background image

1. Description

This document provides instructions for mounting and wiring the Detector 

Base PAD100-6DB and PAD100-4DB.  The following detectors are compatible 

with Detector Base PAD100-6DB and PAD100-4DB.

  PAD200-PD & PAD100-PD: 

Photoelectric Smoke Detector

  PAD200-PHD & PAD100-PHD:   Photoelectric Smoke / Heat Detector

  PAD200-PCD:   

Photoelectric Smoke / CO Detector 

  PAD200-PCHD:    

Photoelectric Smoke / CO Detector/ Heat Detector

  PAD100-HD: 

 

Heat Detector

  PAD100-CD: 

 

Carbon Monoxide Detector

2.  Field Wiring Diagrams

Typical field wiring diagrams for the Signaling Line Circuit (SLC) (FIGURE 1).  

The SLC supports NFPA wiring Class B, A and X.

Typical of NFPA Style B SLC (S+, S-) Wiring using either the PAD100-6DB or 

PAD100-4DB base (FIGURE 1).  In Style A arrangement two separate 

conductors would return from the last detector base to a listed compatible 

Fire Alarm Control Panel (FACP).  In Style X, it is required to use PAD100-IB 

(Addressable Isolator Bases) and typical field diagram is in the PAD100-IB 

Installation Manual.

3. Wiring Instruction

  To ensure proper installation of the detector head to the base, wires 

  shall be dressed properly at the time of installation

  Using PAD100 Bases, observe the correct polarity of SLC wiring.

NOTICE: 

 

THE WIRING TO BE USED SHALL BE IN ACCORDANCE WITH THE 

  PROVISIONS OF ARTICLE 300.3(B) OF THE NATIONAL ELECTRICAL 

  CODE, NFPA 70, AS WELL AS ARTICLE 210.

  THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH 

  THE NATIONAL FIRE PROTECTION ASSOCIATION STANDARD 72.
CAUTION! Break wire runs to provide supervision for connections made to 

each wire pair.
Detector Base Mounting

PAD100-6DB / PAD100-4DB should be mounted directly on the electrical box.  

The PAD100-6DB mounting holes are configured for a single gang, double 

gang, octagon or 4” square box.  The PAD100-4DB mounting holes are 

configured for a 3-1/2” octagon box.  Use a box for each base and run the 

power circuit to all base locations.
Use 12 to 22 AWG conductors to connect to terminals of bases.  It is 

recommended that the SLC conductors be color-coded to avoid wiring errors 

and assist in system troubleshooting.  Improper SLC connections may 

prevent the system from operating normally.  Disconnect power to the SLC 

until the detectors are installed.

1.  Wire the detector bases according to Field Wiring Diagrams.

2.  Use the dip switches (SECTION 11) to set address(es) (1 - 127) for each 

  detector head.  

NOTICE: THE DETECTORS AND THE PAD100 MODULES MUST HAVE 

INDIVIDUAL ADDRESS(ES).
3.  To install the detector head onto the base, match the detector heads 

  to the base using the alignment feature and twist clockwise until the 

  detector heads snap into place (FIGURE 2).

4.  After all detector heads, addressable bases and modules have been 

  installed, apply power to the FACP.

5.  Test the detectors as described in the Testing Section of this manual.
NOTICE:  DO NOT INSTALL DETECTOR HEADS UNTIL AREA HAS BEEN 

THOROUGHLY CLEANED TO REMOVE CONSTRUCTION DEBRIS, DUST, 

ETC., AS REQUIRED BY NFPA 72.  

4. Spacing Limitations

NOTICE: REFER TO NFPA 72 FOR SPECIFIC INFORMATION REGARDING 

DETECTOR SPACING, MOUNTING LOCATION AND SPECIAL APPLICATIONS.
PAD100-PD, PAD200-PD, PAD200-PCD, PAD200-PCHD, PAD100-PHD and 

PAD200-PHD: Photoelectric Smoke Detector

PAD100-PD, PAD200-PD, PAD200-PCD, PAD200-PCHD, PAD100-PHD and PAD200-

PHD are ANSI/UL listed on maximum 30ft spacing limitation with alarm set point 

from 135

O

-174

F on smooth ceiling.  Refer to NFPA 72 for specific information 

regarding detector spacing, placement and special applications.  
PAD100-HD: Heat Detector

The ANSI/UL listed spacing limitations of PAD100-HD smooth ceiling are 

dependent on alarm set point.

5. Testing

Testing shall be performed periodically to determine if each detector 

operates properly.  Detectors will offer maximum performance when tested 

in compliance with NFPA 72.
NOTICE: REFER TO FIRE ALARM CONTROL PANEL (FACP) MANUAL FOR 

OPERATION OF DIRTY VALUE READ / PRINT, ALARM 

SIMULATION AND WALK TEST.

S+

S-

S+

S-

To FACP

Loop (SLC)

First Detector Base

Last Detector Base

Figure 1: Wiring (Style B)

Using PAD100-6DB or PAD100-4DB

Alarm Set-Point

Rate of Rise Spacing

Fixed Temperature Spacing

135

O

 to 174

F

(57

O

 to 79

O

 C)

Maximum 60 ft.

Maximum 60 ft.

175

O

 to 185

F

(80

O

 to 85

O

 C)

Maximum 15 ft.

Maximum 15 ft.

135

O

 to 160

F

(57

O

 to 71

O

 C)

Maximum 70 ft.

Maximum 70 ft.

Manual Number: 550-0622

550-0622-000

550-0622-000

Detector Bases: 

PAD100-6DB & PAD100-4DB
Detectors:

PAD100-PD, PAD100-PHD, PAD200-PD, PAD200-PHD, 

PAD200-PCD, PAD200-PCHD, PAD100-HD and PAD100-CD

FIGURE 2: Assembly of Detector

Alignment Features

Содержание PAD100-6DB

Страница 1: ...normally Disconnect power to the SLC until the detectors are installed 1 Wire the detector bases according to Field Wiring Diagrams 2 Use the dip switches SECTION 11 to set address es 1 127 for each detector head NOTICE THE DETECTORS AND THE PAD100 MODULES MUST HAVE INDIVIDUAL ADDRESS ES 3 To install the detector head onto the base match the detector heads to the base using the alignment feature a...

Страница 2: ...cation when the detectors should be cleaned NOTICE THE DETECTOR IS NOT WASHABLE DO NOT SUBMERGE THE DETECTOR IN WATER WATER CAN AFFECT THE SENSOR CAUSING PERMANENT DAMAGE DO NOT SPRAY CLEANING CHEMICALS OR INSECT SPRAYS DIRECTLY ON OR NEAR THE DETECTOR DO NOT PAINT OVER THE DETECTOR DOING SO MAY CAUSE PERMANENT DAMAGE a PAD100 PHD PAD200 PHD PAD200 PCD PAD200 PCHD PAD100 HD and PAD100 CD When clea...

Страница 3: ...te side of closed doors may not reach the detector Keep supplied dust cover in place during installation and construction Remove dust cover prior to operation Dust cover is not a substitute for removal of detector during new construction or remodeling The detector cannot detect smoke when the dust cover is in place Never use an open flame of any kind to test your device You may ignite and damage t...

Страница 4: ...Dimensions without base Height 1 94 in 49 mm 1 43 in 36 mm Diameter 3 93 in 100 mm 13 Approvals Listings ANSI UL 521 ANSI UL 2075 14 Permitted Mounting Location s Ceiling Wall 10b Specifications Ratings for Use with Detectors PAD100 CD PAD100 HD No Item PAD100 PD PAD100 PHD PAD200 PCD PAD200 PCHD PAD200 PD PAD200 PHD 1 Working Voltage Range 24 VDC 2 Standby Current 300 µA 3 Alarm Indicator 1 LED 4...

Страница 5: ...Electric Signal Company LLC This warranty does not transfer to subsequent owners or purchasers of this appliance This warranty also does not apply to consumable parts such as batteries cosmetic damage including but not limited to scratches or dents defects caused by normal wear and tear or otherwise due to the normal aging of the appliance or if any serial number has been removed or defaced from t...

Отзывы: