Inbusschlüssel 5250062 Manipulationsschalter für Abdeckung 0090200 Techniker Architektenspezifikationen Druckschalter Für Wasserdurchfluss Schalterkontakte sind auf 10 1 A bei 125 2...

Страница 9: ...Mouser Electronics Authorized Distributor Click to View Pricing Inventory Delivery Lifecycle Information AMSECO PS 10 EX ...

Отзывы: