NOTICE

: TO PREVENT ACCIDENTAL

CANDELA SELECTION CHANGE,

REMOVE THE SCREW FROM THE

UNLOCK POSITION AND PLACE IN THE

LOCK POSITION AFTER THE DESIRED

INTENSITY IS SELECTED.

Adjust candela by turning dial.  Displayed

number will be candela selected.

Instant Voltage Verification 

It is often necessary to confirm the voltage drop along a line of devices. 

The access holes are provided in the back of the terminal block to allow the 

voltage to be measured directly without removing the device. Typically this

would be done at the end of the line to confirm design criteria. Most 

measurements will be taken using the S+ and S- locations although access

is provided to other locations. 

NOTICE:

CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES.

CAUTION:

A jumper card is provided to test for correct

wiring in the supervisory mode only.  DO NOT pass

alarm current through the jumper

.

550-0594

Page 3

RED WIRES

BLACK WIRES

The mounting bracket allows the installer to pre-wire

the system, test for system supervision, remove the

signal head until occupancy, switch out  signals with-

out changing mounting brackets and has locking edge 

connector for snap-in-place installation.

V. CHECKOUT AND TROUBLESHOOTING

1. Supply power to the system control panel.  The auxiliary signaling appliances in the system should not be activated.

2. If the signal is activated:

w

Check all smoke and fire detectors in the system to make sure they have not been activated.

w

Check all wiring connections to make sure the signal detection circuits are not reversed or shorted together.  Check wire color codes and traces.

w

Verify that the jumpers and switches are properly set on both the control module and signal appliance.  If the jumper on the AVSM is removed, the horns will not produce any sound unless 

there is an input to the H+ and H- terminals on the control module.

3. To test the signal appliances, trip the auxiliary panel or activate the alarm circuit at the main control panel or activate one of the fire detection units in the system.  All auxiliary signals should be 

activated.

4. An operational test on this product should be conducted in accordance with National Standards or at a minimum annually and more often if dictated by local and state codes or authorities 

having jurisdiction.

NOTICE:

THESE TESTING PROCEDURES AND TROUBLESHOOTING INSTRUCTIONS ARE GENERALIZED.  PLEASE REFER TO THE SYSTEM CONTROL PANEL OPERATING 

INSTRUCTIONS FOR PROPER OPERATION OF THE PANEL AND FIRE DETECTION SYSTEM.

SIGNALING APPLIANCE LIMITATION:

Your horn and horn/strobe meet or exceed the current audibility requirements of ANSI/UL 464.  However, if the appliance is located outside a bedroom it may not wake up a sound sleeper, 

especially if the room door is closed or only partially open.

THIS APPLIANCE WILL NOT OPERATE WITHOUT ELECTRICAL POWER.  AS FIRES FREQUENTLY CAUSE POWER INTERRUPTIONS, 

POTTER ELECTRIC SUGGESTS YOU DISCUSS FURTHER SAFEGUARDS WITH YOUR LOCAL FIRE PROTECTION SPECIALIST.

VI. TO RETURN AN APPLIANCE

Should you experience problems with your appliance, proceed as follows:

1. Turn off electrical power to the auxiliary alarm circuit.

2. Remove faceplate, then remove mounting screw and slide signal off from bracket.

3. Replace unit that was removed to restore wiring supervision and to eliminate system trouble alert.

4. Carefully pack the defective unit (the manufacturer cannot be responsible for consequential damage due to shipping or mis-handling).  Include your return address and complete details as to 

the nature of the difficulties being experienced and date of installation.

5. Return to: Potter Electric Signaling Company, LLC 1609 Park 370, Hazelwood, MO 63042.  Prior to returning, call the Potter Electric field service department at 1-800-325-3936 to obtain a 

RMA number.

1. SLIDE ONTO BRACKET

2. INSERT MOUNTING SCREW

3. SNAP COVER OVER ASSEMBLY

Switch positions 1 and 2 in the OFF position to select isolated horn and

strobe power inputs.
Switch 3 selects between temporal or non-temporal tone.  ON is temporal.
Switch 4 selects between mechanical or high frequency tone.  ON is 

mechanical.
Switch 5 selects between high or low dBA.  ON is high dBA.

firealarmresources.com

Содержание CS-24 Series

Страница 1: ...wiring clearance 1 Run a minimum 18 gauge insulated 2 or more conductor cable 2 Mount a box for each remote signaling appliance Screw bracket onto box Insert signal into bracket and slide to the right firmly into the terminal block receptacle Insert mounting screw as shown and tighten Cover assembly with the plastic housing NOTICE WIRING SHOULD BE CONNECTED TO MOUNTING BRACKET PRIOR TO MOUNTING SI...

Страница 2: ...ed to power and synchronize the horn place switches 1 and 2 in the OFF position on the CHS 24 CCHS 24A CCHS 24B CCHS 24G CCHS 24R w Choose either continuous horn and allow the FACP to control the horn or choose temporal horn and synchronize the horns with the Potter Electric AVSM synchronization protocol w Use the Potter Electric AVSM synchronization protocol to provide synchronization and mute th...

Страница 3: ...e fire detection units in the system All auxiliary signals should be activated 4 An operational test on this product should be conducted in accordance with National Standards or at a minimum annually and more often if dictated by local and state codes or authorities having jurisdiction NOTICE THESE TESTING PROCEDURES AND TROUBLESHOOTING INSTRUCTIONS ARE GENERALIZED PLEASE REFER TO THE SYSTEM CONTR...

Страница 4: ...ship and materials under normal use and service This warranty does not apply and is void if damage or failure is caused by accident abuse misuse abnormal use faulty installation liquid contact fire earthquake or other external cause operating the appliance outside Potter Electrical Signal Company LLC s published guidelines or service alteration maintenance or repairs performed by anyone other than...

Страница 5: ...le brancher dans la prise du réceptacle Mettre la vis de montage comme illustré puis la serrer Recouvrir l ensemble du boîtier de plastique AVIS LES FILS DOIVENT ÊTRE BRANCHÉS AU SUPPORT AVANT D Y POSER L APPAREIL DE SIGNALISATION LE FIL D ALIMENTATION POSITIF DOIT ÊTRE SCINDÉ EN DEUX CHAQUE PARTIE ÉTANT INSÉRÉE DANS LES DEUX BORNES SUPÉRIEURES SI DEUX FILS D ALIMENTATION SONT ACHEMINÉS À L APPARE...

Страница 6: ...ilisation de l avertisseur dans ce mode et à cette tension n atteint pas le niveau sonore minimum de la norme ANSI UL 464 exigé pour la sécurité incendie publique Ces paramètres conviennent uniquement à une utilisation de l appareil de signalisation pour la sécurité incendie privée Pour les applications publiques utiliser les paramètres dBA les plus élevés Niveaux sonores dB de l avertisseur Pièce...

Страница 7: ...en faire le suivi w S assurer que les cavaliers et les commutateurs sont correctement configurés dans le module de commande et dans les appareils de signalisation Si le cavalier du module AVSM est débranché les avertisseurs ne produiront aucun son à moins qu une entrée soit fournie aux bornes H et H du module de commande 3 Pour vérifier les appareils de signalisation déclencher le panneau auxiliai...

Страница 8: ... emballer soigneusement l appareil pour réduire au minimum les risques de dommage pendant le transport Si nous recevons un appareil endommagé en cours de transport nous vous en aviserons et il vous reviendra d obtenir dédommagement de la part du transporteur Si vous transmettez une demande valable à Potter Electrical Signal Company LLC pendant la période de garantie Potter Electrical Signal Compan...

Отзывы: