4

FFT-1000 INSTALLATION MANUAL-5409205-REV A  4/21

Figure 3. Battery Circuit Connections

Technical Specifications

Standby Current

154 mA

Active Current

255 mA

FFT-1000 Voltage

24V DC

Operating Temperature Range

32° to 120° F (0° to 49°C)

Operating Humidity Range

10% to 93% (non-condensing)

Separation of Circuits - Power Limited, Non-Power Limited, High Voltage Wiring

The main AC power connection is considered high-voltage and non-power limited. The Battery conductors, and the 

low AC and trouble relays are nonpower limited. All remaining circuits are low-voltage, power limited connections. 

Proper separation must be maintained between the circuits listed above. All separations in the different wiring must be 

maintained by at least 0.25 inches and the wire insulation must be for the higher voltage. 

In the panel there are sufficient knock outs located around the periphery of the cabinet to allow the installer to 

maintain power limited and non-power limited connections. 

Phone Circuits

The FFT-1000 is equipped with 24 Class B or 12 Class A phone circuits and can be expanded upon by adding an 

FFT-EXP for an additional 12 Class B or 6 Class A circuits. All circuits are provided with a 5.1K resistor. All phone 

circuits are low voltage, supervised, and power limited. FFT phone circuits are rated 24VDC 60mA max.
Wire Impedance = 50 ohms

Relay Outputs

Figure 4. Panel's Dedicated Relay Outputs

The panels have two dedicated common relays, Trouble and Low AC. 
The contact rating is 24VDC / 3.0A, 125VAC / 3A, Power Factor: 1.0. These outputs are non-power limited and not 

supervised. However, they are power-limited if the power supply to the connected devices is power-limited.

DWG #593-5

Panel

Connections

BATTERY

-

+

12 V 

Battery

-

+

12 V

Battery

-

+

Содержание FFT-1000

Страница 1: ...Installation Manual Document 5409205 Rev A 4 21 Potter Electric Signal Company LLC St Louis MO Customer Service 866 240 1870 Technical Support 866 956 1211 Fax 314 595 6999 For listing information vi...

Страница 2: ...rcuit Voltage Type Power Type AC Connection High Voltage Non Power Limited Battery Connection Low Voltage Non Power Limited Trouble Relay High Voltage Non Power Limited Low AC Relay High Voltage Non P...

Страница 3: ...to connect wire leads for battery connection The battery must be a recognized or listed sealed lead acid battery or equivalent The battery charging voltage is approximately 27 3 VDC and the circuit is...

Страница 4: ...n must be for the higher voltage In the panel there are sufficient knock outs located around the periphery of the cabinet to allow the installer to maintain power limited and non power limited connect...

Страница 5: ...6 500 feet Maximum wire resistance Maximum wiring resistance is based on load Calculate using the following equation Total P Link Alarm Current x Wire Resistance 6 volts Figure 5 P Link Class B and Cl...

Страница 6: ...21 Figure 6 F Link Wiring Example AUX PWR The AUX PWR terminal provides an alternative option to power the FFT 1000 using a 24VDC external power source The AUX PWR input in unsupervised and power limi...

Страница 7: ...d non power limited wiring on the main board as well as within the enclosure Power limited wiring is to remain separated from non power limited by a minimum or 0 25 inches and all cablings should be i...

Страница 8: ...a system by adding the FFT EXP expansion module All phone circuits are shipped with a 5 1K EOL resistor The FFT 1000 is equipped with a proprietary P Link communication bus to operate in conjunction w...

Страница 9: ...OFF 25 30 2 3 OFF OFF ON OFF 31 36 2 4 ON OFF ON OFF 37 42 2 5 OFF ON ON OFF 43 48 2 6 ON ON ON OFF 49 54 3 7 OFF OFF OFF ON 55 60 3 8 ON OFF OFF ON 61 66 3 9 OFF ON OFF ON 67 72 3 10 ON ON OFF ON 73...

Страница 10: ...luminate green When AC is low or not detected the LED will disable GENERAL FAULT The general fault LED is off when no trouble s are indicated The LED will illuminate amber when an active trouble is pr...

Страница 11: ...r 6 Class A phone circuits which are programmable and fully supervised The FFT 1000 can support up six 6 FFT EXP for Class B systems and fourteen 14 FFT EXP for Class A systems The FFT EXP communicate...

Страница 12: ...Standby AH Total AH Efficiency Factor 0 80 Required AH Maximum Allowable Standby Current UL 24 Hour standby time 7 AH 215 A 18 AH 582 A 33 AH 1 082 A 55 AH 1 815 A Important Notes 1 FACP enclosure can...

Страница 13: ...ociated LED on the FSB 24 will flash green indicating an incoming call By selecting the corresponding switch the LED will illuminate solid green indicating the call has been answered Mute When the MUT...

Отзывы: