![Potter PAD100-6DB Скачать руководство пользователя страница 4](http://html.mh-extra.com/html/potter/pad100-6db/pad100-6db_quick-start-manual_1582974004.webp)
10c. Specifications / Ratings for Use with Detector Bases: PAD100-6DB, PAD100-4DB
No.
Item
PAD100-6DB
PAD100-4DB
1
Installation Temperature Range
32
O
to 150
O
F (0
O
to 66
O
C)
2
Operating Relative Humidity Range
0% - 93% (non-condensing)
3
Weight (without detector head)
87 g (3.07 oz)
52g (1.83 oz)
4
Dimensions (without
detector head)
Height
0.75 in (19 mm)
0.72 in (18 mm)
Diameter
6.3 in (166 mm)
3.93 in (100 mm)
5
Approvals / Listings
ANSI/UL 268, ANSI/UL 521, ANSI/UL 2075
* The standby current is the current that the device consumes when the device is in a non-activated condition and where no communication current is transmitted to the FACP.
** Reference spacing requirements in Section 4.
10a. Specifications / Ratings for Use with Detectors: PAD100-PD, PAD200-PD, PAD200-PCD, PAD200-PCHD, PAD100-PHD and PAD200-PHD
No.
Item
PAD100-HD
PAD100-CD
1
Working Voltage Range
24 VDC
2
Standby Current (*)
300 µA
3
Alarm Indicator
1 LED
4
Alarm Indictor Current
1.4 mA
5
Alarm Set-Point Range (**)
135
O
to 174
O
F
(57
O
to 79
O
C)
175
O
to 185
O
F
(80
O
to 85
O
C)
135
O
to 160
O
F
(57
O
to 71
O
C)
Fixed 70, 150, 400 PPM
6
Installation Temperature Range
32
O
to 100
O
F
(0
O
to 38
O
C)
32
O
to 150
O
F
(0
O
to 66
O
C)
32
O
to 100
O
F
(0
O
to 38
O
C)
32
O
to 100
O
F (0
O
to 38
O
C)
7
Operating Relative Humidity Range
0% to 93% (non-condensing)
8
Start-up Time
1 second
9
Maximum Number of Addresses per SLC Loop
127
10
Maximum Number of Lighted
Indicators in Alarm per SLC Loop
30
11
Weight (without base)
82 g (2.89 oz)
92 g (3.25 oz)
12
Dimensions
(without base)
Height
1.94 in (49 mm)
1.43 in (36 mm)
Diameter
3.93 in. (100 mm)
13
Approvals / Listings
ANSI/UL 521
ANSI/UL 2075
14
Permitted Mounting Location(s)
Ceiling, Wall
10b. Specifications / Ratings for Use with Detectors: PAD100-CD , PAD100-HD
No.
Item
PAD100-PD
PAD100-PHD
PAD200-PCD
PAD200-PCHD
PAD200-PD
PAD200-PHD
1
Working Voltage Range
24 VDC
2
Standby Current (*)
300 µA
3
Alarm Indicator
1 LED
4
Alarm Indictor Current
1.4 mA
5
Smoke Sensitivity Range (**)
1.0-3.7 %/ft.
(3.2-11.6%/m)
1.0-3.7 %/ft.
(3.2-11.6%/m) /
135
O
to 174
O
F
(57
O
to 79
O
C)
1.1-3.5 %/ft.
(3.6-11%/m)
1.1-3.5 %/ft.
(3.6-11%/m) /
135
O
to 174
O
F
(57
O
to 79
O
C)
1.1-3.5 %/ft.
(3.6-11%/m)
1.1-3.5 %/ft.
(3.6-11%/m) /
135
O
to 174
O
F
(57
O
to 79
O
C)
6
Installation Temperature Range
32
O
to 120
O
F
(0
O
to 49
O
C)
32
O
to 115
O
F
(0
O
to 46
O
C)
32
O
to 120
O
F
(0
O
to 49
O
C)
32
O
to 115
O
F
(0
O
to 46
O
C)
32
O
to 120
O
F
(0
O
to 49
O
C)
32
O
to 115
O
F
(0
O
to 46
O
C)
7
Operating Relative Humidity Range
0% to 93% (non-condensing)
8
Start-up Time
1 second
9
Maximum Number of Addresses per SLC Loop
127
10
Maximum Number of Lighted
Indicators in Alarm per SLC Loop
30
11
Weight (without base)
110.5 g (3.9 oz)
116 g (4.1 oz)
113 g (4.0 oz)
118.5 g (4.2 oz)
110.5 g (3.9 oz)
116 g (4.1 oz)
12
Dimensions
(without base)
Height
1.35 in (34 mm)
1.94 in (49 mm)
1.35 in (34 mm)
1.94 in (49 mm)
1.35 in (34 mm)
1.94 in (49 mm)
Diameter
3.93 in. (100 mm)
13
Approvals / Listings
ANSI/UL 268 6th
edition
ANSI/UL 268 6th
edition,
ANSI/UL 521 7th
edition
ANSI/UL 268 7th
edition,
ANSI/UL 2075 4th
edition
ANSI/UL 268 7th
edition,
ANSI/UL 521 7th
edition, ANSI/UL
2075 4th edition
ANSI/UL 268 7th
edition
ANSI/UL 268 7th
edition,
ANSI/UL 521 7th
edition
14
Permitted Mounting Location(s)
Ceiling, Wall