FFT-1000 INSTALLATION MANUAL-5409205-REV A  4/21

Appendix A: Battery Calculation Worksheets

Description

Quantity

Standby

(mA)

Total

Standby 

(mA)

Alarm

(mA)

Total

Alarm 

(mA)

FFT-1000

1

146 mA

146 mA

255 mA

255 mA

FSB-8

1

4 mA

4 mA

13 mA

13 mA

FSB-24

1

4 mA

27 mA

FFT-EXP

56 mA

166 mA

Total (mA)

Total (ma)

Convert to Amps

x 0.001

Convert to Amps

x 0.001

(*Refer to maximum allowable standby current) Total A:

Total A:

Multiply by standby hours

x____

60 minutes per hour  

Alarm time (minutes)

Example

 

5 minute alarm: enter 12   

10 minute alarm: enter 6

÷ ____

Total Standby AH

Total Alarm AH

+Total Standby AH

Total AH

Efficiency Factor

÷ 0.80

Required AH

*Maximum Allowable Standby Current

 (UL 24-Hour standby time)

7 AH 

.215 A

18 AH 

.582 A

33 AH 

1.082 A

55 AH 

1.815 A

Important Notes:

1)  FACP enclosure can house up to two (2) 18 AH batteries. Larger batteries require accessory 

enclosure, part #SSU00500.

2)  NFPA 72 requires 24 hours of standby power followed by 5 minutes alarm activation.

3)  Door holder circuits configured to disconnect upon AC loss need not be included in the battery 

standby calculation since they will not draw power during that time.  Door holders will contribute to 

standby current draw when AC is present.

4)  Total current must not exceed power supply rating (5.0A).

5)  LED/Relay/IDC-6 current must be accounted for in the battery calculation for the supplying source.

Содержание FFT-1000

Страница 1: ...Installation Manual Document 5409205 Rev A 4 21 Potter Electric Signal Company LLC St Louis MO Customer Service 866 240 1870 Technical Support 866 956 1211 Fax 314 595 6999 For listing information vi...

Страница 2: ...rcuit Voltage Type Power Type AC Connection High Voltage Non Power Limited Battery Connection Low Voltage Non Power Limited Trouble Relay High Voltage Non Power Limited Low AC Relay High Voltage Non P...

Страница 3: ...to connect wire leads for battery connection The battery must be a recognized or listed sealed lead acid battery or equivalent The battery charging voltage is approximately 27 3 VDC and the circuit is...

Страница 4: ...n must be for the higher voltage In the panel there are sufficient knock outs located around the periphery of the cabinet to allow the installer to maintain power limited and non power limited connect...

Страница 5: ...6 500 feet Maximum wire resistance Maximum wiring resistance is based on load Calculate using the following equation Total P Link Alarm Current x Wire Resistance 6 volts Figure 5 P Link Class B and Cl...

Страница 6: ...21 Figure 6 F Link Wiring Example AUX PWR The AUX PWR terminal provides an alternative option to power the FFT 1000 using a 24VDC external power source The AUX PWR input in unsupervised and power limi...

Страница 7: ...d non power limited wiring on the main board as well as within the enclosure Power limited wiring is to remain separated from non power limited by a minimum or 0 25 inches and all cablings should be i...

Страница 8: ...a system by adding the FFT EXP expansion module All phone circuits are shipped with a 5 1K EOL resistor The FFT 1000 is equipped with a proprietary P Link communication bus to operate in conjunction w...

Страница 9: ...OFF 25 30 2 3 OFF OFF ON OFF 31 36 2 4 ON OFF ON OFF 37 42 2 5 OFF ON ON OFF 43 48 2 6 ON ON ON OFF 49 54 3 7 OFF OFF OFF ON 55 60 3 8 ON OFF OFF ON 61 66 3 9 OFF ON OFF ON 67 72 3 10 ON ON OFF ON 73...

Страница 10: ...luminate green When AC is low or not detected the LED will disable GENERAL FAULT The general fault LED is off when no trouble s are indicated The LED will illuminate amber when an active trouble is pr...

Страница 11: ...r 6 Class A phone circuits which are programmable and fully supervised The FFT 1000 can support up six 6 FFT EXP for Class B systems and fourteen 14 FFT EXP for Class A systems The FFT EXP communicate...

Страница 12: ...Standby AH Total AH Efficiency Factor 0 80 Required AH Maximum Allowable Standby Current UL 24 Hour standby time 7 AH 215 A 18 AH 582 A 33 AH 1 082 A 55 AH 1 815 A Important Notes 1 FACP enclosure can...

Страница 13: ...ociated LED on the FSB 24 will flash green indicating an incoming call By selecting the corresponding switch the LED will illuminate solid green indicating the call has been answered Mute When the MUT...

Отзывы: