ADPS

ADJUSTABLE DEADBAND

PRESSURE SWITCH

FIG. 3

ADJUSTMENTS

The two thumb adjustment dials, accessible
through the enclosure cover, are used to
adjust the set point and reset point of the
switch. The dial scales and pointer may be
used to give an indication of the low and high
set points.
The high setting adjustment dial is calibrated
for increasing pressure. The low setting ad-
justment dial is calibrated for decreasing pres-
sure. For best accuracy, make the final ad-
justments with a pressure gauge at the actual
working media pressure and temperature en-
countered in the application.

The minimum deadband (minimum span be-
tween set and reset points) may be obtained
at any point in the operating range of the
switch.
When the desired settings are obtained, re-
place the adjustment cover. The adjustment
cover and enclosure cover can be made
tamper resistant by a single sealing wire
inserted through the hole in the locking bar.
The repeatability of the set and reset points is
typically ±1% of the operating range.

GROUND SCREW

SNAP-ACTION
SPDT SWITCH

MANUAL SWITCH
ACTUATOR FOR

TESTING

LOW SETTING
ADJUSTMENT DIAL

HIGH SETTING
ADJUSTMENT DIAL

ALUMINUM DIECAST BASE

1

4

"-18 NPT FEMALE PRESSURE CONNECTION

(OPTIONAL 

3

8

"-18 NPT FEMALE)

LOCKING BAR

WITH HOLE FOR

SEALING WIRE

ENCLOSURE COVER

ADJUSTMENT

COVER

DWG. #1060-3

DO NOT LOOSEN OR

REMOVE SCREWS

Содержание ADPS Series

Страница 1: ...e entire operating range of the switch The mini mum deadband minimum span between set and reset points may be obtained at any point in the operating range of the switch A change in pressure greater than the high setting will reposition the switch mechanism to open or close a single snap action electrical switch This control device is designed for use as an operating control in applications sensing...

Страница 2: ...ousing into the fitting FIG 1 WIRING Use properly rated temperature supply wire for the anticipated service temperature Make all electrical connections in accordance with the National Electrical Code and local regulations A wiring check may be performed by manually actuating the switch actuator on the side of the snap actionswitchinsidetheenclosure SeeFig 3 NOTE Donotloosenorremovethetwo 2 screws ...

Страница 3: ...ure en countered in the application The minimum deadband minimum span be tween set and reset points may be obtained at any point in the operating range of the switch When the desired settings are obtained re place the adjustment cover The adjustment cover and enclosure cover can be made tamper resistant by a single sealing wire inserted through the hole in the locking bar The repeatability of the ...

Страница 4: ... COPPER 1370020 ADPS 300 1S 25 300 PSIG 12 PSIG 400 PSIG 1 4 NPT 316 S S BERYLLIUM COPPER W 316 S S ISOLATOR 1370030 ADPS 300 2S 25 300 PSIG 12 PSIG 400 PSIG 3 8 NPT 316 S S BERYLLIUM COPPER W 316 S S ISOLATOR 1370040 ADPS 600 1B 50 600 PSIG 25 PSIG 650 PSIG 1 4 NPT BRASS BERYLLIUM COPPER 1370050 ADPS 600 1S 50 600 PSIG 25 PSIG 650 PSIG 1 4 NPT 316 S S BERYLLIUM COPPER W 316 S S ISOLATOR 1370060 A...

Отзывы: