NOTICE
: TO PREVENT ACCIDENTAL
CANDELA SELECTION CHANGE,
REMOVE THE SCREW FROM THE
UNLOCK POSITION AND PLACE IN THE
LOCK POSITION AFTER THE DESIRED
INTENSITY IS SELECTED.
Adjust candela by turning dial. Displayed
number will be candela selected.
Instant Voltage Verification
It is often necessary to confirm the voltage drop along a line of devices.
The access holes are provided in the back of the terminal block to allow the
voltage to be measured directly without removing the device. Typically this
would be done at the end of the line to confirm design criteria. Most
measurements will be taken using the S+ and S- locations although access
is provided to other locations.
NOTICE:
CARE SHOULD BE TAKEN TO NOT SHORT THE TEST PROBES.
CAUTION:
A jumper card is provided to test for correct
wiring in the supervisory mode only. DO NOT pass
alarm current through the jumper
.
550-0594
Page 3
RED WIRES
BLACK WIRES
The mounting bracket allows the installer to pre-wire
the system, test for system supervision, remove the
signal head until occupancy, switch out signals with-
out changing mounting brackets and has locking edge
connector for snap-in-place installation.
V. CHECKOUT AND TROUBLESHOOTING
1. Supply power to the system control panel. The auxiliary signaling appliances in the system should not be activated.
2. If the signal is activated:
w
Check all smoke and fire detectors in the system to make sure they have not been activated.
w
Check all wiring connections to make sure the signal detection circuits are not reversed or shorted together. Check wire color codes and traces.
w
Verify that the jumpers and switches are properly set on both the control module and signal appliance. If the jumper on the AVSM is removed, the horns will not produce any sound unless
there is an input to the H+ and H- terminals on the control module.
3. To test the signal appliances, trip the auxiliary panel or activate the alarm circuit at the main control panel or activate one of the fire detection units in the system. All auxiliary signals should be
activated.
4. An operational test on this product should be conducted in accordance with National Standards or at a minimum annually and more often if dictated by local and state codes or authorities
having jurisdiction.
NOTICE:
THESE TESTING PROCEDURES AND TROUBLESHOOTING INSTRUCTIONS ARE GENERALIZED. PLEASE REFER TO THE SYSTEM CONTROL PANEL OPERATING
INSTRUCTIONS FOR PROPER OPERATION OF THE PANEL AND FIRE DETECTION SYSTEM.
SIGNALING APPLIANCE LIMITATION:
Your horn and horn/strobe meet or exceed the current audibility requirements of ANSI/UL 464. However, if the appliance is located outside a bedroom it may not wake up a sound sleeper,
especially if the room door is closed or only partially open.
THIS APPLIANCE WILL NOT OPERATE WITHOUT ELECTRICAL POWER. AS FIRES FREQUENTLY CAUSE POWER INTERRUPTIONS,
POTTER ELECTRIC SUGGESTS YOU DISCUSS FURTHER SAFEGUARDS WITH YOUR LOCAL FIRE PROTECTION SPECIALIST.
VI. TO RETURN AN APPLIANCE
Should you experience problems with your appliance, proceed as follows:
1. Turn off electrical power to the auxiliary alarm circuit.
2. Remove faceplate, then remove mounting screw and slide signal off from bracket.
3. Replace unit that was removed to restore wiring supervision and to eliminate system trouble alert.
4. Carefully pack the defective unit (the manufacturer cannot be responsible for consequential damage due to shipping or mis-handling). Include your return address and complete details as to
the nature of the difficulties being experienced and date of installation.
5. Return to: Potter Electric Signaling Company, LLC 1609 Park 370, Hazelwood, MO 63042. Prior to returning, call the Potter Electric field service department at 1-800-325-3936 to obtain a
RMA number.
1. SLIDE ONTO BRACKET
2. INSERT MOUNTING SCREW
3. SNAP COVER OVER ASSEMBLY
Switch positions 1 and 2 in the OFF position to select isolated horn and
strobe power inputs.
Switch 3 selects between temporal or non-temporal tone. ON is temporal.
Switch 4 selects between mechanical or high frequency tone. ON is
mechanical.
Switch 5 selects between high or low dBA. ON is high dBA.