10c. Specifications / Ratings for Use with Detector Bases: PAD100-6DB, PAD100-4DB 

No.

Item

PAD100-6DB

PAD100-4DB

1

Installation Temperature Range

32

O

 to 150

O

 F (0

O

 to 66

O

 C)

2

Operating Relative Humidity Range

0% - 93% (non-condensing)

3

Weight (without detector head)

87 g (3.07 oz)

52g (1.83 oz)

4

Dimensions (without 

detector head)

Height

0.75 in (19 mm)

0.72 in (18 mm)

Diameter

6.3 in (166 mm)

3.93 in (100 mm)

5

Approvals / Listings

ANSI/UL 268, ANSI/UL 521, ANSI/UL 2075

*   The standby current is the current that the device consumes when the device is in a non-activated condition and where no communication current is transmitted to the FACP.

**  Reference spacing requirements in Section 4.

10a. Specifications / Ratings for Use with Detectors: PAD100-PD, PAD200-PD, PAD200-PCD, PAD200-PCHD, PAD100-PHD and PAD200-PHD

No.

Item

PAD100-HD

PAD100-CD

1

Working Voltage Range

24 VDC

2

Standby Current (*)

300 µA

3

Alarm Indicator

1 LED

4

Alarm Indictor Current

1.4 mA

5

Alarm Set-Point Range (**)

135

O

 to 174

F

(57

O

 to 79

O

 C)

175

O

 to 185

O

 F

(80

O

 to 85

O

 C)

135

O

 to 160

O

 F

(57

O

 to 71

O

 C)

Fixed 70, 150, 400 PPM

6

Installation Temperature Range

32

O

 to 100

O

 F

(0

O

 to 38

O

 C)

32

O

 to 150

O

 F

(0

O

 to 66

O

 C)

32

O

 to 100

O

 F

(0

O

 to 38

O

 C)

32

O

 to 100

O

 F (0

O

 to 38

O

 C)

7

Operating Relative Humidity Range

0% to 93% (non-condensing)

8

Start-up Time

1 second

9

Maximum Number of Addresses per SLC Loop

127

10

Maximum Number of Lighted 

Indicators in Alarm per SLC Loop

30

11

Weight (without base)

82 g (2.89 oz)

92 g (3.25 oz)

12

Dimensions 

(without base)

Height

1.94 in (49 mm)

1.43 in (36 mm)

Diameter

3.93 in. (100 mm)

13

Approvals / Listings

ANSI/UL 521

ANSI/UL 2075

14

Permitted Mounting Location(s)

Ceiling, Wall

10b.  Specifications / Ratings for Use with Detectors: PAD100-CD , PAD100-HD

No.

Item

PAD100-PD

PAD100-PHD

PAD200-PCD

PAD200-PCHD

PAD200-PD

PAD200-PHD

1

Working Voltage Range

24 VDC

2

Standby Current (*)

300 µA

3

Alarm Indicator

1 LED

4

Alarm Indictor Current

1.4 mA

5

Smoke Sensitivity Range (**)

1.0-3.7 %/ft.  

(3.2-11.6%/m)

1.0-3.7 %/ft.  

(3.2-11.6%/m) /

135

O

 to 174

O

F  

(57

O

 to 79

O

 C)

1.1-3.5 %/ft.  

(3.6-11%/m)

1.1-3.5 %/ft.  

(3.6-11%/m) /

135

O

 to 174

O

F  

(57

O

 to 79

O

 C)

1.1-3.5 %/ft.  

(3.6-11%/m)

1.1-3.5 %/ft.  

(3.6-11%/m) /

135

O

 to 174

O

F  

(57

O

 to 79

O

 C)

6

Installation Temperature Range

32

O

 to 120

O

 F

(0

O

 to 49

O

 C)

32

O

 to 115

O

 F

(0

O

 to 46

O

 C)

32

O

 to 120

O

 F

(0

O

 to 49

O

 C)

32

O

 to 115

O

 F

(0

O

 to 46

O

 C)

32

O

 to 120

O

 F

(0

O

 to 49

O

 C)

32

O

 to 115

O

 F

(0

O

 to 46

O

 C)

7

Operating Relative Humidity Range

0% to 93% (non-condensing)

8

Start-up Time

1 second

9

Maximum Number of Addresses per SLC Loop

127

10

Maximum Number of Lighted 

Indicators in Alarm per SLC Loop

30

11

Weight (without base)

110.5 g (3.9 oz)

116 g (4.1 oz)

113 g (4.0 oz)

118.5 g (4.2 oz)

110.5 g (3.9 oz)

116 g (4.1 oz)

12

Dimensions 

(without base)

Height

1.35 in (34 mm)

1.94 in (49 mm)

1.35 in (34 mm)

1.94 in (49 mm)

1.35 in (34 mm)

1.94 in (49 mm)

Diameter

3.93 in. (100 mm)

13

Approvals / Listings

ANSI/UL 268 6th 

edition

ANSI/UL 268 6th 

edition,  

ANSI/UL 521 7th 

edition

ANSI/UL 268 7th 

edition,

ANSI/UL 2075 4th 

edition

ANSI/UL 268 7th 

edition,  

ANSI/UL 521 7th 

edition, ANSI/UL 

2075 4th edition

ANSI/UL 268 7th 

edition

ANSI/UL 268 7th 

edition,  

ANSI/UL 521 7th 

edition

14

Permitted Mounting Location(s)

Ceiling, Wall

Содержание PAD100-6DB

Страница 1: ...normally Disconnect power to the SLC until the detectors are installed 1 Wire the detector bases according to Field Wiring Diagrams 2 Use the dip switches SECTION 11 to set address es 1 127 for each detector head NOTICE THE DETECTORS AND THE PAD100 MODULES MUST HAVE INDIVIDUAL ADDRESS ES 3 To install the detector head onto the base match the detector heads to the base using the alignment feature a...

Страница 2: ...cation when the detectors should be cleaned NOTICE THE DETECTOR IS NOT WASHABLE DO NOT SUBMERGE THE DETECTOR IN WATER WATER CAN AFFECT THE SENSOR CAUSING PERMANENT DAMAGE DO NOT SPRAY CLEANING CHEMICALS OR INSECT SPRAYS DIRECTLY ON OR NEAR THE DETECTOR DO NOT PAINT OVER THE DETECTOR DOING SO MAY CAUSE PERMANENT DAMAGE a PAD100 PHD PAD200 PHD PAD200 PCD PAD200 PCHD PAD100 HD and PAD100 CD When clea...

Страница 3: ...te side of closed doors may not reach the detector Keep supplied dust cover in place during installation and construction Remove dust cover prior to operation Dust cover is not a substitute for removal of detector during new construction or remodeling The detector cannot detect smoke when the dust cover is in place Never use an open flame of any kind to test your device You may ignite and damage t...

Страница 4: ...Dimensions without base Height 1 94 in 49 mm 1 43 in 36 mm Diameter 3 93 in 100 mm 13 Approvals Listings ANSI UL 521 ANSI UL 2075 14 Permitted Mounting Location s Ceiling Wall 10b Specifications Ratings for Use with Detectors PAD100 CD PAD100 HD No Item PAD100 PD PAD100 PHD PAD200 PCD PAD200 PCHD PAD200 PD PAD200 PHD 1 Working Voltage Range 24 VDC 2 Standby Current 300 µA 3 Alarm Indicator 1 LED 4...

Страница 5: ...Electric Signal Company LLC This warranty does not transfer to subsequent owners or purchasers of this appliance This warranty also does not apply to consumable parts such as batteries cosmetic damage including but not limited to scratches or dents defects caused by normal wear and tear or otherwise due to the normal aging of the appliance or if any serial number has been removed or defaced from t...

Отзывы: