background image

INSTALLATION MANUAL:  PAD200-DUCT ANALOG ADDRESSABLE DUCT DETECTOR

Document 5406428-A  02/21

Potter Electric Signal Company, LLC           •           St. Louis, MO             •           Phone: (800) 325-3936               •            www.pottersignal.com

 

PAGE 4 OF 4

MOUNTING: 

After securing the sampling and exhaust tubes to the duct smoke unit, (or initially placing the tubes through the 1¼” 

holes drilled or punched in the HVAC duct to accept the inlet sampling and exhaust tubes and then attaching them to the duct unit), 

hold the duct unit assembly in position and use (2) # 12 X ½” sheet metal screws (packaged in the installation kit) to secure the 

duct smoke detector to the HVAC duct.

AIR SAMPLING VERIFICATION: 

To ensure correct operation of the duct unit use a Magnehelic differential pressure gauge, Dwyer 

2000 or 4000 Series (or equivalent) to determine the differential pressure between the inlet (high side) and exhaust (low side) 

tubes. The differential pressure between the two tubes should be greater than 0.01 inches of water and less than 1.2 inches of 

water.

Note:

 For proper operation, the velocity adaptor insert must be installed for air velocities of 100 to 4000 feet per minute. This 

adaptor comes installed but can be removed in order to service the detector head. The adaptor must be reinstalled after the 

detector head service is complete.

6.  Operational Testing

When the PAD200-DUCT is under normal condition in standby mode, the alarm indicator LEDs on the detector head will pulse 

approximately once every 4 seconds.

Note

: When a panel is configured to not flash LEDs, the LEDs on the detectors will not flash at any time.

7.  Functional Testing

Note:

 Be sure to dis-engage all alarm signal services, releasing devices and extinguishing systems, prior to performing the 

following test, except automatic testing by the FACP. Be sure to re-engage these systems when all testing is complete.

8.  Walk Test

The FACP must be placed into Walk Test Mode and follow the steps below. Use the appropriate steps outlined below for the 

detector that is to be tested.

Notes:

• 

Failure to alarm during a test indicates a defective detector. Replace detector immediately.

• 

PAD200-DUCT – Use ANSI/UL listed aerosol such as Home Safeguard Model 25S and SDi Smoke Centurion as 

acceptable to the Authority Having Jurisdiction (AHJ).

• 

Insert the test gas nozzle into the test port on the unit cover.

9.  Maintenance

The detector should be cleaned as needed. Detectors installed in environments more prone to dust may need cleaning based on 

build-up of dust. Clean unit by removing cover and using soft cloth, vacuum or dry compressed air. Clean sensing tubes as needed 

to allow for the free flow of air through both inlet and exhaust tubes.

Consult your local code and AHJ requirements for required maintenance schedules.

These instructions do not purport to cover all the details or variations in the equipment described, nor provide for 

every possible contingency to be met in connection with installation, operation and maintenance.

Specifications subject to change without prior notification.

For Technical Assistance contact Potter Electric Signal Company at 866-956-1211.

Actual performance is based on proper application of the product by a qualified professional.
Should further information be desired or should particular problems arise, which are not covered sufficiently for 

the purchaser's purpose, the matter should be referred to a distributor in your region.

Содержание PAD200-DUCT

Страница 1: ...e ordered Sampling tubes are supplied in three standard lengths 2 5 ft 5 ft and 10 ft and cut to size to fit the duct Mounting the duct smoke unit is accomplished by the use of a template and 2 sheet metal screws which are provided Mounting can be achieved without the removal of the clear cover which is secured by 4 capture screws 2 Setting the Address All PAD protocol detectors and modules requir...

Страница 2: ...ir Velocity 100 to 4000 ft min Ambient Temperature 32 to 120 F 0 to 49 C Humidity 10 to 85 Relative humidity non condensing Housing Material Plastic backbox clear plastic cover Finish Gray backbox with clear cover Dimensions 13 1 2 L x 4 1 2 W x 2 1 4 D Maximum Net Weight 2 lbs Sampling Tubes 2 5 ft 5 ft or 10 ft Sampling Tube Part Numbers 2 5 1000274 5 1000275 10 1000276 4 Wiring Diagram The wiri...

Страница 3: ...e alarms the duct detector should not be mounted in areas of extreme high or low temperatures in areas where high humidity exists or in areas where the duct may contain gases or excessive dust SAMPLING TUBE ASSEMBLY The PAD200 DUCT duct smoke detectors employ a specially notched sampling tube which may be ordered separately in one of four 4 standard lengths STN 1 0 For duct widths of 6 TO 1 0 STN ...

Страница 4: ...te Be sure to dis engage all alarm signal services releasing devices and extinguishing systems prior to performing the following test except automatic testing by the FACP Be sure to re engage these systems when all testing is complete 8 Walk Test The FACP must be placed into Walk Test Mode and follow the steps below Use the appropriate steps outlined below for the detector that is to be tested Not...

Отзывы: