7. Locking Feature

The PAD100-PD, PAD200-PD, PAD100-PHD, PAD200-PHD, PAD200-PCD, 

PAD200-PCHD, PAD100-HD and PAD100-CD include a tamperproof feature 

that locks the detector and does not allow removal without the use of a tool.

1.   Once the detector has been installed the detector locks into the base.  

To remove the detector from the base, insert a small screwdriver  

into the slot on the detector (FIGURE 6) and push the plastic tab while 

simultaneously turning the detector head counter-clockwise.

2.  The locking feature can be disabled.  To disable the locking feature, 

  break off the locking tab before installation (FIGURE 7).

8. Detector Base Options

NOTE: 

  Installation instructions for PAD100-DUCTR, reference docment  

  number 5406321-A. 

  Installation instructions for PAD100-DUCT, reference document  

  number 5406322-A. 

  Installation instructions for PAD200-DUCTR, reference docment  

  number 5406429-A. 

  Installation instructions for PAD200-DUCT, reference document  

  number 5406428-A. 

9.  

  Detector will not operate without electrical power.  Fire can cause 

  power interruption, discuss with a fire protection specialist for 

  additional safeguards.

  

Do not open PAD100-PHD, PAD200-PHD, PAD100-HD PAD200-PCD, 

PAD200-PCHD, or PAD100-CD  

detector for cleaning.  If the detector is opened, product warranty 

becomes void.

  If the detector does not work properly, do not try and fix it yourself.   

  This will void your warranty.  For techincal assistance, contact 

  Potter Electric Signal Company at 866-956-1211 for instructions to 

  return a detector that does not operate properly.

  Detector will not sense fires that start in areas where smoke or heat 

  cannot reach the detector.  Smoke or heat from fires in walls, roofs 

  or on the opposite side of closed doors may not reach the detector.

 

Keep supplied dust cover in place during installation and construction.  

  Remove dust cover prior to operation.  

  Dust cover is not a substitute for removal of detector during new 

  construction or remodeling.

  The detector cannot detect smoke when the dust cover is in place.

  Never use an open flame of any kind to test your device.  You may 

  ignite and damage the detector.  

  Do not cover, tape or otherwise block the openings of your detector.  

  The openings are designed to allow air to pass through the detector, 

  thus sampling the air around the detector.

  Detectors are not to be used with detector guards unless the 

  combination has been evaluated by a nationally recognized testing 

  laboratory and found suitable for that purpose.

  To ensure proper operation, store detector within the 

  recommended ranges.  Allow the detector to stabilize to room 

  temperature before applying power. 

  If the detector ever fails to test properly, replace it immediately.  

  Products under warranty may be returned to the manufacturer for 

  replacement, see LIMITED WARRANTY.

 

For technical assistance, contact Potter Electrical Signal Company at 

  1-866-956-1211

WARNING

!

FIGURE 6: Locking Feature

Insert small 

screwdriver into slot 

to remove detector 

from base

FIGURE 7: Disable Locking Feature

Break off tab (gray area) in image 

to disable locking feature.

Model

Description

PAD100-6DB

6 inch detector base.  

PAD100-4DB

4 inch detector base.  

PAD100-IB

6 inch detector base with short circuit isolator.  

See manual number: 550-0671-000

PAD100-RB

6 inch detector base with relay module.  

See manual number: 550-0671-000 

PAD100-SB

6 inch detector base with sounder module.  

See manual number: 550-0671-000 

PAD100-LFSB

6 inch detector base with low frequency sounder module.

See manual number: 550-0706-000

PAD100-SPKB 6 inch detector base with speaker module.  

See manual number: 550-0706-000

Содержание PAD100-6DB

Страница 1: ...normally Disconnect power to the SLC until the detectors are installed 1 Wire the detector bases according to Field Wiring Diagrams 2 Use the dip switches SECTION 11 to set address es 1 127 for each detector head NOTICE THE DETECTORS AND THE PAD100 MODULES MUST HAVE INDIVIDUAL ADDRESS ES 3 To install the detector head onto the base match the detector heads to the base using the alignment feature a...

Страница 2: ...cation when the detectors should be cleaned NOTICE THE DETECTOR IS NOT WASHABLE DO NOT SUBMERGE THE DETECTOR IN WATER WATER CAN AFFECT THE SENSOR CAUSING PERMANENT DAMAGE DO NOT SPRAY CLEANING CHEMICALS OR INSECT SPRAYS DIRECTLY ON OR NEAR THE DETECTOR DO NOT PAINT OVER THE DETECTOR DOING SO MAY CAUSE PERMANENT DAMAGE a PAD100 PHD PAD200 PHD PAD200 PCD PAD200 PCHD PAD100 HD and PAD100 CD When clea...

Страница 3: ...te side of closed doors may not reach the detector Keep supplied dust cover in place during installation and construction Remove dust cover prior to operation Dust cover is not a substitute for removal of detector during new construction or remodeling The detector cannot detect smoke when the dust cover is in place Never use an open flame of any kind to test your device You may ignite and damage t...

Страница 4: ...Dimensions without base Height 1 94 in 49 mm 1 43 in 36 mm Diameter 3 93 in 100 mm 13 Approvals Listings ANSI UL 521 ANSI UL 2075 14 Permitted Mounting Location s Ceiling Wall 10b Specifications Ratings for Use with Detectors PAD100 CD PAD100 HD No Item PAD100 PD PAD100 PHD PAD200 PCD PAD200 PCHD PAD200 PD PAD200 PHD 1 Working Voltage Range 24 VDC 2 Standby Current 300 µA 3 Alarm Indicator 1 LED 4...

Страница 5: ...Electric Signal Company LLC This warranty does not transfer to subsequent owners or purchasers of this appliance This warranty also does not apply to consumable parts such as batteries cosmetic damage including but not limited to scratches or dents defects caused by normal wear and tear or otherwise due to the normal aging of the appliance or if any serial number has been removed or defaced from t...

Отзывы: